| Plan Review Stops For Permit 18080413 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2019-03-22 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-03-22 |
Time |
19:03 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-03-22 |
Time |
19:03 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2019-02-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-02-04 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-02-04 |
Time |
11:41 |
Sent To |
I |
|
| Notes |
| 2019-02-04 14:47:41 | PLAN | | | REVIEW COMMENTS | | | | | | 3RD REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) BASED ON THE INFORMATION THAT WAS SUBMITTED TO | | | ADDRESS THE MECHANICAL COMMENTS, IT APPEARS THAT SOME | | | OF THE MATERIALS THAT WILL BE USED AND STORED IN THE | | | LAB ARE CLASSIFIED AS HAZARDOUS. THE HAZARDOUS | | | MATERIALS IN THIS CASE APPEARS TO BE FLAMABLE LIQUIDS. | | | THE QUANTITY OF THE FLAMABLE LIQUIDS THAT YOU PROVIDED | | | ARE WITHIN THE MAXIMUM ALLOWABLE QUANTITY ALLOWED PER | | | CONTROL AREA. REVISE THE PLANS TO SHOW HOW THE STORAGE | | | AND HANDLING OF THESE HAZARDOUS MATERIALS WILL BE | | | ADDRESSED. FBC 307 & 414 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2018-11-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-11-14 |
Time |
18:05 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-11-14 |
Time |
16:32 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-09-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-09-04 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-08-31 |
Time |
17:49 |
Sent To |
I |
|
| Notes |
| 2018-09-04 11:05:11 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THERE IS A NOTE ON SHEET LS-1 THAT STATES AREA OF | | | WORK TO REMAIN UNSPRINKLERED. THE CODE ANALYSIS | | | INDICATES THAT THIS IS A TYPE LL A SPRINKLER BUILDING | | | AND ALL OF THE EXIT REQUIREMENTS ARE BASED ON A FULLY | | | SPRINKLERED BUILDING IN ACCORDANCE WITH FBC 903.3.1.1. | | | THIS ENTIRE BUILDING INCLUDING THIS UNIT IS REQUIRED TO | | | BE FIRE SPRINKLERED. | | | | | | 2) ON SHEET LS-1 THE TRAVEL DISTANCE TO AN EXIT IS | | | LISTED AS 400 FEET. FBC 1017.3 AND TABLE 1017.2 | | | SPECIFIES THE TRAVEL DISTANCE FOR A BUSINESS OCCUPANCY | | | IN A FULLY SPRINKLED BUILDING AS 300 FEET. EXPLAIN HOW | | | THE 400 FEET OF TRAVEL WAS DETERMINED. | | | | | | 3) SPECIFY THE OCCUPANT LOAD FOR THIS PROJECT AREA ON | | | THE LIFE SAFETY PLANS. FBC 1004.1 | | | | | | 4) THE COMMON PATH OF EGRESS TRAVEL IS NOT SHOWN ON | | | LS-1. FBC 1006.2.1 & FBC CHAPTER 2, COMMON PATH OF | | | EGRESS TRAVEL. THAT PORTION OF THE EXIT ACCESS TRAVEL | | | DISTANCE MEASURED FROM THE MOST REMOTE POINT WITHIN A | | | STORY TO THAT POINT WHERE THE OCCUPANTS HAVE SEPARATE | | | AND DISTINCT ACCESS TO TWO EXITS OR EXIT ACCESS | | | DOORWAYS. | | | | | | 5) THE EXIT ACCESS TRAVEL DISTANCE IS NOT SHOWN | | | CORRECTLY ON LS-1. FBC 1017 & FBC CHAPTER 2, EXIT | | | ACCESS. THAT PORTION OF A MEANS OF EGRESS SYSTEM THAT | | | LEADS FROM ANY OCCUPIED PORTION OF A BUILDING OR | | | STRUCTURE TO AN EXIT. 1017.3 MEASUREMENT. EXIT ACCESS | | | TRAVEL DISTANCE SHALL BE MEASURED FROM THE MOST REMOTE | | | POINT WITHIN A STORY ALONG THE NATURAL AND UNOBSTRUCTED | | | PATH OF HORIZONTAL AND VERTICAL EGRESS TRAVEL TO THE | | | ENTRANCE TO AN EXIT. FOR THIS PROJECT THE EXIT ACCESS | | | TRAVEL DISTANCE IS MEASURED FROM THE MOST REMOTE POINT | | | IN THE UNIT TO THE DOOR OF THE NEAREST INTERIOR EXIT | | | STAIRWAY. | | | | | | 6) SHOW THAT THE DOUBLE DOOR 300 THAT SWINGS OUT INTO | | | THE EXIT ACCESS CORRIDOR COMPLIES WITH FBC 1005.7. | | | ENCROACHMENTS INTO THE REQUIRED MEANS OF EGRESS WIDTH | | | SHALL BE IN ACCORDANCE WITH THE PROVISIONS OF THIS | | | SECTION. 1005.7.1 DOORS, WHEN FULLY OPENED, SHALL NOT | | | REDUCE THE REQUIRED WIDTH BY MORE THAN 7 INCHES (178 | | | MM). DOORS IN ANY POSITION SHALL NOT REDUCE THE | | | REQUIRED WIDTH BY MORE THAN ONE-HALF. | | | | | | 7) THE DOUBLE DOOR 300 IS SHOWN ON SHEET A-2 WITH LEVER | | | OPERATING DEVICES ON EACH LEAF. EXPLAIN HOW THE DOORS | | | WILL COMPLY WITH FBC 1010.1.9.3 & 1010.1.9.4. | | | 1010.1.9 DOOR OPERATIONS. EXCEPT AS SPECIFICALLY | | | PERMITTED BY THIS SECTION, EGRESS DOORS SHALL BE | | | READILY OPENABLE FROM THE EGRESS SIDE WITHOUT THE USE | | | OF A KEY OR SPECIAL KNOWLEDGE OR EFFORT. | | | 1010.1.9.3 LOCKS AND LATCHES. LOCKS AND LATCHES SHALL | | | BE PERMITTED TO PREVENT OPERATION OF DOORS WHERE ANY OF | | | THE FOLLOWING EXIST: | | | - 3.WHERE EGRESS DOORS ARE USED IN PAIRS, APPROVED | | | AUTOMATIC FLUSH BOLTS SHALL BE PERMITTED TO BE USED, | | | PROVIDED THAT THE DOOR LEAF HAVING THE AUTOMATIC FLUSH | | | BOLTS DOES NOT HAVE A DOORKNOB OR SURFACE-MOUNTED | | | HARDWARE. | | | | | | FBC 1010.1.9.4 BOLT LOCKS. MANUALLY OPERATED FLUSH | | | BOLTS OR SURFACE BOLTS ARE NOT PERMITTED. | | | EXCEPTIONS: | | | - 3.WHERE A PAIR OF DOORS SERVES AN OCCUPANT LOAD OF | | | LESS THAN 50 PERSONS IN A GROUP B, F OR S OCCUPANCY, | | | MANUALLY OPERATED EDGE- OR SURFACE-MOUNTED BOLTS ARE | | | PERMITTED ON THE INACTIVE LEAF. THE INACTIVE LEAF SHALL | | | NOT CONTAIN DOORKNOBS, PANIC BARS OR SIMILAR OPERATING | | | HARDWARE. | | | | | | - 4.WHERE A PAIR OF DOORS SERVES A GROUP B, F OR S | | | OCCUPANCY, MANUALLY OPERATED EDGE- OR SURFACE-MOUNTED | | | BOLTS ARE PERMITTED ON THE INACTIVE LEAF PROVIDED SUCH | | | INACTIVE LEAF IS NOT NEEDED TO MEET EGRESS CAPACITY | | | REQUIREMENTS AND THE BUILDING IS EQUIPPED THROUGHOUT | | | WITH AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH | | | SECTION 903.3.1.1. THE INACTIVE LEAF SHALL NOT CONTAIN | | | DOORKNOBS, PANIC BARS OR SIMILAR OPERATING HARDWARE. | | | | | | 8) THE EXISTING DOOR TO THE STAIR ADJACENT TO ROOM 319 | | | DOES NOT APPEAR TO HAVE 18" ON THE PULL SIDE AS | | | REQUIRED BY FBC ACCESSIBILITY SEC. 404.2.4.1. | | | | | | 9) THE ADA SHOWER ON SHEET A-2 IS NOT SHOWN WITH THE | | | 36" WIDE ENTRY THAT IS REQUIRED BY FBC ACCESSIBILITY | | | SEC. 608.2.3. | | | | | | 10) SHOW THE REQUIRED CLEAR FLOOR SPACE AT THE BREAK | | | ROOM SINK FOR EITHER A PARALLEL OR FORWARD APPROACH | | | THAT IS REQUIRED BY FBC ACCESSIBILITY SEC. 606.2, 305 | | | AND 305.6. | | | | | | 11) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2019-02-03 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-02-03 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-02-03 |
Time |
15:09 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2018-10-17 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-10-17 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-10-17 |
Time |
09:58 |
Sent To |
FIRE |
|
| Notes |
| 2018-10-17 10:57:05 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | | | 1. CORRECTED. | | | 2. PROVIDE ACCURATE LOAD CALCULATION FOR EACH SERVICE | | | MAIN PER ONE OF THE METHODS IN NEC 220. ESTIMATING THE | | | LOAD BASED ON THE OCP SIZE IS NOT A PERMITTED METHOD, | | | NOR IS A FUTURE DATA RECORDING. HOW IS IT POSSIBLE TO | | | DESIGN THE SYSTEM WITHOUT KNOWING THE ACTUAL LOAD? | | | PROVIDE COMPLIANCE. NEC 220 (ACCURATE LOAD CALCULATION | | | NOT PROVIDED. A ONE TIME AMP READING IS NOT SUFFICIENT | | | INFORMATION TO BASE A LOAD CALCULATION ON. PROVIDE AS | | | PREVIOUSLY REQUESTED USING ONE OF THE METHODS PERMITTED | | | IN NEC 220.) | | | 3. CORRECTED. | | | 4. CORRECTED. | | | 5. CORRECTED. | | | 6. CORRECTED. | | | 7. CORRECTED. | | | 8. CORRECTED. | | | 9. CORRECTED. | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD | | | SHEETS?. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-08-24 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-08-24 |
Time |
08:23 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-08-23 |
Time |
08:57 |
Sent To |
|
|
| Notes |
| 2018-08-23 16:02:12 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE FULL RISER DIAGRAM AND SHOW LOCATION ON SITE | | | PLAN OF MAIN LOCATIONS. ALL MAINS SHOULD BE GROUPED. | | | NEC 230.72; WPB FBC 107.2.1 | | | 2. PROVIDE ACCURATE LOAD CALCULATION FOR EACH SERVICE | | | MAIN PER ONE OF THE METHODS IN NEC 220. ESTIMATING THE | | | LOAD BASED ON THE OCP SIZE IS NOT A PERMITTED METHOD, | | | NOR IS A FUTURE DATA RECORDING. HOW IS IT POSSIBLE TO | | | DESIGN THE SYSTEM WITHOUT KNOWING THE ACTUAL LOAD? | | | PROVIDE COMPLIANCE. NEC 220 | | | 3. PLAN STATES THAT THERE ARE 600 AMP FEEDERS TO | | | WIREWAY, BUT THEN STATES TO UPGRADE TO COMPLY. THIS | | | INDICATES THAT THE DESIGN PROFESSIONAL DOES NOT KNOW | | | WHAT IS THERE. HOW IS IT POSSIBLE TO DESIGN WITHOUT | | | KNOWING THE ACTUAL CAPACITY OF THE WIRING? PROVIDE | | | CORRECTION. NEC 215.2, 215.5, 310.15; WPB FBC 107.2.1 | | | 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. | | | NEC 110.9, 110.10 | | | 5. PROVIDE AIC RATING OF SERVICE DISCONNECTS AND | | | PANELS. NEC 110.3, 110.9 | | | 6. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF | | | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND | | | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 | | | 7. PROVIDE THE ESSENTIAL ELECTRICAL SYSTEMS REQUIRED | | | FOR MEDICAL OFFICE. NEC 517.25, 517.45 | | | 8. CONDUCTOR KEY NOTE 2 SHOWS AN EQUIPMENT GROUNDING | | | CONDUCTOR (EGC). IF THIS IS A TAP FROM FPL FEED, AN EGC | | | IS NOT PERMITTED. PROVIDE CORRECTION. NEC 250.6 | | | 9. SOME RECEPTACLE OUTLETS ARE SHOWN WITHIN 6 FEET OF A | | | SINK WITHOUT THE PROPER GFCI PROTECTION. PROVIDE | | | CORRECTION. NEC 210.8 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD | | | SHEETS?. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2019-03-18 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2019-03-18 |
Time |
10:04 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2019-03-18 |
Time |
09:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2018-10-17 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2018-10-17 |
Time |
11:11 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2018-10-17 |
Time |
11:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2018-08-24 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2018-08-24 |
Time |
09:59 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2018-08-24 |
Time |
09:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2019-03-22 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-03-22 |
Time |
19:04 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-03-12 |
Time |
15:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-02-04 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-01-29 |
Time |
15:36 |
Sent To |
|
|
| Notes |
| 2019-01-30 15:36:35 | RESUB ROUTED TO JPEARSON |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-11-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-11-14 |
Time |
18:06 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-10-11 |
Time |
15:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-09-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-09-04 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-08-08 |
Time |
09:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2018-08-31 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-08-31 |
Time |
18:31 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-08-31 |
Time |
18:30 |
Sent To |
|
|
| Notes |
| 2018-08-31 18:31:40 | PROJECT WILL REMAIN A BUSINESS OCCUPANCY. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2019-03-15 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-03-15 |
Time |
16:39 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-03-15 |
Time |
16:39 |
Sent To |
|
|
| Notes |
| 2019-03-15 16:49:57 | 4TH REVIEW FBC-2017 MECHANICAL | | | PERMIT #18080413 | | | 2/4/19 | | | | | | CODES IN EFFECT: | | | | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | COMMENT #3 FROM THE 3RD REVIEW PRINTED BELOW HAS NOT | | | BEEN ADDRESSED. I HAVE PRINTED THE CODE SECTION BELOW. | | | PLEASE FORWARD TO THE ARCHITECT OF RECORD. | | | PLEASE NOTE THAT UNTIL ADEQUATE INFORMATION IS PROVIDED | | | TO VERIFY COMPLIANCE WITH THE EXCEPTION, A HAZARDOUS | | | EXHAUST SYSTEM WILL BE REQUIRED, AND DAMPERS ARE | | | PROHIBITED IN THE EXHAUST DUCT- SECTION 510.7.1 FBC M. | | | SEE SECTIONS 510.7.3 FOR DUCT ENCLOSURE REQUIREMENT, | | | AND 510.9 FOR DUCT MATERIALS | | | | | | 3) M1.1: REFER TO SECTION 510.2 EXCEPTION FBC M AND | | | VERIFY COMPLIANCE OR A HAZARDOUS EXHAUST SYSTEM | | | COMPLYING WITH SECTIONS 510.6- 510.10 SHALL BE | | | PROVIDED. THE CURRENT EXHAUST SYSTEM SHOWN IS NOT IN | | | COMPLIANCE. | | | | | | 510.2 WHERE REQUIRED. | | | | | | A HAZARDOUS EXHAUST SYSTEM SHALL BE REQUIRED WHEREVER | | | OPERATIONS INVOLVING THE HANDLING OR PROCESSING OF | | | HAZARDOUS MATERIALS, IN THE ABSENCE OF SUCH EXHAUST | | | SYSTEMS AND UNDER NORMAL OPERATING CONDITIONS, HAVE THE | | | POTENTIAL TO CREATE ONE OF THE FOLLOWING CONDITIONS: | | | | | | 1.A FLAMMABLE VAPOR, GAS, FUME, MIST OR DUST IS PRESENT | | | IN CONCENTRATIONS EXCEEDING 25 PERCENT OF THE LOWER | | | FLAMMABILITY LIMIT OF THE SUBSTANCE FOR THE EXPECTED | | | ROOM TEMPERATURE. | | | | | | 2.A VAPOR, GAS, FUME, MIST OR DUST WITH A HEALTH-HAZARD | | | RATING OF 4 IS PRESENT IN ANY CONCENTRATION. | | | | | | 3.A VAPOR, GAS, FUME, MIST OR DUST WITH A HEALTH-HAZARD | | | RATING OF 1, 2 OR 3 IS PRESENT IN CONCENTRATIONS | | | EXCEEDING 1 PERCENT OF THE MEDIAN LETHAL CONCENTRATION | | | OF THE SUBSTANCE FOR ACUTE INHALATION TOXICITY. | | | | | | EXCEPTION: LABORATORIES, AS DEFINED IN SECTION 510.1, | | | EXCEPT WHERE THE CONCENTRATIONS LISTED IN ITEM 1 ARE | | | EXCEEDED OR A VAPOR, GAS, FUME, MIST OR DUST WITH A | | | HEALTH-HAZARD RATING OF 1, 2, 3 OR 4 IS PRESENT IN | | | CONCENTRATIONS EXCEEDING 1 PERCENT OF THE MEDIAN LETHAL | | | CONCENTRATION OF THE SUBSTANCE FOR ACUTE INHALATION | | | TOXICITY. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2019-02-04 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-02-04 |
Time |
10:38 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-02-04 |
Time |
08:53 |
Sent To |
B |
|
| Notes |
| 2019-02-04 11:07:16 | 3RD REVIEW FBC-2017 MECHANICAL | | | PERMIT #18080413 | | | 2/4/19 | | | | | | CODES IN EFFECT: | | | | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M0.2: BASED ON THE SUBMITTED MSDS SHEETS, | | | STORAGE OF FLAMMABLE LIQUIDS NOT EXCEEDING THE MAXIMUM | | | ALLOWABLE QUANTITIES WILL OCCUR IN THE LAB WHICH | | | REQUIRES THE ROOM TO BE DESIGNATED AS A "CONTROL AREA" | | | - SEE SECTIONS 202 AND 414.2 FBC. THE CONTROL AREA | | | (LAB) IS REQUIRED TO BE SEPARATED FROM OTHER ROOMS AND | | | SPACES WITH 1-HR FIRE-RESISTANT RATED CONSTRUCTION- | | | SECTION 414.2.4 AND TABLE 414.2.2 FBC B. | | | | | | 2) M1.1: BECAUSE FIRE-BARRIERS ARE NOW REQUIRED TO | | | ENCLOSE THE LAB, ALL DUCT PENETRATIONS SHALL BE | | | PROTECTED WITH FIRE DAMPERS- SECTION 607.5.2 FBC M. | | | | | | 3) M1.1: REFER TO SECTION 510.2 EXCEPTION FBC M AND | | | VERIFY COMPLIANCE OR A HAZARDOUS EXHAUST SYSTEM | | | COMPLYING WITH SECTIONS 510.6- 510.10 SHALL BE | | | PROVIDED. THE CURRENT EXHAUST SYSTEM SHOWN IS NOT IN | | | COMPLIANCE. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2018-10-24 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-10-24 |
Time |
14:59 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-10-24 |
Time |
14:08 |
Sent To |
|
|
| Notes |
| 2018-10-24 15:05:00 | 2ND REVIEW FBC-2017 MECHANICAL | | | PERMIT #18080413 | | | 10/24/18 | | | | | | CODES IN EFFECT: | | | | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) M0.2: A) REFER TO SECTION 414.1.3 FBC B AND PROVIDE | | | THE HAZARDOUS MATERIALS CLASSIFICATIONS FOR ALL | | | CHEMICALS LISTED IN THE SCHEDULE AND SUBMIT MSDS SHEETS | | | FOR EACH- SEE TABLES 307.1(1) AND 307.1(2). B) SHOW THE | | | LOCATION OF THE FUME HOOD ON THE PLAN AND SUBMIT | | | MANUFACTURER'S SPECIFICATIONS- | | | | | | 2) M1.1: RECIRCULATION OF AIR FROM THE LAB IS ONLY | | | PERMITTED WHERE THE RESULTING AIRSTREAM CONSISTS OF NOT | | | MORE THAN 10 PERCENT AIR RECIRCULATED FORM THE ROOM- | | | TABLE 403.3.1.1 FOOTNOTE G. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-08-24 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-08-24 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-08-24 |
Time |
13:13 |
Sent To |
|
|
| Notes |
| 2018-08-24 16:36:19 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #18080413 | | | 8/24/18 | | | | | | CODES IN EFFECT: | | | | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M0.2 & M1.1: THE O/A CALCS AND PLAN SHOW TWO | | | ROOMS THAT REQUIRE EXHAUST VENTILATION PER TABLE 403.3 | | | FBC M: THE ROOMS ARE THE LAB- 1.0 CFMS PER SF AND THE | | | PHOTO- 1.0 CFMS PER SF. THE STORAGE ROOM MAY ALSO | | | REQUIRE EXHAUST DEPENDING ON WHAT IS BEING STORED | | | THERE. PLEASE PROVIDE A LIST OF ALL CHEMICALS OR | | | MATERIALS TO BE STORED IN THE ROOM AND THEIR | | | QUANTITIES- REFER TO SECTIONS 510.1- 510.10 FBC M. | | | | | | 2) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW | | | FAN COIL UNITS- SECTION C403.2.1 FBC-17 ENERGY | | | CONSERVATION. | | | | | | 3) SHEET M1.1 & M5.1: THERE IS A FIRE DAMPER | | | INSTALLATION DETAIL ON THE PLAN. PLEASE INDICATE WHERE | | | IT IS TO BE INSTALLED | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2018-11-05 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-11-05 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-11-05 |
Time |
11:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-08-31 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-08-31 |
Time |
07:34 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-08-30 |
Time |
11:42 |
Sent To |
|
|
| Notes |
| 2018-08-31 08:59:41 | 1ST REVIEW: | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. PROVIDE THE DIMENSIONS OF THE SHOWER OPENING SHALL | | | COMPLY WITH FBC ACC 608.2.3 | | | | | | 2. SHOW COMPLIANCE WITH FBC ACC 608.5.3 ALTERNATE | | | ROLL-IN TYPE SHOWER COMPARTMENTS. | | | IN ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS, THE | | | CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE | | | LOCATED ABOVE THE GRAB BAR, BUT NO HIGHER THAN 48 | | | INCHES ABOVE THE SHOWER FLOOR. WHERE A SEAT IS | | | PROVIDED, THE CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT | | | SHALL BE LOCATED ON THE SIDE WALL ADJACENT TO THE SEAT | | | 27 INCHES MAXIMUM FROM THE SIDE WALL BEHIND THE SEAT OR | | | SHALL BE LOCATED ON THE BACK WALL OPPOSITE THE SEAT 15 | | | INCHES MAXIMUM, LEFT OR RIGHT, OF THE CENTERLINE OF THE | | | SEAT. WHERE A SEAT IS NOT PROVIDED, THE CONTROLS, | | | FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON | | | THE SIDE WALL FARTHEST FROM THE COMPARTMENT ENTRY | | | | | | 3. SHOW COMPLIANCE WITH FBC ACC 608.3.3 ALTERNATE | | | ROLL-IN TYPE SHOWER COMPARTMENTS. | | | IN ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS, GRAB | | | BARS SHALL BE PROVIDED ON THE BACK WALL AND THE SIDE | | | WALL FARTHEST FROM THE COMPARTMENT ENTRY. GRAB BARS | | | SHALL NOT BE PROVIDED ABOVE THE SEAT. GRAB BARS SHALL | | | BE INSTALLED 6 INCHES MAXIMUM FROM ADJACENT WALLS. | | | | | | 4. THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE | | | GRIPPING SURFACE FROM FINISHED FLOOR. PER FBC ACC 609.4 | | | | | | 5. TOILET PAPER DISPENSERS SHALL BE 7 INCHES MINIMUM | | | AND 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET | | | MEASURED TO THE CENTERLINE OF THE DISPENSER. PLEASE | | | CLARIFY ON THE PLAN PER FBC ACC 604.7 | | | | | | 6. A MINIMUM OF ONE OF THE SINKS IN THE EXAM ROOMS | | | SHALL COMPLY WITH FBC ACC 606.2, 606.3 PER FBC ACC | | | 212.3 | | | | | | 7. A LINT TRAP IS REQUIRED FOR THE DISCHARGE OF THE | | | WASHING MACHINE IF MACHINE IS A COMMERCIAL MODEL | | | PROVIDE MAKE AND MODEL OF EXISTING WASHING MACHINE. PER | | | FBC PL 1003.6 EXCEPTIONS(2) | | | | | | 8. PLEASE PROVIDE THE FOLLOWING INFORMATION ON THE PLAN | | | PER WPB AMEND TO FBC | | | A) THE LEVEL OF ALTERATION. | | | B) THE OCCUPANT LOAD. | | | | | | 8. A DRINKING FOUNTAIN MAYBE REQUIRED IF OCCUPANT LOAD | | | INCREASED OR CHANGE OF OCCUPANCY PROVIDE NOTE ON THE | | | PLAN THE PREVIOUS OCCUPANCY TYPE AND LOAD. PER FBC PL | | | TABLE 403.1 AND FBC EX CH 7, 8, 9, 10 | | | | | | 9. THE WATER HEATER SHALL COMPLY WITH FBC ENERGY C404.2 | | | PLEASE PLACE NOTE ON THE PLAN. | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
X |
PERMIT EXTENSION |
| Rev No |
1 |
Status |
P |
Date |
2019-09-18 |
|
|
Cont ID |
|
| Sent By |
spalmer |
Date |
2019-09-18 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
spalmer |
Date |
2019-09-18 |
Time |
16:09 |
Sent To |
|
|
| Notes |
| 2019-09-18 16:10:27 | PERMIT EXTENDED TO DECEMBER 18 2019 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2018-08-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2018-08-20 |
Time |
17:15 |
Sent To |
|
|
| Notes |
| 2018-08-21 15:40:31 | THE SCOPE OF WORK IS INTERIOR REMODELING/IMPROVEMENTS, | | | SO A ZONING REVIEW IS NOT REQUIRED. THE FOOTPRINT OF | | | THE BUILDING IIS NOT CHANGING. | | | | | | ALANA WOOTEN | | | ASSOCIATE PLANNER | | | 561-822-1449 | | | [email protected] |
|
|