Plan Review Details - Permit 18080413
Plan Review Stops For Permit 18080413
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-03-22 Cont ID  
Sent By rmcdouga Date 2019-03-22 Time 19:03 Rev Time 0.00
Received By rmcdouga Date 2019-03-22 Time 19:03 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-02-04 Cont ID  
Sent By rmcdouga Date 2019-02-04 Time 14:47 Rev Time 0.00
Received By rmcdouga Date 2019-02-04 Time 11:41 Sent To I
Notes
2019-02-04 14:47:41PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) BASED ON THE INFORMATION THAT WAS SUBMITTED TO
 ADDRESS THE MECHANICAL COMMENTS, IT APPEARS THAT SOME
 OF THE MATERIALS THAT WILL BE USED AND STORED IN THE
 LAB ARE CLASSIFIED AS HAZARDOUS. THE HAZARDOUS
 MATERIALS IN THIS CASE APPEARS TO BE FLAMABLE LIQUIDS.
 THE QUANTITY OF THE FLAMABLE LIQUIDS THAT YOU PROVIDED
 ARE WITHIN THE MAXIMUM ALLOWABLE QUANTITY ALLOWED PER
 CONTROL AREA. REVISE THE PLANS TO SHOW HOW THE STORAGE
 AND HANDLING OF THESE HAZARDOUS MATERIALS WILL BE
 ADDRESSED. FBC 307 & 414
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-11-14 Cont ID  
Sent By rmcdouga Date 2018-11-14 Time 18:05 Rev Time 0.00
Received By rmcdouga Date 2018-11-14 Time 16:32 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-09-04 Cont ID  
Sent By rmcdouga Date 2018-09-04 Time 15:59 Rev Time 0.00
Received By rmcdouga Date 2018-08-31 Time 17:49 Sent To I
Notes
2018-09-04 11:05:11PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THERE IS A NOTE ON SHEET LS-1 THAT STATES AREA OF
 WORK TO REMAIN UNSPRINKLERED. THE CODE ANALYSIS
 INDICATES THAT THIS IS A TYPE LL A SPRINKLER BUILDING
 AND ALL OF THE EXIT REQUIREMENTS ARE BASED ON A FULLY
 SPRINKLERED BUILDING IN ACCORDANCE WITH FBC 903.3.1.1.
 THIS ENTIRE BUILDING INCLUDING THIS UNIT IS REQUIRED TO
 BE FIRE SPRINKLERED.
  
 2) ON SHEET LS-1 THE TRAVEL DISTANCE TO AN EXIT IS
 LISTED AS 400 FEET. FBC 1017.3 AND TABLE 1017.2
 SPECIFIES THE TRAVEL DISTANCE FOR A BUSINESS OCCUPANCY
 IN A FULLY SPRINKLED BUILDING AS 300 FEET. EXPLAIN HOW
 THE 400 FEET OF TRAVEL WAS DETERMINED.
  
 3) SPECIFY THE OCCUPANT LOAD FOR THIS PROJECT AREA ON
 THE LIFE SAFETY PLANS. FBC 1004.1
  
 4) THE COMMON PATH OF EGRESS TRAVEL IS NOT SHOWN ON
 LS-1. FBC 1006.2.1 & FBC CHAPTER 2, COMMON PATH OF
 EGRESS TRAVEL. THAT PORTION OF THE EXIT ACCESS TRAVEL
 DISTANCE MEASURED FROM THE MOST REMOTE POINT WITHIN A
 STORY TO THAT POINT WHERE THE OCCUPANTS HAVE SEPARATE
 AND DISTINCT ACCESS TO TWO EXITS OR EXIT ACCESS
 DOORWAYS.
  
 5) THE EXIT ACCESS TRAVEL DISTANCE IS NOT SHOWN
 CORRECTLY ON LS-1. FBC 1017 & FBC CHAPTER 2, EXIT
 ACCESS. THAT PORTION OF A MEANS OF EGRESS SYSTEM THAT
 LEADS FROM ANY OCCUPIED PORTION OF A BUILDING OR
 STRUCTURE TO AN EXIT. 1017.3 MEASUREMENT. EXIT ACCESS
 TRAVEL DISTANCE SHALL BE MEASURED FROM THE MOST REMOTE
 POINT WITHIN A STORY ALONG THE NATURAL AND UNOBSTRUCTED
 PATH OF HORIZONTAL AND VERTICAL EGRESS TRAVEL TO THE
 ENTRANCE TO AN EXIT. FOR THIS PROJECT THE EXIT ACCESS
 TRAVEL DISTANCE IS MEASURED FROM THE MOST REMOTE POINT
 IN THE UNIT TO THE DOOR OF THE NEAREST INTERIOR EXIT
 STAIRWAY.
  
 6) SHOW THAT THE DOUBLE DOOR 300 THAT SWINGS OUT INTO
 THE EXIT ACCESS CORRIDOR COMPLIES WITH FBC 1005.7.
 ENCROACHMENTS INTO THE REQUIRED MEANS OF EGRESS WIDTH
 SHALL BE IN ACCORDANCE WITH THE PROVISIONS OF THIS
 SECTION. 1005.7.1 DOORS, WHEN FULLY OPENED, SHALL NOT
 REDUCE THE REQUIRED WIDTH BY MORE THAN 7 INCHES (178
 MM). DOORS IN ANY POSITION SHALL NOT REDUCE THE
 REQUIRED WIDTH BY MORE THAN ONE-HALF.
  
 7) THE DOUBLE DOOR 300 IS SHOWN ON SHEET A-2 WITH LEVER
 OPERATING DEVICES ON EACH LEAF. EXPLAIN HOW THE DOORS
 WILL COMPLY WITH FBC 1010.1.9.3 & 1010.1.9.4.
 1010.1.9 DOOR OPERATIONS. EXCEPT AS SPECIFICALLY
 PERMITTED BY THIS SECTION, EGRESS DOORS SHALL BE
 READILY OPENABLE FROM THE EGRESS SIDE WITHOUT THE USE
 OF A KEY OR SPECIAL KNOWLEDGE OR EFFORT.
 1010.1.9.3 LOCKS AND LATCHES. LOCKS AND LATCHES SHALL
 BE PERMITTED TO PREVENT OPERATION OF DOORS WHERE ANY OF
 THE FOLLOWING EXIST:
 - 3.WHERE EGRESS DOORS ARE USED IN PAIRS, APPROVED
 AUTOMATIC FLUSH BOLTS SHALL BE PERMITTED TO BE USED,
 PROVIDED THAT THE DOOR LEAF HAVING THE AUTOMATIC FLUSH
 BOLTS DOES NOT HAVE A DOORKNOB OR SURFACE-MOUNTED
 HARDWARE.
  
 FBC 1010.1.9.4 BOLT LOCKS. MANUALLY OPERATED FLUSH
 BOLTS OR SURFACE BOLTS ARE NOT PERMITTED.
 EXCEPTIONS:
 - 3.WHERE A PAIR OF DOORS SERVES AN OCCUPANT LOAD OF
 LESS THAN 50 PERSONS IN A GROUP B, F OR S OCCUPANCY,
 MANUALLY OPERATED EDGE- OR SURFACE-MOUNTED BOLTS ARE
 PERMITTED ON THE INACTIVE LEAF. THE INACTIVE LEAF SHALL
 NOT CONTAIN DOORKNOBS, PANIC BARS OR SIMILAR OPERATING
 HARDWARE.
  
 - 4.WHERE A PAIR OF DOORS SERVES A GROUP B, F OR S
 OCCUPANCY, MANUALLY OPERATED EDGE- OR SURFACE-MOUNTED
 BOLTS ARE PERMITTED ON THE INACTIVE LEAF PROVIDED SUCH
 INACTIVE LEAF IS NOT NEEDED TO MEET EGRESS CAPACITY
 REQUIREMENTS AND THE BUILDING IS EQUIPPED THROUGHOUT
 WITH AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 SECTION 903.3.1.1. THE INACTIVE LEAF SHALL NOT CONTAIN
 DOORKNOBS, PANIC BARS OR SIMILAR OPERATING HARDWARE.
  
 8) THE EXISTING DOOR TO THE STAIR ADJACENT TO ROOM 319
 DOES NOT APPEAR TO HAVE 18" ON THE PULL SIDE AS
 REQUIRED BY FBC ACCESSIBILITY SEC. 404.2.4.1.
  
 9) THE ADA SHOWER ON SHEET A-2 IS NOT SHOWN WITH THE
 36" WIDE ENTRY THAT IS REQUIRED BY FBC ACCESSIBILITY
 SEC. 608.2.3.
  
 10) SHOW THE REQUIRED CLEAR FLOOR SPACE AT THE BREAK
 ROOM SINK FOR EITHER A PARALLEL OR FORWARD APPROACH
 THAT IS REQUIRED BY FBC ACCESSIBILITY SEC. 606.2, 305
 AND 305.6.
  
 11) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-02-03 Cont ID  
Sent By jpearson Date 2019-02-03 Time 15:09 Rev Time 0.00
Received By jpearson Date 2019-02-03 Time 15:09 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-10-17 Cont ID  
Sent By jpearson Date 2018-10-17 Time 10:57 Rev Time 0.00
Received By jpearson Date 2018-10-17 Time 09:58 Sent To FIRE
Notes
2018-10-17 10:57:05CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. PROVIDE ACCURATE LOAD CALCULATION FOR EACH SERVICE
 MAIN PER ONE OF THE METHODS IN NEC 220. ESTIMATING THE
 LOAD BASED ON THE OCP SIZE IS NOT A PERMITTED METHOD,
 NOR IS A FUTURE DATA RECORDING. HOW IS IT POSSIBLE TO
 DESIGN THE SYSTEM WITHOUT KNOWING THE ACTUAL LOAD?
 PROVIDE COMPLIANCE. NEC 220 (ACCURATE LOAD CALCULATION
 NOT PROVIDED. A ONE TIME AMP READING IS NOT SUFFICIENT
 INFORMATION TO BASE A LOAD CALCULATION ON. PROVIDE AS
 PREVIOUSLY REQUESTED USING ONE OF THE METHODS PERMITTED
 IN NEC 220.)
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
 9. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-24 Cont ID  
Sent By jpearson Date 2018-08-24 Time 08:23 Rev Time 0.00
Received By jpearson Date 2018-08-23 Time 08:57 Sent To  
Notes
2018-08-23 16:02:12CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE FULL RISER DIAGRAM AND SHOW LOCATION ON SITE
 PLAN OF MAIN LOCATIONS. ALL MAINS SHOULD BE GROUPED.
 NEC 230.72; WPB FBC 107.2.1
 2. PROVIDE ACCURATE LOAD CALCULATION FOR EACH SERVICE
 MAIN PER ONE OF THE METHODS IN NEC 220. ESTIMATING THE
 LOAD BASED ON THE OCP SIZE IS NOT A PERMITTED METHOD,
 NOR IS A FUTURE DATA RECORDING. HOW IS IT POSSIBLE TO
 DESIGN THE SYSTEM WITHOUT KNOWING THE ACTUAL LOAD?
 PROVIDE COMPLIANCE. NEC 220
 3. PLAN STATES THAT THERE ARE 600 AMP FEEDERS TO
 WIREWAY, BUT THEN STATES TO UPGRADE TO COMPLY. THIS
 INDICATES THAT THE DESIGN PROFESSIONAL DOES NOT KNOW
 WHAT IS THERE. HOW IS IT POSSIBLE TO DESIGN WITHOUT
 KNOWING THE ACTUAL CAPACITY OF THE WIRING? PROVIDE
 CORRECTION. NEC 215.2, 215.5, 310.15; WPB FBC 107.2.1
 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 5. PROVIDE AIC RATING OF SERVICE DISCONNECTS AND
 PANELS. NEC 110.3, 110.9
 6. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 7. PROVIDE THE ESSENTIAL ELECTRICAL SYSTEMS REQUIRED
 FOR MEDICAL OFFICE. NEC 517.25, 517.45
 8. CONDUCTOR KEY NOTE 2 SHOWS AN EQUIPMENT GROUNDING
 CONDUCTOR (EGC). IF THIS IS A TAP FROM FPL FEED, AN EGC
 IS NOT PERMITTED. PROVIDE CORRECTION. NEC 250.6
 9. SOME RECEPTACLE OUTLETS ARE SHOWN WITHIN 6 FEET OF A
 SINK WITHOUT THE PROPER GFCI PROTECTION. PROVIDE
 CORRECTION. NEC 210.8
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-03-18 Cont ID  
Sent By scaldero Date 2019-03-18 Time 10:04 Rev Time 0.00
Received By scaldero Date 2019-03-18 Time 09:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-10-17 Cont ID  
Sent By scaldero Date 2018-10-17 Time 11:11 Rev Time 0.00
Received By scaldero Date 2018-10-17 Time 11:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-08-24 Cont ID  
Sent By scaldero Date 2018-08-24 Time 09:59 Rev Time 0.00
Received By scaldero Date 2018-08-24 Time 09:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-03-22 Cont ID  
Sent By rmcdouga Date 2019-03-22 Time 19:04 Rev Time 0.00
Received By rmcdouga Date 2019-03-12 Time 15:02 Sent To  
Notes
2019-03-13 15:02:51B21

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-02-04 Time   Rev Time 0.00
Received By lmarchan Date 2019-01-29 Time 15:36 Sent To  
Notes
2019-01-30 15:36:35RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-14 Cont ID  
Sent By rmcdouga Date 2018-11-14 Time 18:06 Rev Time 0.00
Received By rmcdouga Date 2018-10-11 Time 15:38 Sent To  
Notes
2018-10-12 15:39:07B28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-04 Cont ID  
Sent By rmcdouga Date 2018-09-04 Time 15:59 Rev Time 0.00
Received By rmcdouga Date 2018-08-08 Time 09:50 Sent To  
Notes
2018-08-10 09:50:18B20

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-08-31 Cont ID  
Sent By rmcdouga Date 2018-08-31 Time 18:31 Rev Time 0.00
Received By rmcdouga Date 2018-08-31 Time 18:30 Sent To  
Notes
2018-08-31 18:31:40PROJECT WILL REMAIN A BUSINESS OCCUPANCY.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2019-03-15 Cont ID  
Sent By ccole Date 2019-03-15 Time 16:39 Rev Time 0.00
Received By ccole Date 2019-03-15 Time 16:39 Sent To  
Notes
2019-03-15 16:49:574TH REVIEW FBC-2017 MECHANICAL
 PERMIT #18080413
 2/4/19
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENT #3 FROM THE 3RD REVIEW PRINTED BELOW HAS NOT
 BEEN ADDRESSED. I HAVE PRINTED THE CODE SECTION BELOW.
 PLEASE FORWARD TO THE ARCHITECT OF RECORD.
 PLEASE NOTE THAT UNTIL ADEQUATE INFORMATION IS PROVIDED
 TO VERIFY COMPLIANCE WITH THE EXCEPTION, A HAZARDOUS
 EXHAUST SYSTEM WILL BE REQUIRED, AND DAMPERS ARE
 PROHIBITED IN THE EXHAUST DUCT- SECTION 510.7.1 FBC M.
 SEE SECTIONS 510.7.3 FOR DUCT ENCLOSURE REQUIREMENT,
 AND 510.9 FOR DUCT MATERIALS
  
 3) M1.1: REFER TO SECTION 510.2 EXCEPTION FBC M AND
 VERIFY COMPLIANCE OR A HAZARDOUS EXHAUST SYSTEM
 COMPLYING WITH SECTIONS 510.6- 510.10 SHALL BE
 PROVIDED. THE CURRENT EXHAUST SYSTEM SHOWN IS NOT IN
 COMPLIANCE.
  
 510.2 WHERE REQUIRED.
  
 A HAZARDOUS EXHAUST SYSTEM SHALL BE REQUIRED WHEREVER
 OPERATIONS INVOLVING THE HANDLING OR PROCESSING OF
 HAZARDOUS MATERIALS, IN THE ABSENCE OF SUCH EXHAUST
 SYSTEMS AND UNDER NORMAL OPERATING CONDITIONS, HAVE THE
 POTENTIAL TO CREATE ONE OF THE FOLLOWING CONDITIONS:
  
 1.A FLAMMABLE VAPOR, GAS, FUME, MIST OR DUST IS PRESENT
 IN CONCENTRATIONS EXCEEDING 25 PERCENT OF THE LOWER
 FLAMMABILITY LIMIT OF THE SUBSTANCE FOR THE EXPECTED
 ROOM TEMPERATURE.
  
 2.A VAPOR, GAS, FUME, MIST OR DUST WITH A HEALTH-HAZARD
 RATING OF 4 IS PRESENT IN ANY CONCENTRATION.
  
 3.A VAPOR, GAS, FUME, MIST OR DUST WITH A HEALTH-HAZARD
 RATING OF 1, 2 OR 3 IS PRESENT IN CONCENTRATIONS
 EXCEEDING 1 PERCENT OF THE MEDIAN LETHAL CONCENTRATION
 OF THE SUBSTANCE FOR ACUTE INHALATION TOXICITY.
  
 EXCEPTION: LABORATORIES, AS DEFINED IN SECTION 510.1,
 EXCEPT WHERE THE CONCENTRATIONS LISTED IN ITEM 1 ARE
 EXCEEDED OR A VAPOR, GAS, FUME, MIST OR DUST WITH A
 HEALTH-HAZARD RATING OF 1, 2, 3 OR 4 IS PRESENT IN
 CONCENTRATIONS EXCEEDING 1 PERCENT OF THE MEDIAN LETHAL
 CONCENTRATION OF THE SUBSTANCE FOR ACUTE INHALATION
 TOXICITY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2019-02-04 Cont ID  
Sent By ccole Date 2019-02-04 Time 10:38 Rev Time 0.00
Received By ccole Date 2019-02-04 Time 08:53 Sent To B
Notes
2019-02-04 11:07:163RD REVIEW FBC-2017 MECHANICAL
 PERMIT #18080413
 2/4/19
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M0.2: BASED ON THE SUBMITTED MSDS SHEETS,
 STORAGE OF FLAMMABLE LIQUIDS NOT EXCEEDING THE MAXIMUM
 ALLOWABLE QUANTITIES WILL OCCUR IN THE LAB WHICH
 REQUIRES THE ROOM TO BE DESIGNATED AS A "CONTROL AREA"
 - SEE SECTIONS 202 AND 414.2 FBC. THE CONTROL AREA
 (LAB) IS REQUIRED TO BE SEPARATED FROM OTHER ROOMS AND
 SPACES WITH 1-HR FIRE-RESISTANT RATED CONSTRUCTION-
 SECTION 414.2.4 AND TABLE 414.2.2 FBC B.
  
 2) M1.1: BECAUSE FIRE-BARRIERS ARE NOW REQUIRED TO
 ENCLOSE THE LAB, ALL DUCT PENETRATIONS SHALL BE
 PROTECTED WITH FIRE DAMPERS- SECTION 607.5.2 FBC M.
  
 3) M1.1: REFER TO SECTION 510.2 EXCEPTION FBC M AND
 VERIFY COMPLIANCE OR A HAZARDOUS EXHAUST SYSTEM
 COMPLYING WITH SECTIONS 510.6- 510.10 SHALL BE
 PROVIDED. THE CURRENT EXHAUST SYSTEM SHOWN IS NOT IN
 COMPLIANCE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-10-24 Cont ID  
Sent By ccole Date 2018-10-24 Time 14:59 Rev Time 0.00
Received By ccole Date 2018-10-24 Time 14:08 Sent To  
Notes
2018-10-24 15:05:002ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18080413
 10/24/18
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M0.2: A) REFER TO SECTION 414.1.3 FBC B AND PROVIDE
 THE HAZARDOUS MATERIALS CLASSIFICATIONS FOR ALL
 CHEMICALS LISTED IN THE SCHEDULE AND SUBMIT MSDS SHEETS
 FOR EACH- SEE TABLES 307.1(1) AND 307.1(2). B) SHOW THE
 LOCATION OF THE FUME HOOD ON THE PLAN AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS-
  
 2) M1.1: RECIRCULATION OF AIR FROM THE LAB IS ONLY
 PERMITTED WHERE THE RESULTING AIRSTREAM CONSISTS OF NOT
 MORE THAN 10 PERCENT AIR RECIRCULATED FORM THE ROOM-
 TABLE 403.3.1.1 FOOTNOTE G.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-08-24 Cont ID  
Sent By ccole Date 2018-08-24 Time 16:14 Rev Time 0.00
Received By ccole Date 2018-08-24 Time 13:13 Sent To  
Notes
2018-08-24 16:36:191ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18080413
 8/24/18
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M0.2 & M1.1: THE O/A CALCS AND PLAN SHOW TWO
 ROOMS THAT REQUIRE EXHAUST VENTILATION PER TABLE 403.3
 FBC M: THE ROOMS ARE THE LAB- 1.0 CFMS PER SF AND THE
 PHOTO- 1.0 CFMS PER SF. THE STORAGE ROOM MAY ALSO
 REQUIRE EXHAUST DEPENDING ON WHAT IS BEING STORED
 THERE. PLEASE PROVIDE A LIST OF ALL CHEMICALS OR
 MATERIALS TO BE STORED IN THE ROOM AND THEIR
 QUANTITIES- REFER TO SECTIONS 510.1- 510.10 FBC M.
  
 2) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 FAN COIL UNITS- SECTION C403.2.1 FBC-17 ENERGY
 CONSERVATION.
  
 3) SHEET M1.1 & M5.1: THERE IS A FIRE DAMPER
 INSTALLATION DETAIL ON THE PLAN. PLEASE INDICATE WHERE
 IT IS TO BE INSTALLED
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-11-05 Cont ID  
Sent By gjohnson Date 2018-11-05 Time 14:34 Rev Time 0.00
Received By gjohnson Date 2018-11-05 Time 11:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-08-31 Cont ID  
Sent By gjohnson Date 2018-08-31 Time 07:34 Rev Time 0.00
Received By gjohnson Date 2018-08-30 Time 11:42 Sent To  
Notes
2018-08-31 08:59:411ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE THE DIMENSIONS OF THE SHOWER OPENING SHALL
 COMPLY WITH FBC ACC 608.2.3
  
 2. SHOW COMPLIANCE WITH FBC ACC 608.5.3 ALTERNATE
 ROLL-IN TYPE SHOWER COMPARTMENTS.
 IN ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS, THE
 CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE
 LOCATED ABOVE THE GRAB BAR, BUT NO HIGHER THAN 48
 INCHES ABOVE THE SHOWER FLOOR. WHERE A SEAT IS
 PROVIDED, THE CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT
 SHALL BE LOCATED ON THE SIDE WALL ADJACENT TO THE SEAT
 27 INCHES MAXIMUM FROM THE SIDE WALL BEHIND THE SEAT OR
 SHALL BE LOCATED ON THE BACK WALL OPPOSITE THE SEAT 15
 INCHES MAXIMUM, LEFT OR RIGHT, OF THE CENTERLINE OF THE
 SEAT. WHERE A SEAT IS NOT PROVIDED, THE CONTROLS,
 FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON
 THE SIDE WALL FARTHEST FROM THE COMPARTMENT ENTRY
  
 3. SHOW COMPLIANCE WITH FBC ACC 608.3.3 ALTERNATE
 ROLL-IN TYPE SHOWER COMPARTMENTS.
 IN ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS, GRAB
 BARS SHALL BE PROVIDED ON THE BACK WALL AND THE SIDE
 WALL FARTHEST FROM THE COMPARTMENT ENTRY. GRAB BARS
 SHALL NOT BE PROVIDED ABOVE THE SEAT. GRAB BARS SHALL
 BE INSTALLED 6 INCHES MAXIMUM FROM ADJACENT WALLS.
  
 4. THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE FROM FINISHED FLOOR. PER FBC ACC 609.4
  
 5. TOILET PAPER DISPENSERS SHALL BE 7 INCHES MINIMUM
 AND 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET
 MEASURED TO THE CENTERLINE OF THE DISPENSER. PLEASE
 CLARIFY ON THE PLAN PER FBC ACC 604.7
  
 6. A MINIMUM OF ONE OF THE SINKS IN THE EXAM ROOMS
 SHALL COMPLY WITH FBC ACC 606.2, 606.3 PER FBC ACC
 212.3
  
 7. A LINT TRAP IS REQUIRED FOR THE DISCHARGE OF THE
 WASHING MACHINE IF MACHINE IS A COMMERCIAL MODEL
 PROVIDE MAKE AND MODEL OF EXISTING WASHING MACHINE. PER
 FBC PL 1003.6 EXCEPTIONS(2)
  
 8. PLEASE PROVIDE THE FOLLOWING INFORMATION ON THE PLAN
 PER WPB AMEND TO FBC
 A) THE LEVEL OF ALTERATION.
 B) THE OCCUPANT LOAD.
  
 8. A DRINKING FOUNTAIN MAYBE REQUIRED IF OCCUPANT LOAD
 INCREASED OR CHANGE OF OCCUPANCY PROVIDE NOTE ON THE
 PLAN THE PREVIOUS OCCUPANCY TYPE AND LOAD. PER FBC PL
 TABLE 403.1 AND FBC EX CH 7, 8, 9, 10
  
 9. THE WATER HEATER SHALL COMPLY WITH FBC ENERGY C404.2
 PLEASE PLACE NOTE ON THE PLAN.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop X PERMIT EXTENSION
Rev No 1 Status P Date 2019-09-18 Cont ID  
Sent By spalmer Date 2019-09-18 Time 16:09 Rev Time 0.00
Received By spalmer Date 2019-09-18 Time 16:09 Sent To  
Notes
2019-09-18 16:10:27PERMIT EXTENDED TO DECEMBER 18 2019

Review Stop Z ZONING
Rev No 1 Status N Date   Cont ID  
Sent By awooten Date 2018-08-21 Time   Rev Time 0.00
Received By awooten Date 2018-08-20 Time 17:15 Sent To  
Notes
2018-08-21 15:40:31THE SCOPE OF WORK IS INTERIOR REMODELING/IMPROVEMENTS,
 SO A ZONING REVIEW IS NOT REQUIRED. THE FOOTPRINT OF
 THE BUILDING IIS NOT CHANGING.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 561-822-1449
 [email protected]