Plan Review Details - Permit 18080440
Plan Review Stops For Permit 18080440
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-09-04 Cont ID  
Sent By skennedy Date 2018-09-04 Time 16:44 Rev Time 0.00
Received By skennedy Date 2018-09-04 Time 16:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-09-01 Cont ID  
Sent By shill Date 2018-09-01 Time 17:03 Rev Time 0.00
Received By shill Date 2018-09-01 Time 17:03 Sent To  
Notes
2018-09-01 17:04:13****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SEE PLUMBING COMMENTS. IF YOU NEED ASSISTANCE,
 PLEASE CONTACT ME.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-01 Cont ID  
Sent By shill Date 2018-09-01 Time 17:04 Rev Time 0.00
Received By shill Date 2018-08-08 Time 09:36 Sent To  
Notes
2018-08-10 09:36:55REVISION ROUTED TO TKLARGE

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-09-04 Cont ID  
Sent By skennedy Date 2018-09-04 Time 16:44 Rev Time 0.00
Received By skennedy Date 2018-09-04 Time 16:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-08-22 Cont ID  
Sent By tklarge Date 2018-08-22 Time 10:22 Rev Time 0.00
Received By tklarge Date 2018-08-21 Time 05:19 Sent To  
Notes
2018-08-22 10:22:411) SUBMIT A FLOOR PLAN FOR THE BATHROOM WHERE THE WORK
 IS BEING PERFORMED. THIS BUILDING WAS BUILT IN
 COMPLIANCE WITH THE FAIR HOUSING ACT AND FULL
 COMPLIANCE MUST BE MAINTAINED.
 2) THE HEIGHT OF THE NEW LAVATORY CABINET BEING
 INSTALLED CANNOT EXCEED 34 INCHES FROM THE FINISH FLOOR
 TO THE TOP OF THE COUNTER PER THE FAIR HOUSING ACT.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WATER
 HEATER TO BE REPLACED. WPB AMEND. TO FBC SEC. 107.2.1.
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION
 INSTRUCTIONS FOR THE NEW TUB TO BE INSTALLED. WPB
 AMEND. TO FBC SEC. 107.2.1.
 5) THE BATHTUB VALVE SHALL BE EQUIPPED WITH A WATER
 TEMPERATURE LIMITING DEVICE THAT LIMITS THE TEMPERATURE
 OF THE WATER TO 120 DEGREES AND THAT CONFORMS TO ASSE
 1070 PER THE 2017 FBC-PLUMBING SEC.424.5.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  