Plan Review Details - Permit 18080195
Plan Review Stops For Permit 18080195
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-09-12 Cont ID  
Sent By skennedy Date 2018-09-12 Time 09:01 Rev Time 0.00
Received By skennedy Date 2018-09-12 Time 09:01 Sent To  
Notes
2018-09-12 10:15:39APPROVED PROVISIONALLY. DO YOU KNOW WHICH WINDOW YOU
 ARE USING FROM THE FLORIDA PRODUCT APPROVAL NUMBER
 243-R20 ? I PRESUMED IT IS 243.5. YOU DID NOT PROVIDE
 THE CERTIFICATE AGENCY CERTIFICATE OR INSTALLATION
 INSTRUCTION. I PRINTED IT FOR YOU WHICH TURNED OUT TO
 BE MIAMI DADE NOA 17-0614.11. I ATTACHED ONLY THE NOA
 TO THE PLAN AS THE FLORIDA PRODUCT APPROVAL SHEET JUST
 CONFUSES THE ISSUE. YOUR ENGINEER OF RECORD, ANDRE H.
 THOMAS IS SUPPOSED TO PROVIDE EVIDENCE THAT HE REVIEWED
 THE USE OF THIS PRODUCT FOR CONSISTENCY WITH THE DESIGN
 OTHER ISSUES THAT WERE NOT ADDRESSED IN THE RESPONSE
 SHOULD ALSO BE PROVIDED BY THE ENGINEER AS HE IS
 RESPONSIBLE FOR THE DESIGN. THOSE ITEMS ARE AS FOLLOWS:
  
 1. [FBC EB501]PROVIDE DESIGN DATA: OCCUPANCY=R-3, LEVEL
 OF ALTERATION AND TYPE OF CONSTRUCTION.
  
 2. [FBC 107.2.5]PROVIDE FURTHER DETAIL SHEET A-1 BLOCK
 IN-FILL. WHAT IS THE EXTERIOR FINISH, INSULATION AND
 INTERIOR FINISH.
  
 3. [FBC ENERGY R503.1.1.1]WHERE SOME OR ALL OF AN
 EXISTING FENESTRATION UNIT IS REPLACED WITH A NEW
 FENESTRATION PRODUCT, INCLUDING SASH AND GLAZING, THE
 REPLACEMENT FENESTRATION UNIT SHALL MEET THE APPLICABLE
 REQUIREMENTS FOR U-FACTOR AND SHGC AS PROVIDED IN TABLE
 R402.1.2.
 NEW FENESTRATION SHOULD HAVE MAXIMUM SOLAR HEAT GAIN
 CO-EFFICIENT (SHGC) OF 0.25 IN CLIMATE ZONE 1.
  
 THE ENGINEER MAY PROVIDE A LETTER ADDRESSING THESE
 ISSUES FOR MY REVIEW OR IT MAY BE GIVEN TO THE BUILDING
 INSPECTOR AT THE FRAMING INSPECTION.
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-28 Cont ID  
Sent By dbattles Date 2018-08-28 Time 08:14 Rev Time 0.00
Received By dbattles Date 2018-08-28 Time 08:14 Sent To  
Notes
2018-08-28 08:16:48****CORRECTIONS****
 W.P.B. PERMIT: 18080195
 REVIEWED: AUGUST 28, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC EB = FBC EXISTING BUILDING
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC EB501]PROVIDE DESIGN DATA: OCCUPANCY=R-3, LEVEL
 OF ALTERATION AND TYPE OF CONSTRUCTION.
  
 2. [FBC 107.2.5]CHANGE FIRST LINE OF GENERAL NOTES TO
 SAY 2017 BUILDING CODE.
  
 3. [FBC 107.2.5]PROVIDE FURTHER DETAIL SHEET A-1 BLOCK
 IN-FILL. WHAT IS THE EXTERIOR FINISH, INSULATION AND
 INTERIOR FINISH.
  
 4. [FBC ENERGY R503.1.1.1]WHERE SOME OR ALL OF AN
 EXISTING FENESTRATION UNIT IS REPLACED WITH A NEW
 FENESTRATION PRODUCT, INCLUDING SASH AND GLAZING, THE
 REPLACEMENT FENESTRATION UNIT SHALL MEET THE APPLICABLE
 REQUIREMENTS FOR U-FACTOR AND SHGC AS PROVIDED IN TABLE
 R402.1.2.
 NEW FENESTRATION SHOULD HAVE MAXIMUM SOLAR HEAT GAIN
 CO-EFFICIENT (SHGC) OF 0.25 IN CLIMATE ZONE 1.
  
 5. [FBC 107.2.5]SHEET A-2. ADJUST THE DASHED LINE OF
 UPPER CABINET TO ACCOUNT FOR WINDOWS AND ADD INTERIOR
 ELEVATION FOR CLARITY.
  
 6. [FBC 107.2.5]REVIEW OVEN AND REFRIDGERATOR
 DOCUMENTATION TO MAKE SURE THEY ARE COMPATIBLE SIDE BY
 SIDE.
  
 7. [FBC AMENDED 107.2.1.2]ON PRODUCT APPROVAL FOR FIXED
 WINDOW FL243-R20, PLEASE SELECT THE PRODUCT IN MIND,
 AND PRINT OUT THE CERTIFICATE AND INSTRUCTIONS FOR
 ATTACHMENT DETAILS.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-09-02 Cont ID  
Sent By jpearson Date 2018-09-02 Time 10:08 Rev Time 0.00
Received By jpearson Date 2018-09-02 Time 10:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-20 Cont ID  
Sent By jpearson Date 2018-08-20 Time 09:47 Rev Time 0.00
Received By jpearson Date 2018-08-20 Time 09:47 Sent To  
Notes
2018-08-20 09:47:02CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL NOTE STATES THAT RECEPTACLES SHALL BE
 TAMPER RESISTANT PER NEC 406.11. THIS CODE SECTION DOES
 NOT APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE E4002.14
 2. NOTE ON PARTIAL VIEW ELECTRICAL PLAN STATES THAT
 "ALL OUTLETS NOT NOTES AS FGCI PROTECTED SHALL BE AFCI
 PROTECTED (SIC)". AFCI PROTECTION SHOWN IN NOT CODE
 COMPLIANT. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902
 3. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 4. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. A MINIMUM OF TWO SMALL APPLIANCE
 BRANCH CIRCUITS MUST BE INCLUDED. I DO NOT SEE THE OVEN
 INCLUDED. MUST SHOW ALL LOADS. NEC 215.2, 220, 408.30;
 FBC RE E3602.2
 5. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
 6. NOTE ON PARTIAL VIEW ELECTRICAL PLAN STATES THAT
 "ALL SMOKE DETECTORS TO BE ADDED OR REPLACED LOCATED AT
 EACH BEDROOM". THIS STATEMENT IS NOT CODE COMPLIANT.
 PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER
 CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-12 Cont ID  
Sent By skennedy Date 2018-09-12 Time 09:01 Rev Time 0.00
Received By skennedy Date 2018-08-30 Time 12:54 Sent To  
Notes
2018-08-31 12:54:58R01

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-28 Cont ID  
Sent By rmcdouga Date 2018-08-28 Time 10:07 Rev Time 0.00
Received By rmcdouga Date 2018-08-03 Time 14:18 Sent To  
Notes
2018-08-07 09:26:56R05
2018-08-06 14:18:28LIBRARY

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2018-08-09 Cont ID  
Sent By cmontell Date 2018-08-09 Time 13:55 Rev Time 0.00
Received By cmontell Date 2018-08-09 Time 13:54 Sent To  
Notes
2018-08-09 13:57:01NO MECHANICAL WORK ON PLAN
  
 CHRIS MONTELLO
 561-805-6733

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-09-12 Cont ID  
Sent By skennedy Date 2018-09-12 Time 09:01 Rev Time 0.00
Received By skennedy Date 2018-09-12 Time 09:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-08-28 Cont ID  
Sent By rmcdouga Date 2018-08-28 Time 10:07 Rev Time 0.00
Received By rmcdouga Date 2018-08-28 Time 10:07 Sent To I
Notes
***NONE***