Plan Review Details - Permit 18080466
Plan Review Stops For Permit 18080466
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-11-15 Cont ID  
Sent By dbattles Date 2018-11-15 Time 14:04 Rev Time 0.00
Received By dbattles Date 2018-11-15 Time 14:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-09-26 Cont ID  
Sent By dbattles Date 2018-09-26 Time 14:43 Rev Time 0.00
Received By dbattles Date 2018-09-26 Time 10:14 Sent To  
Notes
2018-09-26 14:52:14****CORRECTIONS****
 W.P.B. PERMIT: 18080466
 REVIEWED: SEPTEMBER 26, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC 107.2.5]PROVIDE SURVEY OF PROPERTY SHOWING
 EASEMENTS AND DISTANCE FROM PROPERTY LINES TO NEW
 STRUCTURE.
  
 2. [FBC R806.3]VENT AND INSULATION CLEARANCE.
 WHERE EAVE OR CORNICE VENTS ARE INSTALLED, INSULATION
 SHALL NOT BLOCK THE FREE FLOW OF AIR. NOT LESS THAN A
 1-INCH (25 MM) SPACE SHALL BE PROVIDED BETWEEN THE
 INSULATION AND THE ROOF SHEATHING AND AT THE LOCATION
 OF THE VENT.
 ADD NOTE TO STATE CLEARANCE AT SHEATHING TO BE 1?
 MINIMUM.
  
 3. [FBC AMENDED 107.2.1.2]PROVIDE PRODUCT APPROVALS FOR
 WINDOWS, WINDOW MULL(IF APPLICABLE) AND DOORS, OR
 INDICATE THAT YOU WOULD LIKE THEM DEFERED.
  
 4. [FBC AMENDED 107.3.4.1]SUBMIT TRUSS SHOP DRAWINGS TO
 THE BUILDING INSPECTOR PRIOR TO INSTALLATION.
  
 5. [FBC AMENDED 107.2.1.2]ADDITIONAL INFO ON PRODUCT
 APPROVALS NEEDED FOR ROOFING, OR INDICATE THAT YOU
 WOULD TO DEFER IT UNTIL SUB-PERMIT APPLICATION.
 -SELECT WHICH SYSYTEM IS BEING USED BASED ON MDP.
 -PROVIDE ENGINEERING (RAS 117) FOR ENHANCED NAILING AS
 STATED IN PRODUCT APPROVAL UNDER GENERAL LIMITATIONS
 #7.
 -WHAT IS THE EXISTING ROOF PITCH, AND THE NEW ROOF TO
 BE SHINGLED?
 [FBC R905.2.2] [FBC R905.1.1]FOR ROOF SLOPES FROM TWO
 UNITS VERTICAL IN 12 UNITS HORIZONTAL (2:12) AND LESS
 THAN FOUR UNITS VERTICAL IN 12 UNITS HORIZONTAL (4:12),
 DOUBLE UNDERLAYMENT APPLICATION IS REQUIRED.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-12-05 Cont ID  
Sent By jpearson Date 2018-12-03 Time 10:24 Rev Time 0.00
Received By jpearson Date 2018-12-03 Time 07:59 Sent To  
Notes
2018-12-03 10:24:51CHANGED STATUS TO PASS 12-5-18
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-09-04 Cont ID  
Sent By jpearson Date 2018-09-04 Time 11:25 Rev Time 0.00
Received By jpearson Date 2018-09-04 Time 11:25 Sent To  
Notes
2018-09-04 11:25:29CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. AFCI PROTECTION NOTE IS NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902
 2. PLAN STATES THE 2017 NEC AS BASIS FOR DESIGN. THIS
 IS NOT THE CURRENT CODE. PROVIDE CORRECTION. FBC
 PREFACE (ALSO SEE CURRENT CODES ABOVE)
 3. NOTE 9 STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE E4002.14
 4. LIGHTS IN CLOSET ARE SHOWN AS STANDARD RECESS
 LIGHTS. PER CODE: LIGHTING WITH OPEN OR PARTIALLY
 ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS
 SHALL NOT BE PERMITTED IN CLOTHES CLOSETS. PROVIDE
 CORRECTION. NEC 410.16; FBC RE E4003.12
 5. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2018-11-26 Cont ID  
Sent By fmittner Date 2018-11-26 Time 09:58 Rev Time 0.00
Received By fmittner Date 2018-11-26 Time 09:58 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2018-08-24 Cont ID  
Sent By fmittner Date 2018-08-24 Time 16:44 Rev Time 0.00
Received By fmittner Date 2018-08-24 Time 16:44 Sent To  
Notes
2018-08-24 16:45:06REQUIRES HPB APPROVAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-12-17 Cont ID  
Sent By dbattles Date 2018-12-17 Time 15:10 Rev Time 0.00
Received By hmoser Date 2018-12-07 Time 11:20 Sent To P
Notes
2018-12-11 14:09:5212/11/18 TO DB DESK / S.HILL
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-05 Cont ID  
Sent By hmoser Date 2018-12-05 Time 14:28 Rev Time 0.00
Received By hmoser Date 2018-11-05 Time 10:16 Sent To  
Notes
2018-11-07 10:16:10R26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-11 Cont ID  
Sent By hmoser Date 2018-10-11 Time 15:00 Rev Time 0.00
Received By hmoser Date 2018-08-09 Time 10:43 Sent To  
Notes
2018-08-10 10:43:48R27

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2018-12-14 Cont ID  
Sent By dbattles Date 2018-12-14 Time 13:55 Rev Time 0.00
Received By dbattles Date 2018-12-14 Time 13:55 Sent To  
Notes
2018-12-14 13:57:46PLANS STAMPED - OK
 RECEIPT IN FILE.
 MU-2018-041120-0000

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-12-11 Cont ID  
Sent By dbattles Date 2018-12-11 Time 15:34 Rev Time 0.00
Received By dbattles Date 2018-12-11 Time 15:27 Sent To  
Notes
2018-12-11 15:34:28ALL REVIEWS ARE COMPLETE.
 PLEASE COME CHECK OUT ONE SET OF PLANS TO TAKE TO PALM
 BEACH COUNTY IMPACT REVIEW.
 2300 N. JOG ROAD, 2ND FLOOR
 WEST PALM BEACH, FL 33411-2741
  
 THEY WILL ASK FOR THE QUESTIONNAIRE-SEE LINK BELOW
  
 RETURN THE PLANS WITH STAMP AND COPY OF RECEIPT.
  
 [FBC AMENDED 109]PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-09-26 Cont ID  
Sent By dbattles Date 2018-09-26 Time 14:57 Rev Time 0.00
Received By dbattles Date 2018-09-26 Time 14:57 Sent To  
Notes
2018-09-26 14:59:17[FBC AMENDED 109]PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-12-17 Cont ID  
Sent By hmoser Date 2018-12-17 Time 15:09 Rev Time 0.00
Received By hmoser Date 2018-12-17 Time 14:50 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-12-05 Cont ID  
Sent By hmoser Date 2018-12-05 Time 14:22 Rev Time 0.00
Received By hmoser Date 2018-12-05 Time 14:20 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-10-11 Cont ID  
Sent By hmoser Date 2018-10-11 Time 15:00 Rev Time 0.00
Received By hmoser Date 2018-10-11 Time 14:02 Sent To I
Notes
2018-10-11 14:59:59PLAN DENIED
 EQUIPMENT SCHEDULE STATES NEW UNIT
 PLAN STATES EXISTING UNIT. PLEASE VERIFY
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-12-11 Cont ID  
Sent By hmoser Date 2018-12-17 Time 15:10 Rev Time 0.00
Received By jesmith Date 2018-12-11 Time 14:05 Sent To  
Notes
2018-12-11 14:07:11APPROVED
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-11-27 Cont ID  
Sent By jesmith Date 2018-11-27 Time 14:56 Rev Time 0.00
Received By jesmith Date 2018-11-27 Time 14:56 Sent To  
Notes
2018-11-27 14:56:47CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 2ND REVIEW: DENIED
  
 1. RE: PLAN SHEET P.1; TANKLESS WATER HEATER. BOSCH 7
 GAL WATER HEATER INDICATED ON THE PLAN IS A POINT OF
 USE HEATER AND IS NOT TANK-LESS. ADDITIONALLY,
 ELECTRICAL CHARACTERISTICS DO NOT MATCH UP TO THE
 ELECTRICAL LOAD CALCULATIONS ON PLAN PAGE E.1. PLEASE
 PROVIDE ON PLUMBING PLAN THE MANUFACTURER, MODEL AND
 SPECS FOR THE TANK-LESS WATER HEATER WHICH WILL SERVE
 THE WHOLE HOUSE AND IS NOT A POINT OF USE.
 2. RE: PLAN SHEET S.1; EXISTING WATER HEATER. CHANGE
 NOTE "TO BE RELOCATED" TO "TO BE REPLACED WITH
 TANK-LESS WATER HEATER".
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-09-18 Cont ID  
Sent By shill Date 2018-09-18 Time 11:49 Rev Time 0.00
Received By jesmith Date 2018-09-18 Time 11:46 Sent To  
Notes
2018-09-18 11:49:361ST REVIEW: FBC 2017 6TH EDITION
 PERMIT 18080466
 PLUMBING COMMENTS: DENIED
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST PLUMBING. FBC 109.3
 2. TANKLESS WATER HEATER: 1ST REVIEW: FBC 2017 6TH
 EDITION
 PERMIT 18080466
 PLUMBING COMMENTS: DENIED
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST PLUMBING. FBC 109.3
 2. TANKLESS WATER HEATER: PROVIDE ON PLUMBING PLAN THE
 MANUFACTURER, MODEL AND SPECS FOR TANKLESS WATER
 HEATER. CONFIRM THAT MANUFACTURER HAS NOT DESIGNATED
 THIS UNIT AS A POINT OF USE UNIT DESIGNED FOR USE WITH
 SINGLE FIXTURE AND THAT IT WILL PROVIDE ADEQUATE HOT
 WATER FOR THE MASTER BATH FIXTURES IN ACCORDANCE WITH
 FBC RES 2903.1
 3. PROVIDE NOTE: SHOWER CONTROL VALVE(S) SHALL BE
 PRESSURE BALANCED PB,THERMOSTATIC MIXING (TM) OR
 COMBINATION PB/TM VALVE TYPES WITH HIGH TEMPERATURE
 LIMITING STOP. 2017 FBC RES 2708.4
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6715

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2018-11-15 Cont ID  
Sent By dbattles Date 2018-11-15 Time 14:05 Rev Time 0.00
Received By dbattles Date 2018-11-15 Time 14:05 Sent To  
Notes
2018-11-15 14:08:0012/14/18 RAS 117 WAS PROVIDED - OK
 CHANGED R-STOP TO PASSED.
  
 FLAT ROOF NOA -OK, BUT THE REQUESTED RAS 117 WASN'T
 PROVIDED.
 PLEASE PROVIDE WITH THE SUB PERMIT APPLICATION.
 -PROVIDE ENGINEERING (RAS 117) FOR ENHANCED NAILING AS
 STATED IN PRODUCT APPROVAL UNDER GENERAL LIMITATIONS
 #7.
  
 PROVISO:
 PER TRUSS ENGINEERING THE ROOF IS 3/12 PITCH AND WILL
 NEED DOUBLE UNDERLAMENT PER FBC 905.2.2.
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-09-26 Cont ID  
Sent By dbattles Date 2018-09-26 Time 14:52 Rev Time 0.00
Received By dbattles Date 2018-09-26 Time 14:52 Sent To  
Notes
2018-09-26 14:56:37****CORRECTIONS****
 W.P.B. PERMIT: 18080466
 REVIEWED: SEPTEMBER 26, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC R = FBC RESIDENTIAL
  
 [FBC AMENDED 107.2.1.2]ADDITIONAL INFO ON PRODUCT
 APPROVALS NEEDED FOR ROOFING, OR INDICATE THAT YOU
 WOULD TO DEFER IT UNTIL SUB-PERMIT APPLICATION.
 -SELECT WHICH SYSYTEM IS BEING USED BASED ON MDP.
 -PROVIDE ENGINEERING (RAS 117) FOR ENHANCED NAILING AS
 STATED IN PRODUCT APPROVAL UNDER GENERAL LIMITATIONS
 #7.
 -WHAT IS THE EXISTING ROOF PITCH, AND THE NEW ROOF TO
 BE SHINGLED?
 [FBC R905.2.2] [FBC R905.1.1]FOR ROOF SLOPES FROM TWO
 UNITS VERTICAL IN 12 UNITS HORIZONTAL (2:12) AND LESS
 THAN FOUR UNITS VERTICAL IN 12 UNITS HORIZONTAL (4:12),
 DOUBLE UNDERLAYMENT APPLICATION IS REQUIRED.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-11-26 Cont ID  
Sent By fmittner Date 2018-11-26 Time 09:58 Rev Time 0.00
Received By fmittner Date 2018-11-26 Time 09:58 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-08-24 Cont ID  
Sent By fmittner Date 2018-08-24 Time 16:45 Rev Time 0.00
Received By fmittner Date 2018-08-24 Time 16:45 Sent To  
Notes
2018-08-24 16:45:28REQUIRES HPB APPROVAL