Plan Review Details - Permit 18080398
Plan Review Stops For Permit 18080398
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-12-21 Cont ID  
Sent By cthroop Date 2018-12-21 Time 10:04 Rev Time 0.00
Received By cthroop Date 2018-12-21 Time 07:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-09-18 Cont ID  
Sent By rmcdouga Date 2018-09-18 Time 19:40 Rev Time 0.00
Received By rmcdouga Date 2018-09-18 Time 10:42 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-12-13 Cont ID  
Sent By jpearson Date 2018-12-13 Time 14:05 Rev Time 0.00
Received By jpearson Date 2018-12-13 Time 07:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-30 Cont ID  
Sent By fgiaquin Date 2018-08-30 Time 12:59 Rev Time 0.00
Received By fgiaquin Date 2018-08-30 Time 09:00 Sent To  
Notes
2018-08-30 12:59:01ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. LOAD CALCULATION IS NOT ACCURATE. PROVIDE ACCURATE
 LOAD CALCULATION INCLUDING ALL LOADS. NEC 220; FBC RE
 E3602.2
  
 10KW @100%= 5000KW FOR A/C?
  
 APPLIANCE (NOT LABLED) 3000KW?
  
 2. I AM NOT AWARE OF A COOKTOP UNIT THAT IS 20AMP @
 1500WATTS. PLEASE PROVIDE UL OR OTHER NRTL LISTING AND
 ADJUST LOAD CALC ACCORDINGLY. NEC 110.3B
  
 3. JACUZZI TUB RECEPTACLE NEEDS GFCI PROTECTION.
 680.43A3 NEC
  
 4. KITCHEN REQUIRES MINIMUM OF 2-20AMP SMALL APPLIANCE
 CIRCUITS, ONLY ONE ON PLANS. PLEASE PROVIDE CORRECTION.
 210.52B1 NEC
  
 5. SMOKE DETECTOR OUTSIDE OF BEDROOM MUST ALSO BE A
 CARBON MONOXIDE DETECTOR. FBC R315.1
  
 6. NO LOCATION FOR SERVICE EQUIPMENT ON PLAN, PLEASE
 PROVIDE CORRECTION. FBC 107.2.1 INFORMATIONAL NOTE:
 SERVICE RECEPTACLE REQUIRED WITHIN 50' OF SERVICE.
 210.64 NEC
  
 7. POWER UTILITY NORMALLY DOESNT INSTALL RIGID STEEL
 CONDUIT TO METER, USUALLY IT IS PVC TYPE CONDUIT.
 PLEASE CONFIRM WITH POWER UTILITY AND PROVIDE
 CORRECTION. FBC 107.2.1
  
 8. DISHWASHER MUST BE ARC-FAULT AND GFCI PROTECTED
 210.8D, 210.12A NEC
  
 9. PROVIDE ACCURATE PANEL SCHEDULE INDICATING ANY NEW
 OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR
 THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE
 APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12,
 215.5, 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
  
 10. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-08-15 Cont ID  
Sent By lcrespo Date 2018-08-15 Time 15:14 Rev Time 0.00
Received By lcrespo Date 2018-08-15 Time 15:14 Sent To  
Notes
2018-08-15 15:15:01GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN
 PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS
 WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT
 REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE. AT
 THIS TIME. WPB AMENDMENTS TO FBC SEC. 107.2.1.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-01-08 Cont ID  
Sent By cthroop Date 2019-01-08 Time 15:15 Rev Time 0.00
Received By cthroop Date 2019-01-08 Time 14:44 Sent To  
Notes
2019-01-08 14:44:45IMPACT FEES ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-21 Cont ID  
Sent By cthroop Date 2018-12-21 Time 10:04 Rev Time 0.00
Received By cthroop Date 2018-11-28 Time 15:16 Sent To  
Notes
2018-11-29 15:16:30R22

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-18 Cont ID  
Sent By rmcdouga Date 2018-09-18 Time 19:41 Rev Time 0.00
Received By rmcdouga Date 2018-08-08 Time 15:26 Sent To  
Notes
2018-08-09 15:26:34R24

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-01-08 Cont ID  
Sent By cthroop Date 2019-01-08 Time 15:14 Rev Time 0.00
Received By cthroop Date 2019-01-08 Time 15:07 Sent To  
Notes
2019-01-08 15:15:31IMPACT FEES $0.00, MU-2019-411. CT

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-09-18 Cont ID  
Sent By rmcdouga Date 2018-09-18 Time 10:43 Rev Time 0.00
Received By rmcdouga Date 2018-09-18 Time 10:42 Sent To  
Notes
2018-09-18 10:43:12PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-09-07 Cont ID  
Sent By cmontell Date 2018-09-07 Time 06:20 Rev Time 0.00
Received By cmontell Date 2018-09-05 Time 14:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-12-21 Cont ID  
Sent By cthroop Date 2018-12-21 Time 10:04 Rev Time 0.00
Received By cthroop Date 2018-12-21 Time 10:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-08-15 Cont ID  
Sent By lcrespo Date 2018-08-15 Time 15:08 Rev Time 0.00
Received By lcrespo Date 2018-08-15 Time 15:08 Sent To  
Notes
2018-08-15 15:13:4208/15/2018 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON FORM R405-2017 OF THE FLORIDA ENERGY EFFICIENCY
 CODE HAS A ELECTRIC HEATER EF 0.92 BUT ON YOUR SHEET 02
 IT SHOW A TANKLESS AND ON E-1 IT REFERS IT AS A GAS
 TANKLESS, PLEASE CLARIFY. WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 2. THE HOME HAS A GAS APPLIANCE, AS FOR THE COOK TOP IT
 HAS A 20 AMP CIRCUIT TO IT, IT?S ON ELECTRICAL LEGEND
 ON PAGE E-1, AND WILL THE COOK TOP BE GAS OR ELECTRIC,
 PLEASE CLARIFY. WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 3. A SEPARATE PERMIT WILL BE REQUIRED FOR GAS AND A
 REVIEW, WPB AMENDMENTS TO THE FBC SEC. 105.1 REQUIRED
 APPLICATION FOR PERMIT
 4. NO CLEAN OUT REQUIRED AT BASE OF STACK, IF
 PREFERENCE YOU MAY REQUIRE IT BUT NOT IN THE CODE ONLY
 OUTSIDE IS REQUIRED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2018-12-21 Cont ID  
Sent By cthroop Date 2018-12-21 Time 10:04 Rev Time 0.00
Received By cthroop Date 2018-12-21 Time 07:06 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-09-18 Cont ID  
Sent By rmcdouga Date 2018-09-18 Time 18:26 Rev Time 0.00
Received By rmcdouga Date 2018-09-18 Time 18:26 Sent To  
Notes
2018-09-18 18:43:50PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENERGY EFFICIENCY COMPLIANCE FORM R-405 CONTAINS
 SEVERAL ERRORS. PLEASE CORRECT. FBC ENERGY CONSERVATION
 R103.3
  
 A) THE EXTERIOR WALLS ARE LISTED AS WOOD FRAME (R-11)
 AND THE PLANS SHOW CONCRETE BLOCK (R- 4.1).
 B) THE EXTERIOR WALLS ARE NOT ALL 8 FEET IN HEIGHT.
 ONLY THE NORTH WALL IS 8 FEET IN HEIGHT. SEE PLANS.
 C) THE NORTH WALL HAS ONE 10' X 6'-8" SLIDING GLASS
 DOOR (WHICH COUNTS AS A WINDOW) AND NOT TWO WINDOWS AS
 LISTED ON THE FORM.
 D) THE PLANS SPECIFY A TANKLESS WATER HEATER NOT A 40
 GALLON TANK WATER HEATER.
 E) THE FORM LISTS NO ATTIC AND ALSO A VENTED ATTIC.
 PLEASE CLARIFY.
  
 2) PROVIDE A NORTH CARDINAL DIRECTIONAL ARROW ON THE
 PLANS THAT INDICATES THE ORIENTATION OF THE STRUCTURE.
 FBC 107.2.1 & FBC ENERGY CONSERVATION R405.4.2.1
  
 3) PROVIDE A CROSS SECTION OF THE ENTIRE STRUCTURE THAT
 SHOWS A PERPENDICULAR VIEW OF THE ROOF TRUSSES. FBC
 107.2.1
  
 5) SHOW COMPLIANCE WITH FBC-R807 FOR ATTIC ACCESS.
  
 6) THE FLOOR PLAN ON SHEET 1 AND THE SLAB, BEAM AND
 COLUMN PLAN ON SHEET 02 SPECIFIES A 10' TOP OF BEAM
 HEIGHT AT THE FRONT OF THE STRUCTURE. THE ELEVATION
 SHOWS A 14' ELEVATION AT THE FRONT OF THE BUILDING.
 PLEASE CLARIFY. FBC 107.2.1
  
 7) PROVIDE A TRUSS BRACING DETAIL. FBC-R802.10.3
  
 8) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS AND EXTERIOR EGRESS ENTRY DOOR.
  
 9) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS. DUE TO MISSING
 INFORMATION FROM THE CONSTRUCTION DOCUMENTS, ADDITIONAL
 PLAN REVIEW COMMENTS MAY BE GENERATED DURING PLAN
 RESUBMISSION.
  
  
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-12-12 Cont ID  
Sent By awooten Date 2018-12-12 Time   Rev Time 0.00
Received By awooten Date 2018-12-12 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-08-22 Cont ID  
Sent By awooten Date 2018-08-22 Time 11:08 Rev Time 0.00
Received By awooten Date 2018-08-20 Time 17:15 Sent To  
Notes
2018-08-22 11:08:10*************************************ZONING REVIEW
 FAILED*******************************************
  
 THIS PROPERTY IS ZONED SF-7. THIS IS A SINGLE FAMILY
 DISTRICT WHICH ONLY PERMITS ONE SINGLE FAMILY HOUSE PER
 LOT. THERE IS AN EXISTING HOME ON THIS PROPERTY.
  
 I SPOKE WITH OWNER, DAVID JUHE, AND HE ADVISED ME THAT
 THE EXISTING HOME WILL BE DEMOLISHED PRIOR TO RECEIVING
 CERTIFICATE OF OCCUPANY (CO) FOR THE NEW HOME. HE WROTE
 A LETTER STATING SUCH, ADDING TO THE FILE. I AM ALSO
 PLACING A HOLD ON THE CO UNTIL DEMOLITION PERMIT HAS
 BEEN ISSUED.
  
 NEW RESIDENTIAL DEVELOPMENT REQUIRES LANDSCAPING.
  
 PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT. SHOWING THE FOLLOWING:
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 O GROSS LOT SQUARE FOOTAGE MINUS
 O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]