Plan Review Details - Permit 18080200
Plan Review Stops For Permit 18080200
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-09-04 Cont ID  
Sent By cthroop Date 2018-09-04 Time 07:19 Rev Time 0.00
Received By cthroop Date 2018-09-04 Time 07:14 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-16 Cont ID  
Sent By cthroop Date 2018-08-16 Time 15:34 Rev Time 0.00
Received By cthroop Date 2018-08-16 Time 15:32 Sent To E
Notes
2018-08-16 15:38:20BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE SITE PLAN. SHOW LOCATION OF PROPOSED SIGN.
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED ON A BOUNDARY LINE SURVEY.
  
 2. PROVIDE DESIGN WIND LOADS FOR PROPOSED SIGN.
 FBC 107.3.5.1.1(8) ? PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-CHAPTER 16
  
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 NOTE: PROVIDE WELDER CERTIFICATIONS AT TIME OF
 INSPECTION FOR ANY ON SITE WELDING.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-29 Cont ID  
Sent By fgiaquin Date 2018-08-29 Time 07:15 Rev Time 0.00
Received By fgiaquin Date 2018-08-29 Time 07:13 Sent To B
Notes
2018-08-29 07:15:29NEW DISCONNECT REQURIED (RED-LINED ON PLAN) BY 600.6A1
 NEC 2014 AND ASTRONOMICAL TIMECLOCK REQUIRED BY FBC CE
 405.2.4 TO BE INSTALLED AND PERMITTED BY LICENSED
 ELECTRICIAN. FAILURE TO SECURE PROPER PERMIT AND THEN
 THE INSTALLATION OF THESE ITEMS BY SIGN CONTRACTOR WILL
 RESULT IN A 4X PERMIT FEE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-22 Cont ID  
Sent By fgiaquin Date 2018-08-22 Time 16:53 Rev Time 0.00
Received By fgiaquin Date 2018-08-22 Time 16:28 Sent To I
Notes
2018-08-22 16:53:32ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SHOWING
 DISCONNECT REQUIRED BY 600.6A1 AND ALL OTHER ELECTRICAL
 ASSOCIATED WITH INSTALLATION OF THE SIGN, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
  
 2. SEAL BY ENGINEER UNREADABLE AND IS NOT VALID. PHOTO
 COPIES OF SEALS ARE NOT ACCEPTABLE. PLEASE SEE
 REQUIREMENTS FOR SEALS BELOW:
  
 PHYSICALLY TRANSMITTED DOCUMENTS REQUIRE THAT THE
 LICENSEE CREATE BY HAND AN ORIGINAL OF THE LICENSEE?S
 SIGNATURE. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE IS NOT ALLOWED
 ON PHYSICALLY TRANSMITTED DOCUMENTS.
 CHAPTER 61G15-23.003(1), F.A.C., THE LICENSEE SHALL
 SIGN BY HAND AN ORIGINAL OF THE LICENSEE?S SIGNATURE ON
 EACH PAGE REQUIRED TO BE SEALED. A SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED.
  
 AS FOR CREATING THE SEAL, PHYSICALLY TRANSMITTED
 DOCUMENTS ARE ALLOWED TO BE EMBOSSED, SEALED USING A
 WET STAMP, OR CONTAIN A DIGITALLY CREATED SEAL (AS PART
 OF THE BORDER). IN EACH OF THESE CASES THE SEAL IS TO
 PARTIALLY OVERLAP THE LICENSEE?S SIGNATURE SUCH THAT
 THE SIGNATURE IS NOT MADE ILLEGIBLE.
 CHAPTER 61G15-23.003(2), F.A.C., THE LICENSEE MUST THEN
 USE A WET SEAL, A DIGITALLY CREATED SEAL, OR AN
 EMBOSSING SEAL PLACED PARTIALLY OVERLAPPING THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. THE PLACEMENT OF THE SEAL SHALL NOT RENDER THE
 SIGNATURE ILLEGIBLE.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-04 Cont ID  
Sent By cthroop Date 2018-09-04 Time 07:20 Rev Time 0.00
Received By cthroop Date 2018-08-23 Time 13:58 Sent To  
Notes
2018-08-24 13:59:06RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-22 Cont ID  
Sent By fgiaquin Date 2018-08-22 Time 16:53 Rev Time 0.00
Received By fgiaquin Date 2018-08-03 Time 14:42 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2018-08-28 Cont ID  
Sent By mcruz Date 2018-08-28 Time 16:12 Rev Time 0.00
Received By mcruz Date 2018-08-28 Time 16:12 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-08-08 Cont ID  
Sent By fgiaquin Date 2018-08-22 Time 16:53 Rev Time 0.00
Received By mcruz Date 2018-08-08 Time 16:28 Sent To B
Notes
2018-08-08 16:49:24ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) PROVIDE A SITE PLAN DEPICTING LOCATION OF PROPOSED
 HIGH FREE STANDING SIGN. ENSURE THE SIGN MEETS THE
 FOLLOWING SIZE/LOCATION REQUIREMENTS: SEC. 94-408(D)(3)
 HIGH FREESTANDING SIGNS. THE REQUIREMENTS FOR HIGH
 FREESTANDING SIGNS SHALL BE AS FOLLOWS:
 A. CONTENT: THE NAME, LOGO AND ADDRESS OF THE BUILDING
 AND BUILDING OCCUPANTS TO WHICH THE SIGN IS ACCESSORY
 AND OTHER RELATED INFORMATION. IN ADDITION, SIGNS
 PERMITTED PURSUANT TO THIS SECTION MAY CONTAIN ANY
 NONCOMMERCIAL MESSAGE THAT HAS NOT BEEN DECLARED BY A
 COURT OF COMPETENT JURISDICTION TO BE OBSCENE,
 DEFAMATORY OR OTHERWISE CONTRARY TO LAW.
 B. MAXIMUM SUM TOTAL AREA OF ALL HIGH FREESTANDING
 SIGNS ALONG FRONT STREET RIGHT-OF-WAY LINES WHICH ARE
 NOT OPPOSITE RESIDENTIAL USES: OE SQUARE FOOT FOR EACH
 ONE LINEAR FOOT OF FRONTAGE.
 C. MAXIMUM SUM TOTAL AREA OF ALL HIGH FREESTANDING
 SIGNS ALONG FRONT RIGHT-OF-WAY LINES WHICH ARE NOT
 FRONT STREET RIGHT-OF-WAY LINES AND WHICH ARE OPPOSITE
 RESIDENTIAL USES: 0.50 SQUARE FEET FOR EACH ONE LINEAR
 FOOT OF FRONTAGE.
 D. MAXIMUM SUM TOTAL AREA OF ALL HIGH FREESTANDING
 SIGNS ALONG FRONT STREET OF OTHER PUBLIC RIGHT-OF-WAY
 LINES WHICH ARE OPPOSITE RESIDENTIAL USES: 0.25 SQUARE
 FEET FOR EACH ONE LINEAR FOOT OF FRONTAGE.
 E. MAXIMUM NUMBER OF ALL HIGH FREESTANDING SIGNS ON
 EACH STREET FRONTAGE: NO SIGNS FOR THE FIRST 75 LINEAR
 FEET OF STREET FRONTAGE; ONE SIGN FOR EACH ADDITIONAL
 75 FEET OR FRACTION THEREOF OF STREET FRONTAGE.
 FRONTAGE ON EACH STREET SHALL BE CONSIDERED SEPARATELY
 IN DETERMINING IF THIS REQUIREMENT IS MET.
 F. MINIMUM SETBACKS:
 1. FROM LOT LINE OF ANOTHER LOT: 24 FEET.
 2. FROM PUBLIC RIGHT-OF-WAY LINE: FIVE FEET, EXCEPT
 THAT IN THE TRIANGULAR AREA MADE BY THE INTERSECTION OF
 TWO PUBLIC RIGHT-OF-WAY LINES AND A LINE CONNECTING
 POINTS ON EACH LINE 20 FEET FROM THE POINT OF
 INTERSECTION, ONE FREESTANDING SIGN MAY BE ERECTED
 PROVIDED THE LOT ON WHICH IT IS ERECTED QUALIFIES FOR A
 HIGH FREESTANDING SIGN UNDER THE AREA AND NUMBER
 PROVISIONS OF THIS SUBSECTION (D)(3)F.2. SIGNS SO
 LOCATED SHALL CONFORM TO THE PROVISIONS OF SUBSECTION
 94-305(E).
 3. FROM OTHER HIGH FREESTANDING SIGNS ON SAME LOT: 75
 FEET MEASURED FROM THE GRADE LEVEL OF THE LAND WHERE
 THE SIGN IS POSITIONED.
 4. FROM UTILITY POLES WHICH SUPPORT ELECTRICAL
 TRANSMISSION LINES: EIGHT FEET.
  
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]