Plan Review Details - Permit 18080194
Plan Review Stops For Permit 18080194
Review Stop AD ADDRESSING
Rev No 3 Status N Date 2018-10-30 Cont ID  
Sent By skennedy Date 2018-10-30 Time 12:48 Rev Time 0.00
Received By skennedy Date 2018-10-30 Time 12:48 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2018-10-29 Cont ID  
Sent By rmcdouga Date 2018-10-29 Time 16:28 Rev Time 0.00
Received By rmcdouga Date 2018-10-26 Time 19:00 Sent To  
Notes
2018-10-29 16:28:04THE PERMIT CAN NOT BE ISSUED UNTIL AN ADDRESS HAS BEEN
 ASSIGNED TO THE PROPERTY. IN ORDER TO OBTAIN AN
 ADDRESS, PLEASE CONTACT MICHEAL ORIO BY PHONE AT
 561-494-1080 OR BY EMAIL AT [email protected]. THE TITLE
 BLOCK ON THE PLANS HAS AN ADDRESS OF 210 COSTELLO ROAD
 AND THE CITY RECORDS HAS 7105 WASHINGTON ROAD FOR THIS
 PROPERTY.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2018-09-05 Cont ID  
Sent By rmcdouga Date 2018-09-05 Time 11:33 Rev Time 0.00
Received By rmcdouga Date 2018-09-05 Time 11:33 Sent To  
Notes
2018-09-05 11:33:31THE PERMIT CAN NOT BE ISSUED UNTIL AN ADDRESS HAS BEEN
 ASSIGNED TO THE PROPERTY. IN ORDER TO OBTAIN AN
 ADDRESS, PLEASE CONTACT MICHEAL ORIO BY PHONE AT
 561-494-1080 OR BY EMAIL AT [email protected].

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-10-30 Cont ID  
Sent By rmcdouga Date 2018-10-30 Time 10:03 Rev Time 0.00
Received By rmcdouga Date 2018-10-26 Time 17:47 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-09-11 Cont ID  
Sent By rmcdouga Date 2018-09-11 Time 17:31 Rev Time 0.00
Received By rmcdouga Date 2018-09-05 Time 13:34 Sent To I
Notes
2018-09-11 15:35:39PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS HAVE SEVERAL REFERENCES TO THE FBC FIFTH
 EDITION (2014). THE FBC SIXTH EDITION (2017) WENT INTO
 EFFECT ON JANUARY 1, 2018. ALL NEW PERMITS APPLIED FOR
 ON OR AFTER THAT DATE ARE REQUIRED TO COMPLY WITH AND
 REFERENCE THE FBC SIXTH EDITION (2017). FS CHAPTER 553
  
 2) THE REFERENCED STANDARDS ON SHEET A-101 ARE OLD AND
 NOT THE ONES THAT ARE LISTED IN CHAPTER 46 OF THE 2017
 FBC RESIDENTIAL.
  
 3) ON A-201 THE GARAGE SEPARTION CODE SECTIONS THAT ARE
 SPECIFIED ARE INCORRECT. FBC-R 302.5 IS THE APPLICABLE
 CODE IN THE 2017 EDITION. FBC 107.2.1
  
 4) ON SHEETS A-201 AND A-202, TYPICAL RAILING NOTE #3,
 R312.1.3 NO LONGER HAS THE PART ABOUT THE 64 SQUARE
 INCHES. FBC 107.2.1
  
 5) ON SHEETS A-201 AND A-202, TYPICAL STAIR NOTES NEED
 TO BE UPDATED TO THE 2017 FBC. NOTE #3 ABOUT THE SUM OF
 TWO RISERS AND ONE TREAD IS NO LONGER IN THE CODE.
 FBC-R 311.7.5
  
 6) ON SHEETS A-201 AND A-202, UPDATE THE EGRESS NOTE TO
 CODE SECTIONS 311.2, 311.3.1 AND 310.2.2. NOTE 2 SHOULD
 READ THAT SILL HEIGHT OF NOT MORE THAN 44".
  
 7) UP DATE THE STAIR NOTES ON A-201 AND A-202 TO 2017
 FBC-R TABLE R301.5 FOR MINIMUM UNIFORMLY DISTRUBITED
 LIVE LOADS.
  
 8) THE ELEVATIONS ON THE THE DRAINAGE PLAN SHEET C-1
 ARE IN NGVD-29. ON OCTOBER 5TH, 2017, THE CITY OF WEST
 PALM BEACH ADOPTED NEW FLOOD INSURANCE RATE MAPS WHICH
 USE NAVD 88 AS THE VERTICAL DATUM.
  
 9) SUBMIT THE MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE OUTDOOR GAS COOKTOP
 AND EXHAUST HOOD. FBC 107.2.1
  
 10) ON SHEETS S-2 AND S-3 THE ROOF FRAMING NOTES
 SPECIFY EXPOSURE D AND THE BEAM UPLIFT CALCULATIONS
 SPECIFY EXPOSURE C. PLEASE COORDINATE THE EXPOSURE
 CATEGORY. FBC-R301.2.1.4.3
  
 11) THE WIND DESIGN PRESSURES FOR THE WINDOWS AND DOORS
 ON SHEET A-301 ARE DIFFERENT FROM THE ONES ON SHEETS
 S-2 AND S-3. PLEASE REVIEW AND REVISE AS NEEDED.
 FBC-R301.2.1 AND ASCE 7-10.
  
 12) ON SHEET A-301 THE NOA NO. FOR THE SECTIONAL GARAGE
 DOOR DOES NOT MATCH THE ONE THAT WASA SUBMITTED.
  
 13) SECTION 2 ON SHEET A-401 HAS A NOTE STATING
 CONCRETE TILE OVER 30# FELT. THE 30# FELT ALONE IS NOT
 AN ACCEPTABLE UNDERLAYMENT FOR CONCRETE TILE. SPECIFY
 AN APPROVED CONCRETE ROOF TILE UNDERLAYMENT AND
 ASSEMBLY. FBC-R905.3
  
 14) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED
 TO INSTALL THE CEMENT ROOF TILE. IF AN ADHESIVE OR
 MORTAR WILL BE USED, THEN SUBMIT TWO SETS OF PRODUCT
 APPROVALS FOR IT. FBC 107.2.1 & FAC 61G20-3.001 PER
 FLORIDA STATUTE 553.842 (5)
  
 15) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE TARCO
 ROOF MEMBRANE SHOWN IN SECTION 2 ON SHEET A-401. FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5)
  
 16) SUBMIT TWO SETS OF THE PRODUCT APPROVALS,
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE SEALOFLEX WATERPROOFING SYATEM.
 FBC 107.2.1, FAC 61G20-3.001 PER FLORIDA STATUTE
 553.842 (5) AND FBC-R905.15
  
 17) PRODUCT APPROVALS FOR SINGLE HUNG WINDOWS, NOA NO.
 16-1003.01, WERE SUBMITTED AND THERE ARE NONE SHOWN OR
 SPECIFIED ON THE PLANS. PLEASE REMOVE THEM AS THEY DO
 NOT APPLY TO THIS PROJECT. FBC 107.2.1
  
 18) REVISE THE WINDOW SCHEDULE ON SHEET A-302 TO
 PROVIDE A MORE ACQURATE MATCH WITH THE PLANS. FBC
 107.2.1
  
 19) REVIEW THE PRODUCT APPROVAL NUMBERS ON THE DOOR
 SCHEDULE AND REVISE THEM TO MATCH THE ONES THAT ARE
 BEING SUBMITTED. FBC 107.2.1
  
 20) NOA NO. 14-0908.18 FOR THE FIXED WINDOWS IS
 EXPIRED. THE INSTALLATION DRAWINGS ARE TOO SMALL TO BE
 LEGIBLE. PRINT THESE IN LANDSCAPE ORIENTATION SO THEY
 BETTER FIT THE PRINTER PAPER SIZE.
  
 21) NOA NOS. 14-0908.02 FOR THE SLIDING GLASS DOORS AND
 14-0908.07 FOR THE FRENCH DOORS EXPIRED PRIOR TO THE
 DATE OF YOUR PERMIT APPLICATION. SUBMIT CURRENT PRODUCT
 APPROVALS. FAC 61G20-3.001 PER FLORIDA STATUTE 553.842
 (5)
  
 22) SPECIFY THE DOOR THAT FL 15187.3 IS INTENDED FOR.
 FBC 107.2.1
  
 23) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE 3'-6"
 X 8'-0" ENTRY DOOR. FAC 61G20-3.001 PER FLORIDA STATUTE
 553.842 (5)
  
 24) THE ENERGY CALCULATIONS SPECIFY A METAL ROOF AND
 THIS BUILDING HAS A CONCRETE TILE ROOF. PLEASE CORRECT.
 FBC-R101.5.1.1.2
  
 25) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-10-12 Cont ID  
Sent By jpearson Date 2018-10-12 Time 13:23 Rev Time 0.00
Received By jpearson Date 2018-10-12 Time 13:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-27 Cont ID  
Sent By jpearson Date 2018-08-27 Time 11:27 Rev Time 0.00
Received By jpearson Date 2018-08-27 Time 07:08 Sent To  
Notes
2018-08-27 11:27:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3603.3
 2. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 3. RISER DIAGRAM SHOWS A DIFFERENT CONFIGURATION THAN
 THE ELECTRICAL PLAN. WILL THERE BE MAIN BREAKER PANELS
 ON THE OUTSIDE OF THE GARAGE THAT FEED INTERIOR MAIN
 LUG PANELS? OR WILL THERE BE MAIN BREAKER PANELS IN THE
 GARAGE? THE PANEL SCHEDULES FOR BOTH PANELS SHOWS THEM
 AS MAIN LUG ONLY. CORRECT DISCREPANCY. IF THERE ARE
 MAIN LUG PANELS IN THE GARAGE, THESE WILL REQUIRE AN
 EQUIPMENT GROUNDING CONDUCTOR(EGC). IF THE METER FEEDS
 DIRECTLY TO A MAIN BREAKER PANEL, THIS SHOULD NOT HAVE
 AND EGC. PROVIDE CORRECTIONS. WPB FBC 107.2.1; NEC
 250.6, 250.122; FBC RE E3610.4, E3704.6, E3607.3.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-10-25 Cont ID  
Sent By jesmith Date 2018-10-25 Time 08:43 Rev Time 0.00
Received By jesmith Date 2018-10-25 Time 08:46 Sent To  
Notes
2018-10-25 08:43:10A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
 A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
 IF THERE IS AN EXISTING SYSTEM, THE BTU LOAD OF THE
 EXISTING GAS SYSTEM MUST BE ADDED INTO THE TOTAL BTU
 LOAD ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS
 PROPERLY SIZED. IF UNDERSIZED, THE EXISTING SYSTEM MUST
 BE REDONE TO ENSURE A SAFE OPERATING SYSTEM. SUBMIT A
 GAS PIPING RISER DIAGRAM THAT SHOWS THE TYPE OF
 EXISTING APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE
 PIPE SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES. FBCR SECS.G2412.4, G2412.8,
 G2413.1, G2413.2, G2413.3.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561-805-6715

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-30 Cont ID  
Sent By rmcdouga Date 2018-10-30 Time 10:03 Rev Time 0.00
Received By rmcdouga Date 2018-10-05 Time 14:58 Sent To  
Notes
2018-10-09 14:58:25LIBRARY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-11 Cont ID  
Sent By rmcdouga Date 2018-09-11 Time 17:31 Rev Time 0.00
Received By rmcdouga Date 2018-08-03 Time 10:12 Sent To  
Notes
2018-08-07 10:12:59R29

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-10-29 Cont ID  
Sent By rmcdouga Date 2018-10-29 Time 16:32 Rev Time 0.00
Received By rmcdouga Date 2018-10-26 Time 18:06 Sent To  
Notes
2018-10-29 16:40:09MU 2018-34435, PAID $9,904.34

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-09-05 Cont ID  
Sent By rmcdouga Date 2018-09-05 Time 11:31 Rev Time 0.00
Received By rmcdouga Date 2018-09-05 Time 11:30 Sent To  
Notes
2018-09-05 11:32:00PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-10-19 Cont ID  
Sent By cmontell Date 2018-10-19 Time 15:03 Rev Time 0.00
Received By cmontell Date 2018-10-19 Time 14:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-09-04 Cont ID  
Sent By cmontell Date 2018-09-04 Time 13:51 Rev Time 0.00
Received By cmontell Date 2018-09-04 Time 13:50 Sent To  
Notes
2018-09-04 13:50:41MECHANICAL PLAN FAIL
  
 1 - NEED EQUIPMENT SIZING PER 2017 FLORIDA BUILDING
 CODE - ENERGY CONSERVATION SEC. R403.7.1
  
  
 CHRIS MONTELLO
 561-805-6733
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-10-30 Cont ID  
Sent By jesmith Date 2018-10-25 Time 09:47 Rev Time 0.00
Received By jesmith Date 2018-10-30 Time 12:57 Sent To  
Notes
2018-10-30 13:17:042ND REVIEW REV 1:
 PLUMBING COMMENTS: APPROVED WITH EXCEPTION
  
 1. A REVISION IS REQUIRED REFLECTING THE CHANGES LISTED
 BELOW. FAILURE TO CORRECT THE LISTED DEFICIENCIES IN
 THIS PLAN PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
 2. REGARDING SANITARY PLUMBING RISER ON PLAN SHEET S-1:
 PLEASE SEE REDLINED NOTES AND MARKUPS IN CLOUDED AREAS
 FOR THE ITEMS LISTED BELOW; REVISE PLAN AND SUBMIT AS A
 REVISION.
 A. MASTER BATH:FIXTURE DRAINS FOR SHOWER AND BATHTUB
 MUST CONNECT INDEPENDENTLY TO THE WET VENT. FBC RES
 P3108.1
 B. GUEST BATH: FIXTURE DRAINS FOR TWO SHOWERS MUST
 CONNECT INDEPENDENTLY TO THE WET VENT. FBC RES P3108.1
 C. BATH #2: FIXTURE DRAINS FOR SHOWER AND WATER CLOSET
 MUST CONNECT INDEPENDENTLY TO THE WET VENT. FBC RES
 P3108.1
 D. BATH #3: FIXTURE DRAINS FOR SHOWER AND WATER CLOSET
 MUST CONNECT INDEPENDENTLY TO THE WET VENT. FBC RES
 P3108.1
 E. KITCHEN SINK: DISHWASHERS TO CONNECT TO SINK
 TAILPIECE ABOVE THE TRAP INLET. REVISE OR DO NOT SHOW
 THE DISHWASHER CONNECTIONS ON THE DRAWING.
 D. GENERAL NOTE: ALL FIXTURE DRAINS MUST CONNECT TO
 VENT IN ACCORDANCE WITH TABLE P3105.1; MAXIMUM DISTANCE
 OF TRAP TO VENT.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL: [email protected]
 PHONE: 561-805-6715
  
2018-10-25 09:47:33CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 2ND REVIEW:
 PLUMBING COMMENTS: DENIED
  
 1. REGARDING SANITARY PLUMBING RISER ON PLAN SHEET S-1:
 PLEASE SEE REDLINED NOTES AND MARKUPS IN CLOUDED AREAS
 FOR THE ITEMS LISTED BELOW; REVISE PLAN AND RESUBMIT.
 2017 FBC RES 3108.1
 A. MASTER BATH:FIXTURE DRAINS FOR SHOWER AND BATHTUB
 MUST CONNECT INDEPENDENTLY TO THE WET VENT. FBC RES
 P3108.1
 B. GUEST BATH: FIXTURE DRAINS FOR TWO SHOWERS MUST
 CONNECT INDEPENDENTLY TO THE WET VENT. FBC RES P3108.1
 C. BATH #2: FIXTURE DRAINS FOR SHOWER AND WATER CLOSET
 MUST CONNECT INDEPENDENTLY TO THE WET VENT. FBC RES
 P3108.1
 D. BATH #3: FIXTURE DRAINS FOR SHOWER AND WATER CLOSET
 MUST CONNECT INDEPENDENTLY TO THE WET VENT. FBC RES
 P3108.1
 E. KITCHEN SINK: DISHWASHERS TO CONNECT TO SINK
 TAILPIECE ABOVE THE TRAP INLET. REVISE OR DO NOT SHOW
 THE DISHWASHER CONNECTIONS ON THE DRAWING.
 D. GENERAL NOTE: ALL FIXTURE DRAINS MUST CONNECT TO
 VENT IN ACCORDANCE WITH TABLE P3105.1; MAXIMUM DISTANCE
 OF TRAP TO VENT.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN
 ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL: [email protected]
 PHONE: 561-805-6715
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-09-06 Cont ID  
Sent By shill Date 2018-09-06 Time 10:49 Rev Time 0.00
Received By jesmith Date 2018-09-06 Time 10:42 Sent To  
Notes
2018-09-07 12:39:50REVIEW COMPLETED BY JERALD SMITH 0017-P
2018-09-06 10:47:241ST REVIEW: FBC 2017 6TH EDITION
 PERMIT 18080194
 PLUMBING COMMENTS: DENIED
  
 1. REGARDING SANITARY PLUMBING RISER ON PLAN SHEET S-1:
 A. DESIGNATION C.O. IF CLEANOUTS SHOWN AT END OF
 BATHROOM SANITARY RUNOUTS ON THE GROUND FLOOR ARE TO BE
 REQUIRED THEY MUST BE ACCESSIBLE. 2017 FBC RES
 3005.2.10. PLEASE CLARIFY.
  
 B. AUTOMATIC CLOTHES WASHERS REQUIRE A FIXTURE TRAP PER
 2017 FBC RES 3201.6 AND A VENT PER 2017 FBC RES 3105.1.
 CORRECT ON THE SANITARY RISER DIAGRAM ON PLAN SHEET S-1
 TO SHOW THE SAME.
  
 C. FIXTURE DRAINS FOR SHOWER AND BATHTUB IN MASTER BATH
 #2 MUST CONNECT INDEPENDENTLY TO THE WET VENT. CORRECT
 ON THE SANITARY RISER DIAGRAM ON PLAN SHEET S-1 TO SHOW
 THE SAME. 2017 FBC RES 3108.1
  
 D. WHAT IS THE TERM "STUTTER VENT" NOTED AT DIFFERENT
 FIXTURES ON RISER DIAGRAM? PLEASE CLARIFY.
  
 E. PLEASE CLARIFY 3" VTR RISING ABOVE 2" WET VENTS.
  
 2. THERE IS A GAS FIRED TANKLESS WATER HEATER AND A BBQ
 GRILL NOTED ON PLAN SHEET A-201. A GAS PLAN HAS NOT
 BEEN INCLUDED IN THIS SUBMITTAL PACKAGE. A GAS PLAN
 REVIEW HAS NOT BEEN PERFORMED AT THIS TIME. A SEPARATE
 GAS PERMIT AND PLANS WILL BE REQUIRED FOR A CONTRACTOR
 TO PERFORM THE RELATED WORK PER WPB AMEND. TO FBC SEC.
 105.1. PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
  
 3. NOTE: SEE FOLLOWING COMMENTS
 A. HAND HELD SHOWER REQUIRES AN ATMOSPHERIC VACUUM
 BREAKER AT SHOWER ARM OUTLET. 2017 FBC RES 2708.5
  
 B. SHOWER CONTROL VALVE(S) SHALL BE PRESSURE BALANCED
 PB,THERMOSTATIC MIXING (TM) OR COMBINATION PB/TM VALVE
 TYPES WITH HIGH TEMPERATURE LIMITING STOP. 2017 FBC RES
 2708.4
  
 C. ACCESSIBLE TEMPERATURE LIMITING DEVICE REQUIRED ON
 HOT WATER TO MASTER BATH BATHTUB(S) IS REQUIRED. 2017
 FBC RES 2713.3
  
 D. THE VALVES FOR THE STACKABLE WASHING MACHINE(S)
 SHALL BE ACCESSIBLE. 2017 FBC RES P2903.9.3
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711

Review Stop Z ZONING
Rev No 2 Status P Date 2018-10-26 Cont ID  
Sent By awooten Date 2018-10-26 Time   Rev Time 0.00
Received By awooten Date 2018-10-26 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-08-16 Cont ID  
Sent By awooten Date 2018-08-16 Time 14:11 Rev Time 0.00
Received By awooten Date 2018-08-15 Time 16:36 Sent To  
Notes
2018-08-16 14:09:56*******************************ZONING REVIEW
 FAILED***************************************
  
 THE LANDSCAPE PLAN SUBMITTED WITH THIS PERMIT NEEDS TO
 BE SUBMITTED ON ITS OWN AS A LANDSCAPE PERMIT.
  
 THE DRIVEWAY, FENCE AND POOL REQUIRE A SEPARATE PERMIT.
  
 PROVIDE THE SETBACKS FOR ALL THE MECHANICAL EQUIPMENT
 (IT CANNOT GO MORE THAN 4 FEET INTO THE SETBACK).
  
 ALL OVERHANGS, EVEN THE ONES FOR THE GARAGE, CANNOT
 EXTEND FURTHER THAN 3 FEET INTO SETBACK.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]