| Plan Review Stops For Permit 18080353 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2018-08-09 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-08-09 |
Time |
16:03 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-08-09 |
Time |
16:03 |
Sent To |
|
|
| Notes |
| 2018-08-09 16:04:23 | ****CORRECTIONS**** | | | W.P.B. PERMIT: 18080353 | | | REVIEWED: AUGUST 9, 2018 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC R = FBC RESIDENTIAL | | | | | | 1. PRODUCT APPROVAL FOR EMAX RIB IS FOR ATTACHMENT TO | | | PURLIN. PLEASE PROVIDE APPROVAL THAT MEETS DESIGN | | | PRESSURE FOR ATTACHMENT TO WOOD DECK. | | | | | | 2. PROVIDE TRUSS SPACING ON PAGE 5 OF 5 WITH EXISTING | | | DECKING THICKNESS. | | | ALSO, FILL OUT MAX. DESIGN PRESSURE LISTED IN APPROVAL | | | AND FOLLOW NOTE ON PAGE 5 OF 5 TO SEE IF ENHANCED | | | FASTENING IS NEEDED, AND ALLOWED WITH THE PRODUCT | | | APPROVAL. | | | | | | 3. IS THE FLAT ROOF GETTING DONE? HOW WILL METAL | | | ROOFING TIE IN TO THE FLAT? | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-08-09 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-08-09 |
Time |
16:03 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-08-07 |
Time |
13:42 |
Sent To |
|
|
| Notes |
| 2018-08-08 13:42:39 | DBATTLES |
|
|
|