Plan Review Details - Permit 18080347
Plan Review Stops For Permit 18080347
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-10-04 Cont ID  
Sent By fgiaquin Date 2018-10-04 Time 07:04 Rev Time 0.00
Received By fgiaquin Date 2018-10-04 Time 06:50 Sent To G
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-15 Cont ID  
Sent By fgiaquin Date 2018-08-15 Time 07:14 Rev Time 0.00
Received By fgiaquin Date 2018-08-15 Time 06:55 Sent To I
Notes
2018-08-15 07:14:14ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 VALUE ADJUSTED TO $16500
  
  
 1. SHOW SIZE OF EXISTING RESIDENTIAL SERVICE. SHOW SIZE
 OF MAINS, SHOW SIZE OF SUB-PANELS. NEC 220.16A1&2,
 220.12, 220.14 FBC RE 3602.1, FBC RE 3602.2, FBC
 107.2.1
  
 2. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-10-04 Cont ID  
Sent By lcrespo Date 2018-10-04 Time 17:07 Rev Time 0.00
Received By lcrespo Date 2018-10-04 Time 17:07 Sent To  
Notes
2018-10-04 17:08:3710/04/18 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-08-10 Cont ID  
Sent By lcrespo Date 2018-08-10 Time 17:08 Rev Time 0.00
Received By lcrespo Date 2018-08-10 Time 17:08 Sent To  
Notes
2018-08-10 17:08:5108/10/2018 1ST PLUMBING/GAS REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE OF EXISTING SYSTEM.
 THERE APPEARS TO BE A DIFFERENCE IN WHAT WAS SUBMITTED
 AND WHAT IS IN OUR RECORDS. I HAVE PUT TWO DIFFERENT
 PRIOR GAS DRAWINGS FOR REFREANCE ONLY, ONE SHOWS A POOL
 HEATER AT 400,000 BTU'S AND GAS GRILL 60,800 BTU'S IN
 2011 AND A SECOND ONE IN 2012 SHOWS AN OVEN AT 100,200
 BTU'S. WHAT YOU HAVE ON THE SUBMITTED ISOMETRIC DOES
 NOT MATCH, PLEASE REVIEW AND BRIEFLY THAT THE BTU LOAD
 OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE TOTAL
 BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS
 PROPERLY SIZED. IF UNDERSIZED, THE EXISTING SYSTEM MUST
 BE REDONE TO ENSURE A SAFE OPERATING SYSTEM. SUBMIT A
 GAS PIPING RISER DIAGRAM THAT SHOWS THE TYPE OF
 EXISTING APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE
 PIPE SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. 2017 FBC FUEL GAS RES SECS. G2413.4.1,
 G2413.4.2.
 2. PLEASE PUT THE ADDRESS AND CUSTOMER INFORMATION ON
 ISOMETRIC DRAWING, WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 3. THE CODE ON THE ISOMETRIC REFERS TO 2014 AND WE ARE
 ON 2017, PLEASE UPDATE. WPB AMENDMENTS TO THE FBC SEC.
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-08-09 Cont ID  
Sent By destabro Date 2018-08-09 Time 11:13 Rev Time 0.00
Received By destabro Date 2018-08-09 Time 11:13 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-04 Cont ID  
Sent By lcrespo Date 2018-10-04 Time 17:08 Rev Time 0.00
Received By lcrespo Date 2018-10-01 Time 14:03 Sent To  
Notes
2018-10-02 14:04:12RESUB ROUTED TO FGIAQUINTO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-15 Cont ID  
Sent By fgiaquin Date 2018-08-15 Time 07:14 Rev Time 0.00
Received By fgiaquin Date 2018-08-07 Time 14:59 Sent To  
Notes
2018-08-08 14:59:59ROUTED TO HISTORIC INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2018-08-09 Cont ID  
Sent By destabro Date 2018-08-09 Time 11:13 Rev Time 0.00
Received By destabro Date 2018-08-09 Time 11:13 Sent To G
Notes
2018-08-09 11:14:308/9/2018 - GENERATOR PLACEMENT ALLOWED TO ENCROACH 4'
 INTO SIDE SETBACK, DLE