Plan Review Details - Permit 18080433
Plan Review Stops For Permit 18080433
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-08-30 Cont ID  
Sent By dbattles Date 2018-08-30 Time 14:24 Rev Time 0.00
Received By dbattles Date 2018-08-30 Time 14:23 Sent To  
Notes
2018-08-30 14:26:52PROVISO:
 [FBC 107.3.5.3] PROVIDE SEDIMENT CONTROL PLAN TO KEEP
 CONSTRUCTION DEBRIS FROM ENTERING ADJACENT PROPERTIES
 AND STORM DRAINS.
  
 ADDED PRODUCT APPOVAL NUMBERS TO SHEET A-3.0 TO MATCH
 P.A.'S PROVIDED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-09-06 Cont ID  
Sent By jleahy Date 2018-09-06 Time 12:29 Rev Time 0.00
Received By jpearson Date 2018-09-06 Time 12:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-24 Cont ID  
Sent By jpearson Date 2018-08-24 Time 13:20 Rev Time 0.00
Received By jpearson Date 2018-08-24 Time 12:32 Sent To  
Notes
2018-08-24 13:19:59CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER SHOWS METER MAIN COMBO WITH AN AIC RATING OF
 10000 AMPS. INTERIOR PANEL SCHEDULE SHOWS THE SAME
 RATING FOR THE INTERIOR PANEL. FPL FAULT CURRENT LETTER
 STATES THE THE AVAILABLE FAULT CURRENT IS 21110 AMPS.
 ELECTRICAL EQUIPMENT MUST MEET OR EXCEED THIS VALUE.
 PROVIDE CORRECTION. NEC 110.9
 2. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 3. AFCI PROTECTION SHOWN IN NOTE 5 IS NOT CODE
 COMPLIANT. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902
 4. SPECIFY THE EQUIPMENT GROUNDING CONDUCTOR WIRE SIZE
 FROM METER MAIN COMBO TO INTERIOR PANEL. NEC 250.122;
 FBC RE E3704.6
 5. RECEPTACLES INSTALLED TO SERVE THE COUNTER TOP IN
 KITCHEN REQUIRE GFCI PROTECTION, INCLUDING THE
 PENINSULA. PROVIDE CORRECTION. NEC 210.8; FBC RE
 E3902.6
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-06 Cont ID  
Sent By jleahy Date 2018-09-06 Time 12:38 Rev Time 0.00
Received By jleahy Date 2018-09-06 Time 09:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-04 Cont ID  
Sent By hmoser Date 2018-09-04 Time 11:44 Rev Time 0.00
Received By hmoser Date 2018-08-09 Time 11:23 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2018-09-05 Cont ID  
Sent By dbattles Date 2018-09-05 Time 16:24 Rev Time 0.00
Received By cpuell Date 2018-09-04 Time 11:49 Sent To  
Notes
2018-09-05 16:24:36PASSED & STAMPED BY IMPACT FEE OFFICE
2018-09-04 11:49:449/4/18 EMAILED WILLIE TO REVIEW FOR IMPACT FEES. LEM
2018-08-30 14:28:30IMPACT FEE QUESTIONAIRE IS UPLOADED TO SUPPORTING
 DOCUMENTS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-09-04 Cont ID  
Sent By hmoser Date 2018-09-04 Time 11:43 Rev Time 0.00
Received By hmoser Date 2018-09-04 Time 11:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2018-08-26 Time   Rev Time  
Received By   Date 2018-08-26 Time   Sent To  
Notes
2018-08-27 09:44:26REVIEW BY GJOHNSON.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2018-08-30 Cont ID  
Sent By dbattles Date 2018-08-30 Time 14:22 Rev Time 0.00
Received By dbattles Date 2018-08-30 Time 14:22 Sent To  
Notes
2018-08-30 14:23:41SHINGLES P.A. FL10674-R13 - OK.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2018-09-06 Cont ID  
Sent By jleahy Date 2018-09-06 Time 12:29 Rev Time 0.00
Received By shill Date 2018-09-06 Time 12:29 Sent To  
Notes
2018-09-06 12:41:54****PROVISO****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PLAN PAGES SIGNATURES OK
  
 SOILS REPORT IS NOT DIGITALLY SIGNED; PROVIDE ONE
 ORIGINAL SIGNED AND SEALED PAPER DOCUMENT
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-09-04 Cont ID  
Sent By shill Date 2018-09-04 Time 11:57 Rev Time 0.00
Received By shill Date 2018-09-04 Time 11:56 Sent To  
Notes
2018-09-04 11:57:53****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PLAN PAGES SIGNATURES OK
  
 SOILS REPORT IS NOT DIGITALLY SIGNED; PROVIDE ONE
 ORIGINAL SIGNED AND SEALED PAPER DOCUMENT
  
  
2018-08-24 12:32:48ELECTRICAL SIGNATURE OK.

Review Stop Z ZONING
Rev No 1 Status P Date 2018-08-14 Cont ID  
Sent By mcruz Date 2018-08-14 Time 14:05 Rev Time 0.00
Received By mcruz Date 2018-08-14 Time 10:17 Sent To PC
Notes
***NONE***