Plan Review Details - Permit 18080279
Plan Review Stops For Permit 18080279
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-10-16 Cont ID  
Sent By shill Date 2018-10-16 Time 15:42 Rev Time 0.00
Received By shill Date 2018-10-16 Time 15:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-10-15 Cont ID  
Sent By shill Date 2018-10-15 Time 10:02 Rev Time 0.00
Received By shill Date 2018-10-12 Time 16:20 Sent To  
Notes
2018-10-15 10:03:30****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1-2. OK
  
 3. COMMENT FROM PREVIOUS LIST - THI SINFORMATION MAY BE
 SENT VIA EMAIL.
  
 FBC 109, VALUE IS TO INCLUDE ALL LABOR, MATERIALS,
 OVERHEAD, PROFIT, DESIGN FEES, INCLUDING ITEMS PROVIDED
 BY OTHERS.
  
 4. COMMENT FROM PREVIOUS LIST - THIS INFORMATION MAY BE
 SENT VIA EMAIL.
  
 PLEASE ADVISE, WHAT FLOORING AND UNDERLAYMENT ARE
 PROPOSED? PLEASE ADVISE VIA EMAIL PRIOR TO
 RESUBMITTING. IF THE UNDERLAYMENT PRODUCT PROPOSED IS
 NOT ONE FOR WHICH WE HAVE TEST REPORTS ON FILE, THE
 FOLLOWING REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 5. OK - PER CONTRACTOR, WINDOWS/DOORS ARE NOT WITHIN
 THE SCOPE OF THIS PERMIT.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-09-02 Cont ID  
Sent By shill Date 2018-09-02 Time 15:57 Rev Time 0.00
Received By shill Date 2018-09-02 Time 15:57 Sent To  
Notes
2018-09-02 16:01:10****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC B 1609, NEW SLIDERS AND WINDOW ARE PROPOSED, BUT
 NO DESIGN PRESSURES SPECIFIED.
  
 2. FBC B 1609, CONSTRUCTION NOTES STATE THIS IS
 EXPOSURE B, REVISE.
  
 3. FBC 109, VALUE IS TO INCLUDE ALL LABOR, MATERIALS,
 OVERHEAD, PROFIT, DESIGN FEES, INCLUDING ITEMS PROVIDED
 BY OTHERS.
  
 4. PLEASE ADVISE, WHAT FLOORING AND UNDERLAYMENT ARE
 PROPOSED? PLEASE ADVISE VIA EMAIL PRIOR TO
 RESUBMITTING. IF THE UNDERLAYMENT PRODUCT PROPOSED IS
 NOT ONE FOR WHICH WE HAVE TEST REPORTS ON FILE, THE
 FOLLOWING REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 5. ARE THE WINDOW AND SLIDER PRODUCTS PROPOSED KNOWN AT
 THIS TIME? IF YES, PROVIDE PRODUCT APPROVALS REVIEWED
 BY DESIGNER OF RECORD. IF NO, THIS WILL BE A PROVISO
 ITEM, SUBMIT FOR REVIEW PRIOR TO INSTALLATION.
  
 ON THE PRODUCT APPROVALS, INDICATE METHOD OF
 INSTALLATION TO SHOW COMPLIANCE WITH DESIGN PRESSURES
 SPECIFIED.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-10-01 Cont ID  
Sent By jpearson Date 2018-10-01 Time 09:28 Rev Time 0.00
Received By jpearson Date 2018-10-01 Time 08:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-29 Cont ID  
Sent By jpearson Date 2018-08-29 Time 11:12 Rev Time 0.00
Received By jpearson Date 2018-08-29 Time 06:43 Sent To  
Notes
2018-08-29 11:12:08CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PERMIT APPLICATION STATES THAT THE
 ELECTRICAL PANEL WILL BE CHANGED. PROVIDE LOCATION OF
 PANEL ON PLANS. WPB FBC 107.2.1
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4
 3. SHOW REQUIRED RECEPTACLE OUTLETS PER NEC 210.52 IN
 AREAS REMODELED. NEC 210.52; WPB FBC 107.2.1
 4. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12
 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D)
 6. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-09-18 Cont ID  
Sent By pleduc Date 2018-09-18 Time   Rev Time 0.00
Received By pleduc Date 2018-09-18 Time 11:59 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-08-09 Cont ID  
Sent By pleduc Date 2018-08-09 Time   Rev Time 0.00
Received By pleduc Date 2018-08-08 Time 12:16 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-15 Cont ID  
Sent By shill Date 2018-10-15 Time 10:04 Rev Time 0.00
Received By shill Date 2018-09-14 Time 11:03 Sent To  
Notes
2018-09-17 11:03:57B26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-04 Cont ID  
Sent By gjohnson Date 2018-09-04 Time 15:03 Rev Time 0.00
Received By gjohnson Date 2018-08-06 Time 16:01 Sent To  
Notes
2018-08-07 16:02:01B17

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-10-04 Cont ID  
Sent By jesmith Date 2018-10-04 Time 09:55 Rev Time 0.00
Received By jesmith Date 2018-10-04 Time 09:55 Sent To  
Notes
2018-10-04 10:27:532ND REVIEW:
 PLUMBING COMMENTS: APPROVED
  
 1. REVIEWED REVISED PLAN FOR WHICH PLUMBING HAD BEEN
 PREVIOUSLY APPROVED BY GEORGE JOHNSON. THERE WAS NO
 CHANGE THAT APPLIED TO PLUMBING.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-09-04 Cont ID  
Sent By gjohnson Date 2018-09-04 Time 15:02 Rev Time 0.00
Received By gjohnson Date 2018-09-04 Time 15:02 Sent To  
Notes
***NONE***