Plan Review Details - Permit 18080301
Plan Review Stops For Permit 18080301
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-27 Cont ID  
Sent By fgiaquin Date 2018-08-27 Time 11:41 Rev Time 0.00
Received By fgiaquin Date 2018-08-27 Time 11:11 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-15 Cont ID  
Sent By fgiaquin Date 2018-08-15 Time 05:44 Rev Time 0.00
Received By fgiaquin Date 2018-08-15 Time 05:39 Sent To M
Notes
2018-08-15 05:39:58ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-08-17 Cont ID  
Sent By pleduc Date 2018-08-17 Time   Rev Time 0.00
Received By pleduc Date 2018-08-17 Time 14:54 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-08-10 Cont ID  
Sent By pleduc Date 2018-08-10 Time   Rev Time 0.00
Received By pleduc Date 2018-08-09 Time 16:30 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-27 Cont ID  
Sent By fgiaquin Date 2018-08-27 Time 11:42 Rev Time 0.00
Received By fgiaquin Date 2018-08-15 Time 13:12 Sent To  
Notes
2018-08-16 13:12:26RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-15 Cont ID  
Sent By cpuell Date 2018-08-15 Time 10:25 Rev Time 0.00
Received By cpuell Date 2018-08-07 Time 13:55 Sent To  
Notes
2018-08-08 13:56:01ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2018-08-15 Cont ID  
Sent By fgiaquin Date 2018-08-15 Time 06:54 Rev Time  
Received By fgiaquin Date   Time   Sent To I
Notes
2018-08-15 06:54:43NOT REQURIED PER H.MOSER