Plan Review Details - Permit 18080276
Plan Review Stops For Permit 18080276
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-11-01 Cont ID  
Sent By dbattles Date 2018-11-01 Time 09:44 Rev Time 0.00
Received By dbattles Date 2018-11-01 Time 09:44 Sent To  
Notes
2018-11-01 09:49:39PROVISO:
 1. TRUSS SUBMITTAL TO INSPECTOR PRIOR TO INSTALL.
 2. STAIRS, GUARD RAILS ENGINEERING SUBMITTAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-09-14 Cont ID  
Sent By dbattles Date 2018-09-14 Time 08:01 Rev Time 0.00
Received By dbattles Date 2018-09-12 Time 13:15 Sent To  
Notes
2018-09-14 08:03:01W.P.B. PERMIT: 18080276 (GARAGE)
 REVIEWED: SEPTEMBER 13, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC A = AMENDMENTS TO THE FLORIDA BUILDING CODE,6TH
 EDITION (2017)
 FBC B = FBC BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 [FBC AMENDED 105]SEPARATE PERMIT THROUGH ENGINEERING
 FOR DRIVEWAY ACCESS. CONTACT 561-494-1040, OR ON THE
 WEB: HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-
 WORKS/ENGINEERING-SERVICES
  
 1. [FBC 107.2.5]SHEET 1 WIND INFORMATION-REMOVE LEVEL
 OF ALTERATION 2. THIS WOULD BE NEW CONSTRUCTION R-3.
  
 2. [FBC R301.4]DEAD LOAD AND[FBC R301.5]LIVE LOAD
 PROVIDE LOADS FOR FLOORING AND LOADS FOR ROOFING ON
 SHEET 4.
  
 3. [FBC AMENDED 107.2.1.2]PROVIDE TWO COPIES OF PRODUCT
 APPROVAL FOR GARAGE DOOR.
  
 4. [FBC 107.3.4.1]A CONSTRUCTION GUARDRAIL DETAIL,
 PREPARED BY A DESIGN PROFESSIONAL LICENSED UNDER FS471
 OR FS481, IS REQUIRED TO BE SUBMITTED, REVIEWED AND
 ISSUED BY THE CITY OF WEST PALM BEACH, OR INDICATE THAT
 IT WILL BE DEFERRED.
 *SUBJECT TO THE INSPECTOR'S DISCRETION, THIS MAY BE
 ACCEPTED IN THE FIELD AT TIME OF INSPECTION.
  
 5. [FBC AMENDED 107.3.4.1]SUBMIT TRUSS SHOP DRAWINGS,
 OR INDICATE THAT THE SUBMITTAL WILL BE DEFERRED.
 DEFERRED SUBMITTALS TO BE REVIEWED PRIOR TO
 INSTALLATION.
  
 6. [FBC R3-1.2(6)]PROVIDE ROOFING WIND DIAGRAM THAT
 MATCHES THE ROOF CONDITION OF THIS HOUSE FOR ZONES
 1,2,& 3.
  
 7. [FBC R304.2]MINIMUM DIMENSIONS.
 HABITABLE ROOMS SHALL BE NOT LESS THAN 7 FEET (2134 MM)
 IN ANY HORIZONTAL DIMENSION. ALSO, LABEL EGRESS WINDOW
 FOR THE BEDROOM.
  
 8. [FBC 107.2.5]SHEET 2: 1/2 STAIR DETAIL. WITH THE
 WEIGHT OF WOOD STAIRCASE VERIFY IF THE 4? SLAB IS
 SUFFICIENT BEARING.
  
 9. [FBC 107.2.5]SHEET 4:
 A.UPDATE CONNECTOR H10A TO REFERENCE CURRENT FL 10456.2
 B.FLOOR FRAMING PLAN REFERANCES SECTION 2/5 AT BALCONY,
 BUT THIS DETAIL IS FOR STAIRS WITH POSTS. PROVIDE
 DETAIL FOR CANTILEVER BALCONY INSTEAD OF STAIR LANDING.
  
 10. [FBC 107.2.5]SHEET 5: SECTION 2/5 SECOND FLOOR
 BALCONY. 5/8 CDX PLYWOOD IS CALLED OUT UNDER THE
 DECKING MATERIAL. ID THIS EXTERIOR GRADE AND HOW ARE
 EDGES PROTECTED FROM WATER?
  
 11. [FBC R309.1]FLOOR SURFACE.
 THE AREA OF FLOOR USED FOR PARKING OF AUTOMOBILES OR
 OTHER VEHICLES SHALL BE SLOPED TO FACILITATE THE
 MOVEMENT OF LIQUIDS TO A DRAIN OR TOWARD THE MAIN
 VEHICLE ENTRY DOORWAY.
  
 12. [FBC ENERGY R401.2]PROVIDE ENERGY CALCULATIONS TO
 MEET REQUIREMENTS IN R401.2 RESIDENTIAL ENERGY CODE.
 CHOOSE METHOD IN R401.2 AND SUPPLY DOCUMENTATION.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2018-11-20 Cont ID  
Sent By jpearson Date 2018-11-20 Time 09:23 Rev Time 0.00
Received By jpearson Date 2018-11-20 Time 09:23 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2018-11-09 Cont ID  
Sent By jpearson Date 2018-11-09 Time 08:56 Rev Time 0.00
Received By jpearson Date 2018-11-09 Time 08:56 Sent To  
Notes
2018-11-09 08:56:03CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3603.3 (NOT PROVIDED, NOTED
 THAT WILL BE PROVIDED BEFORE INSPECTION.)
 3. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9; FBC RE E3603.3 (NOT PROVIDED AS NOTED
 ON RESPONSE LETTER.)
 4. CORRECTED.
 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10 (NOT PROVIDED.)
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
 9. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. NEC 220; FBC RE E3602.2 (LOAD CALCULATION
 PROVIDED DOES NOT INCLUDE ALL LOADS, DOES NOT INCLUDE
 GARAGE PANEL, LOAD FOR TANKLESS HEATER NOT INCLUDED.
 PROVIDE LOAD CALCULATION FOR ENTIRE SERVICE AS
 REQUESTED.)
 10. CORRECTED.
 11. RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS SHALL
 HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8(A)(9); FBC RE E3902.9 (NOT PROVIDED.)
 12. LIGHTING MUST MAINTAIN PROPER CLEARANCES FROM THE
 NEAREST POINT OF STORAGE SPACE IN A CLOTHES CLOSET.
 PROVIDE CORRECTION. NEC 410.16; FBC RE E4003.12 (NOT
 CORRECTED.)
 13. CORRECTED.
 14. CORRECTED.
 15. CORRECTED.
 16. CORRECTED.
 17. CORRECTED.
 18. CORRECTED.
 19. CORRECTED.
 20. CORRECTED.
 21. CORRECTED.
 22. CORRECTED.
 23. NEW RISER PROVIDED SHOWS 4/0 ALUMINUM WIRE FROM
 METER TO SERVICE DISCONNECT AND FROM SERVICE DISCONNECT
 TO INTERIOR PANELS. THIS WIRE SIZE IS NOT RATED FOR 200
 AMPS. PROVIDE CORRECTION. NEC 310.15(B)(16); FBC RE
 E3705.1 (NOT CORRECTED.)
 24. FEED TO INTERIOR PANELS FROM SERVICE DISCONNECT IS
 REQUIRED TO HAVE AN EQUIPMENT GROUNDING CONDUCTOR,
 SIZED PER CODE. PROVIDE CORRECTION. NEC 250.122; FBC RE
 E3704.6, 3607.3.1 (ATTEMPTED CORRECTION IS NOT CODE
 COMPLIANT.)
 25. SPECIFY WIRE AND CONDUIT SIZE FOR OVERHEAD MAST TO
 FPL. WPB FBC 107.2.1; NEC 310.15(B)(7); FBC RE E3603.1
 (WIRE SIZE SPECIFIED IS NOT TO CODE.)
 26. GROUNDING ELECTRODE CONDUCTOR SHOULD NOT BE WIRED
 TO METER CAN AND SERVICE DISCONNECT AND INTERIOR PANEL.
 IT IS CONNECTED AT EITHER THE METER CAN OF THE FIRST
 MEANS OF DISCONNECT. PROVIDE CORRECTION. NEC 250.6 (NOT
 CORRECTED.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-10-11 Cont ID  
Sent By jpearson Date 2018-10-11 Time 09:54 Rev Time 0.00
Received By jpearson Date 2018-10-11 Time 09:54 Sent To  
Notes
2018-10-11 09:54:43CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. AFCI PROTECTION SHOWN IN NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902 (NOT CORRECTED. HAND
 WRITTEN NOTES ARE NOT ACCEPTABLE. THE HAND WRITTEN NOTE
 IS NOT CODE COMPLIANT.)
 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3603.3 (NOT PROVIDED, TO BE
 PROVIDED PRIOR TO INSPECTION.)
 3. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9; FBC RE E3603.3 (NOT PROVIDED.)
 4. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1 (NOT PROVIDED.)
 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10 (NOT PROVIDED.)
 6. CORRECTED.
 7. CORRECTED.
 8. A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE
 ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND
 CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF
 GROUNDING ELECTRODE SYSTEM AND WIRING. NEC 250.32; FBC
 RE E3607.3 (GROUNDING ELECTRODE CONDUCTOR SHOULD NOT BE
 INSTALLED TO SUB-PANEL AT MAIN SERVICE. THE CONDUITS
 FEEDING EACH OF THE SUB-PANELS AFTER THE FIRST MEANS OF
 DISCONNECT SHOULD INCLUDE AN EQUIPMENT GROUNDING
 CONDUCTOR SIZED PER NEC 250.122. PROVIDE CORRECTION.)
 9. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. NEC 220; FBC RE E3602.2 (LOAD CALCULATION
 PROVIDED DOES NOT INCLUDE ALL LOADS, DOES NOT INCLUDE
 GARAGE PANEL, LOAD FOR TANKLESS HEATER NOT INCLUDED.
 PROVIDE LOAD CALCULATION FOR ENTIRE SERVICE AS
 REQUESTED. HAND WRITTEN CORRECTIONS ARE NOT
 ACCEPTABLE.)
 10. CORRECTED.
 11. CORRECTED.
 12. NOT ON THIS PLAN.
 13. PROVIDE LOCATION OF METER CAN AND PANEL ON PLAN.
 WPB FBC 107.2.1 (LOCATION OF METER AND SERVICE
 DISCONNECTS NOT SHOWN.)
 14. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR
 ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. NEC 210.8, 210.12, 210.19, 210.20,
 215.5, 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
 (NOT PROVIDED.)
 15. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FS
 481.229; WPB FBC 107.2.1, 107.3.5.1.2 (NOT PROVIDED.
 EACH SHEET SUPPLIED AS PART OF PLAN MUST BEAR THE
 PRINTED NAME AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN. IF THAT PERSON IS LICENSED, IT MUST
 ALSO INCLUDE THAT LICENSE NUMBER.)
 16. CORRECTED.
 17. CORRECTED.
 18. CORRECTED.
 19. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14 (NOT
 PROVIDED.)
 20. NOT ON THIS PLAN.
 21. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN.
 PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE
 E3703.4, E3901.6 (NOT CORRECTED.)
 22. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE
 OUTLETS IN GARAGE. PROVIDE CORRECTION. NEC 210.8; FBC
 RE E3902.2 (INCLUDES GARAGE DOOR OPENER, NOT
 CORRECTED.)
 23. PROVIDE WEATHER PROOF GFCI PROTECTED RECEPTACLE
 OUTLET FOR EACH BALCONY ACCESSIBLE FROM THE DWELLING
 UNIT. NEC 210.52(E)(3); FBC RE E3901.7 (NOT PROVIDED.)
  
 NEW COMMENTS:
  
 24. NEW RISER PROVIDED SHOWS 4/0 ALUMINUM WIRE FROM
 METER TO SERVICE DISCONNECT AND FROM SERVICE DISCONNECT
 TO INTERIOR PANELS. THIS WIRE SIZE IS NOT RATED FOR 200
 AMPS. PROVIDE CORRECTION. NEC 310.15(B)(16); FBC RE
 E3705.1
 25. FEED TO INTERIOR PANELS FROM SERVICE DISCONNECT IS
 REQUIRED TO HAVE AN EQUIPMENT GROUNDING CONDUCTOR,
 SIZED PER CODE. PROVIDE CORRECTION. NEC 250.122; FBC RE
 E3704.6, 3607.3.1
 26. SPECIFY WIRE AND CONDUIT SIZE FOR OVERHEAD MAST TO
 FPL. WPB FBC 107.2.1; NEC 310.15(B)(7); FBC RE E3603.1
 27. GROUNDING ELECTRODE CONDUCTOR SHOULD NOT BE WIRED
 TO METER CAN AND SERVICE DISCONNECT AND INTERIOR PANEL.
 IT IS CONNECTED AT EITHER THE METER CAN OF THE FIRST
 MEANS OF DISCONNECT. PROVIDE CORRECTION. NEC 250.6
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-28 Cont ID  
Sent By jpearson Date 2018-08-28 Time 17:26 Rev Time 0.00
Received By jpearson Date 2018-08-28 Time 17:26 Sent To  
Notes
2018-08-28 17:26:21CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. AFCI PROTECTION SHOWN IN NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902
 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3603.3
 3. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9; FBC RE E3603.3
 4. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 6. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
 7. RISER DIAGRAM SHOWS A SINGLE GROUND ROD AS A
 SUPPLEMENTAL GROUNDING ELECTRODE. THIS SUPPLEMENTAL
 GROUNDING ELECTRODE NEEDS TO BE AUGMENTED BY AN
 ADDITIONAL ELECTRODE AT LEAST 6 FEET AWAY OR PROVIDE
 EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS.
 NEC 250.53(A)(2); FBC RE E3608.4
 8. A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE
 ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND
 CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF
 GROUNDING ELECTRODE SYSTEM AND WIRING. NEC 250.32; FBC
 RE E3607.3
 9. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. NEC 220; FBC RE E3602.2
 10. RECEPTACLES INSTALLED TO SERVE THE COUNTER TOP IN
 KITCHEN REQUIRE GFCI PROTECTION. PROVIDE CORRECTION.
 NEC 210.8; FBC RE E3902.6
 11. RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS SHALL
 HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8(A)(9); FBC RE E3902.9
 12. LIGHTING MUST MAINTAIN PROPER CLEARANCES FROM THE
 NEAREST POINT OF STORAGE SPACE IN A CLOTHES CLOSET.
 PROVIDE CORRECTION. NEC 410.16; FBC RE E4003.12
 13. PROVIDE LOCATION OF METER CAN AND PANEL ON PLAN.
 WPB FBC 107.2.1
 14. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR
 ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. NEC 210.8, 210.12, 210.19, 210.20,
 215.5, 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
 15. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FS
 481.229; WPB FBC 107.2.1, 107.3.5.1.2
 16. ONLY ONE SERVICE PER RESIDENTIAL ADDRESS IS
 PERMITTED. PROVIDE CORRECTION. WPB FBC 107.2.1; NEC
 230.2; FBC RE E3601.2
 17. A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A
 BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE
 DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE
 FEEDER OR BRANCH CIRCUIT. NEC 225.30
 18. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR PANEL A. NEC 225.31,
 225.32
 19. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
 20. PLAN SHOWS ONE SMALL APPLIANCE CIRCUIT FOR KITCHEN
 RECEPTACLE OUTLETS. A MINIMUM OF TWO 20 AMPERE BRANCH
 CIRCUIT SHALL BE PROVIDED TO SUPPLY KITCHEN COUNTERTOP
 RECEPTACLE OUTLET(S). PROVIDE CORRECTION. NEC
 210.11(C)(1) , FBC RE E3703.2
 21. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN.
 PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE
 E3703.4, E3901.6
 22. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE
 OUTLETS IN GARAGE. PROVIDE CORRECTION. NEC 210.8; FBC
 RE E3902.2
 23. PROVIDE WEATHER PROOF GFCI PROTECTED RECEPTACLE
 OUTLET FOR EACH BALCONY ACCESSIBLE FROM THE DWELLING
 UNIT. NEC 210.52(E)(3); FBC RE E3901.7
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2018-10-29 Cont ID  
Sent By fmittner Date 2018-10-29 Time 16:31 Rev Time 0.00
Received By fmittner Date 2018-10-29 Time 16:31 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2018-08-24 Cont ID  
Sent By fmittner Date 2018-08-24 Time 16:13 Rev Time 0.00
Received By fmittner Date 2018-08-24 Time 16:13 Sent To  
Notes
2018-08-24 16:14:10REQUIRES HPB APPROVAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2018-11-20 Time   Rev Time 0.00
Received By lmarchan Date 2018-11-14 Time 15:23 Sent To  
Notes
2018-11-15 15:24:00RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-11-14 Cont ID  
Sent By cmontell Date 2018-11-14 Time 06:34 Rev Time 0.00
Received By cmontell Date 2018-11-14 Time 06:34 Sent To  
Notes
2018-11-06 12:58:59R32
 **TRAVELLING WITH 18070946**

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-01 Cont ID  
Sent By dbattles Date 2018-11-01 Time 09:44 Rev Time 0.00
Received By dbattles Date 2018-10-04 Time 15:30 Sent To  
Notes
2018-10-05 15:31:08LIBRARY
 **TRAVELLING WITH 18070946**

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-25 Cont ID  
Sent By dbattles Date 2018-09-25 Time 13:40 Rev Time 0.00
Received By skennedy Date 2018-08-06 Time 10:33 Sent To  
Notes
2018-09-25 13:40:50SEE REVIEW ON 18070496
2018-09-14 08:03:30STILL NEED MECH AND PLUMB
2018-08-07 15:08:51R30
 **TRAVELLING WITH 18070946**

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2018-11-21 Cont ID  
Sent By dbattles Date 2018-11-21 Time 15:54 Rev Time 0.00
Received By dbattles Date 2018-11-21 Time 15:53 Sent To  
Notes
2018-11-21 15:55:05MU-2018-039114-0000
 PAID ON 11/20/18
 STAMP ON PLANS-OK

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-11-01 Cont ID  
Sent By dbattles Date 2018-11-01 Time 09:45 Rev Time 0.00
Received By dbattles Date 2018-11-01 Time 09:45 Sent To  
Notes
2018-11-01 09:46:38UPON APPROVAL OF ZONING, PLUMBING AND ELECTRICAL PLEASE
 CHACK OUT ONE COPY TO TAKE TO COUNTY.
  
 [FBC AMENDED 109]PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-09-14 Cont ID  
Sent By dbattles Date 2018-09-14 Time 08:07 Rev Time 0.00
Received By dbattles Date 2018-09-14 Time 08:07 Sent To  
Notes
2018-09-14 08:07:09[FBC AMENDED 109]PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-11-14 Cont ID  
Sent By cmontell Date 2018-11-14 Time 06:29 Rev Time 0.00
Received By cmontell Date 2018-11-14 Time 06:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-10-31 Cont ID  
Sent By cmontell Date 2018-10-31 Time 14:57 Rev Time 0.00
Received By cmontell Date 2018-10-31 Time 14:57 Sent To  
Notes
2018-10-31 14:57:37NO PLANS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-09-25 Cont ID  
Sent By skennedy Date 2018-09-25 Time 13:39 Rev Time 0.00
Received By skennedy Date 2018-09-25 Time 13:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-11-13 Cont ID  
Sent By lcrespo Date 2018-11-13 Time 16:42 Rev Time 0.00
Received By lcrespo Date 2018-11-13 Time 16:42 Sent To  
Notes
2018-11-13 16:43:3211/13/18 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-10-30 Cont ID  
Sent By jesmith Date 2018-10-30 Time 11:42 Rev Time 0.00
Received By jesmith Date 2018-10-30 Time 11:19 Sent To  
Notes
2018-10-30 11:42:16CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 2ND REVIEW:
 PLUMBING COMMENTS: DENIED
  
 1. PLAN SHEET 2 OF 7 SHOWS A 30? WIDE SPACE BETWEEN THE
 TWO WALLS AT THE WATER CLOSET, BUT TWO OTHER DIMENSIONS
 BETWEEN THE TWO WALLS SHOW A 2?-8? SPACE. PLEASE
 CLARIFY IN ACCORDANCE WITH WPB FBC 107.2.1.
 2. PROVIDE DIMENSIONS ON PLAN SHEET 2 OF 7 FOR THE
 FOLLOWING AS REQUIRED BY WPB FBC 107.2.1. SECOND
 REQUEST
 A. SHOW THE SHOWER COMPARTMENT ACCESS AND EGRESS
 OPENING SHALL HAVE A CLEAR AND UNOBSTRUCTED FINISHED
 WIDTH OF NOT LESS THAN 22 INCHES PER FBC RES P2708.1.1
 B. PLEASE NOTE ON THE PLAN WHAT TYPE OF COVERING OVER
 THE SHOWER OPENING A DOOR OR SHOWER CURTAIN IT SHALL
 COMPLY WITH FBC RES P2705.1(4)(5); NOTE THAT A SHOWER
 DOOR MUST OPEN OUTWARD PER P2708.1 AND MUST BE
 CONSIDERED WHEN PROVIDING CLEARANCE
 C. SHOW A CLEARANCE OF NOT LESS THAN 21 INCHES IN FRONT
 OF A WATER CLOSET OR LAVATORY TO ANY WALL, FIXTURE OR
 DOOR PER FBC RES P2705.1, (4) (5). IT MAY BE NECESSARY
 TO PROVIDE A CUT SHEET FOR LAVATORY SHOWING PHYSICAL
 DIMENSIONS AND THAT IT WILL FIT IN THE SPACE WHILE
 PROVIDING THE REQUIRED CLEARANCES.
  
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN
 ACCORDANCE WITH FS 471, 481 & FAC 61G15) INTO THE
 ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED
 SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS
 SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-09-14 Cont ID  
Sent By gjohnson Date 2018-09-14 Time 10:43 Rev Time 0.00
Received By gjohnson Date 2018-09-14 Time 09:52 Sent To  
Notes
2018-09-14 12:29:361ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE LAVATORY OVER THE TOILET IS PROHIBITED THE
 FIXTURE SHALL BE MOUNTED ADJACENT TO EACH OTHER. PER
 FBC RES P2705.1(4)(5)
  
 2. THE WASHING MACHINE ON GROUND FLOOR IS NOT VENTED
 PROPERLY IT CANNOT CONNECT TO SOIL STACK WITHOUT
 SEPARATE VENT IT SHALL COMPLY WITH ONE OF THE VENTING
 SYSTEMS SHOWN IN FBC RES CH 31 PER FBC RES P3101.2.1
  
 3. THE WASHING MACHINE STAND PIPE, P-TRAP AND FIXTURE
 DRAIN SHALL BE A MIN OF 2" PER FBC RES P2601.1 AND FBC
 PL SAC 406.2 AND TABLE 709.1
  
 4. PROVIDE MANUFACTURE SPECIFICATIONS AND SIZING
 CALCULATIONS FOR THE ELECTRIC TANKLESS HEATER. PER WPB
 AMEND TO FBC 107.2.1
  
 5. PLEASE PROVIDE ALL DIMENSIONS FOR BATHROOM INCLUDING
 BETWEEN THE FRONT OF THE TOILET AND THE SHOWERR TO
 COMPLY WITH FBC RES P2705.1(4)(5)
  
 6. PLEASE NOTE ON THE PLAN WHAT TYPE OF COVERING OVER
 THE SHOWE OPENING A DOOR OR SHOWER CURTAIN IT SHALL
 COMPLY WITH FBC RES P2705.1(4)(5)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2018-11-01 Cont ID  
Sent By dbattles Date 2018-11-01 Time 09:47 Rev Time 0.00
Received By dbattles Date 2018-11-01 Time 09:47 Sent To  
Notes
2018-11-01 09:48:26PRODUCT APPROVALS APPROVED
 5V METAL ROOF

Review Stop Z ZONING
Rev No 3 Status P Date 2018-11-13 Cont ID  
Sent By fmittner Date 2018-11-13 Time 15:57 Rev Time 0.00
Received By fmittner Date 2018-11-13 Time 15:57 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2018-10-29 Cont ID  
Sent By fmittner Date 2018-10-29 Time 16:31 Rev Time 0.00
Received By fmittner Date 2018-10-29 Time 16:31 Sent To  
Notes
2018-10-29 16:45:23REQUIRES SEPARATE LANDSCAPE PERMIT AND MASTER PERMIT
 SHALL INCLUDE SITE PLAN (SURVEY PROVIDED INDICATES 2
 STORY MAIN HOUSE).

Review Stop Z ZONING
Rev No 1 Status F Date 2018-08-24 Cont ID  
Sent By fmittner Date 2018-08-24 Time 16:14 Rev Time 0.00
Received By fmittner Date 2018-08-24 Time 16:14 Sent To  
Notes
2018-08-24 16:14:40REQUIRES HPB APPROVAL