Plan Review Details - Permit 18080193
Plan Review Stops For Permit 18080193
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2018-10-30 Cont ID  
Sent By skennedy Date 2018-10-30 Time 12:48 Rev Time 0.00
Received By skennedy Date 2018-10-30 Time 12:48 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2018-10-29 Cont ID  
Sent By rmcdouga Date 2018-10-29 Time 15:08 Rev Time 0.00
Received By rmcdouga Date 2018-10-29 Time 15:08 Sent To  
Notes
2018-10-29 15:12:42THE PERMIT CAN NOT BE ISSUED UNTIL AN ADDRESS HAS BEEN
 ASSIGNED TO THE PROPERTY. IN ORDER TO OBTAIN AN
 ADDRESS, PLEASE CONTACT MICHEAL ORIO BY PHONE AT
 561-494-1080 OR BY EMAIL AT [email protected]. THE TITLE
 BLOCK ON THE PLANS HAS AN ADDRESS OF 210 COSTELLO ROAD
 AND THE CITY RECORDS HAS 7105 WASHINGTON ROAD FOR THIS
 PROPERTY.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2018-09-12 Cont ID  
Sent By rmcdouga Date 2018-09-12 Time 18:27 Rev Time 0.00
Received By rmcdouga Date 2018-09-12 Time 18:26 Sent To  
Notes
2018-09-12 18:27:11THE PERMIT CAN NOT BE ISSUED UNTIL AN ADDRESS HAS BEEN
 ASSIGNED TO THE PROPERTY. IN ORDER TO OBTAIN AN
 ADDRESS, PLEASE CONTACT MICHEAL ORIO BY PHONE AT
 561-494-1080 OR BY EMAIL AT [email protected].

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-10-29 Cont ID  
Sent By rmcdouga Date 2018-10-29 Time 15:08 Rev Time 0.00
Received By rmcdouga Date 2018-10-29 Time 08:23 Sent To  
Notes
2018-10-29 14:45:38BUILDING PROVISO
  
 1) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE
 SEALOFLEX WATERPROOFING. FAC RULE 61G20 & FBC 107.3.4

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-09-12 Cont ID  
Sent By rmcdouga Date 2018-09-12 Time 18:59 Rev Time 0.00
Received By rmcdouga Date 2018-09-11 Time 18:56 Sent To I
Notes
2018-09-12 18:59:19PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS HAVE SEVERAL REFERENCES TO THE FBC FIFTH
 EDITION (2014). THE FBC SIXTH EDITION (2017) WENT INTO
 EFFECT ON JANUARY 1, 2018. ALL NEW PERMITS APPLIED FOR
 ON OR AFTER THAT DATE ARE REQUIRED TO COMPLY WITH AND
 REFERENCE THE FBC SIXTH EDITION (2017). FS CHAPTER 553
  
 2) THE REFERENCED STANDARDS ON SHEET A-101 ARE OLD AND
 NOT THE ONES THAT ARE LISTED IN CHAPTER 46 OF THE 2017
 FBC RESIDENTIAL.
  
 3) ON A-201 THE GARAGE SEPARATION CODE SECTIONS THAT
 ARE SPECIFIED ARE INCORRECT. FBC-R 302.5 IS THE
 APPLICABLE CODE IN THE 2017 EDITION. FBC 107.2.1
  
 4) ON SHEETS A-201 AND A-202, TYPICAL RAILING NOTE #3,
 R312.1.3 NO LONGER HAS THE PART ABOUT THE 64 SQUARE
 INCHES. FBC 107.2.1
  
 5) ON SHEETS A-201 AND A-202, TYPICAL STAIR NOTES NEED
 TO BE UPDATED TO THE 2017 FBC. NOTE #3 ABOUT THE SUM OF
 TWO RISERS AND ONE TREAD IS NO LONGER IN THE CODE.
 FBC-R 311.7.5
  
 6) ON SHEETS A-201 AND A-202, UPDATE THE EGRESS NOTE TO
 CODE SECTIONS 311.2, 311.3.1 AND 310.2.2. NOTE 2 SHOULD
 READ THAT SILL HEIGHT OF NOT MORE THAN 44".
  
 7) UP DATE THE STAIR NOTES ON A-201 AND A-202 TO 2017
 FBC-R TABLE R301.5 FOR MINIMUM UNIFORMLY DISTRUBITED
 LIVE LOADS.
  
 8) THE ELEVATIONS ON THE THE DRAINAGE PLAN SHEET C-1
 ARE IN NGVD-29. ON OCTOBER 5TH, 2017, THE CITY OF WEST
 PALM BEACH ADOPTED NEW FLOOD INSURANCE RATE MAPS WHICH
 USE NAVD 88 AS THE VERTICAL DATUM.
  
 9) SUBMIT THE MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE OUTDOOR GAS COOKTOP.
 FBC 107.2.1
  
 10) ON SHEET A-301 THE NOA NO. FOR THE SECTIONAL GARAGE
 DOOR DOES NOT MATCH THE ONE THAT WAS SUBMITTED.
  
 11) SECTION 2 ON SHEET A-401 HAS A NOTE STATING
 CONCRETE TILE OVER 30# FELT. THE 30# FELT ALONE IS NOT
 AN ACCEPTABLE UNDERLAYMENT FOR CONCRETE TILE. SPECIFY
 AN APPROVED CONCRETE ROOF TILE UNDERLAYMENT AND
 ASSEMBLY. FBC-R905.3
  
 12) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED
 TO INSTALL THE CEMENT ROOF TILE. IF AN ADHESIVE OR
 MORTAR WILL BE USED, THEN SUBMIT TWO SETS OF PRODUCT
 APPROVALS FOR IT. FBC 107.2.1 & FAC 61G20-3.001 PER
 FLORIDA STATUTE 553.842 (5)
  
 13) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE
 ALUMNIUM BAHAMA SHUTTERS SHOWN ON SHEET A-301. FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5)
  
 14) SUBMIT TWO SETS OF THE PRODUCT APPROVALS,
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE MASTER SEAL 550 WATERPROOFING
 SYSTEM AT THE CONCRETE BALCONY. FBC 107.2.1, FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) AND
 FBC-R905.15
  
 15) REVIEW THE PRODUCT APPROVAL NUMBERS ON THE DOOR
 SCHEDULE AND REVISE THEM TO MATCH THE ONES THAT ARE
 BEING SUBMITTED. FBC 107.2.1
  
 16) NOA NO. 14-0908.18 FOR THE FIXED WINDOWS IS
 EXPIRED. THE INSTALLATION DRAWINGS ARE TOO SMALL TO BE
 LEGIBLE. PRINT THESE IN LANDSCAPE ORIENTATION SO THEY
 BETTER FIT THE PRINTER PAPER SIZE.
  
 17) NOA NOS. 14-0908.02 FOR THE SLIDING GLASS DOORS AND
 14-0908.07 FOR THE FRENCH DOORS EXPIRED PRIOR TO THE
 DATE OF YOUR PERMIT APPLICATION. SUBMIT CURRENT PRODUCT
 APPROVALS. FAC 61G20-3.001 PER FLORIDA STATUTE 553.842
 (5)
  
 18) SPECIFY THE DOOR THAT FL 15187.3 IS INTENDED FOR.
 FBC 107.2.1
  
 19) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE 3'-6"
 X 8'-0" ENTRY DOOR. FAC 61G20-3.001 PER FLORIDA STATUTE
 553.842 (5)
  
 20) THE ENERGY CALCULATIONS SPECIFY A METAL ROOF AND
 THIS BUILDING HAS A CONCRETE TILE ROOF. PLEASE CORRECT.
 FBC-R101.5.1.1.2
  
 21) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-10-12 Cont ID  
Sent By jpearson Date 2018-10-12 Time 13:22 Rev Time 0.00
Received By jpearson Date 2018-10-12 Time 13:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-27 Cont ID  
Sent By jpearson Date 2018-08-27 Time 13:16 Rev Time 0.00
Received By jpearson Date 2018-08-27 Time 07:08 Sent To  
Notes
2018-08-27 13:16:04CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3603.3
 2. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 3. RISER DIAGRAM SHOWS A DIFFERENT CONFIGURATION THAN
 THE ELECTRICAL PLAN. WILL THERE BE MAIN BREAKER PANELS
 ON THE OUTSIDE OF THE GARAGE THAT FEED INTERIOR MAIN
 LUG PANELS? OR WILL THERE BE MAIN BREAKER PANELS IN THE
 GARAGE? THE PANEL SCHEDULES FOR BOTH PANELS SHOWS THEM
 AS MAIN LUG ONLY. CORRECT DISCREPANCY. IF THERE ARE
 MAIN LUG PANELS IN THE GARAGE, THESE WILL REQUIRE AN
 EQUIPMENT GROUNDING CONDUCTOR(EGC). IF THE METER FEEDS
 DIRECTLY TO A MAIN BREAKER PANEL, THIS SHOULD NOT HAVE
 AND EGC. PROVIDE CORRECTIONS. WPB FBC 107.2.1; NEC
 250.6, 250.122; FBC RE E3610.4, E3704.6, E3607.3.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-10-25 Cont ID  
Sent By jesmith Date 2018-10-25 Time 15:10 Rev Time 0.00
Received By jesmith Date 2018-10-25 Time 15:07 Sent To  
Notes
2018-10-25 15:10:20A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
 A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-30 Cont ID  
Sent By cpuell Date 2018-10-30 Time 11:30 Rev Time 0.00
Received By cpuell Date 2018-10-05 Time 14:54 Sent To  
Notes
2018-10-09 14:54:39R35

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-12 Cont ID  
Sent By rmcdouga Date 2018-09-12 Time 18:59 Rev Time 0.00
Received By rmcdouga Date 2018-08-03 Time 14:22 Sent To  
Notes
2018-08-08 14:22:15R32

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-10-29 Cont ID  
Sent By rmcdouga Date 2018-10-29 Time 08:34 Rev Time 0.00
Received By rmcdouga Date 2018-10-29 Time 08:33 Sent To  
Notes
2018-10-29 08:35:00MU-2018-34430

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-09-11 Cont ID  
Sent By rmcdouga Date 2018-09-11 Time 18:56 Rev Time 0.00
Received By rmcdouga Date 2018-09-11 Time 18:56 Sent To  
Notes
2018-09-11 18:57:31PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-10-26 Cont ID  
Sent By cmontell Date 2018-10-26 Time 10:22 Rev Time 0.00
Received By cmontell Date 2018-10-26 Time 10:06 Sent To  
Notes
2018-10-26 10:22:05MECHANICAL PLAN REVIEW NOTES
  
 PROVISO
 PER 2017 FLORIDA BUILDING CODE - MECHANICAL, SIXTH
 EDITION SECTION 601.6 BALANCED RETURN AIR.
 RETURN IN MASTER SUITE NEEDS TO BE 18?
  
  
 CHRIS MONTELLO
 561-805-6733

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-09-04 Cont ID  
Sent By cmontell Date 2018-09-04 Time 13:43 Rev Time 0.00
Received By cmontell Date 2018-09-04 Time 13:14 Sent To  
Notes
2018-09-04 13:42:44MECHANICAL PLAN FAIL
  
 1 - NEED EQUIPMENT SIZING PER 2017 FLORIDA BUILDING
 CODE - ENERGY CONSERVATION SEC. R403.7.1
  
  
 CHRIS MONTELLO
 561-805-6733
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-10-25 Cont ID  
Sent By jesmith Date 2018-10-25 Time 14:36 Rev Time 0.00
Received By jesmith Date 2018-10-25 Time 14:35 Sent To  
Notes
2018-10-25 14:36:54PLUMBING COMMENTS: APPROVED
  
 PROVISO
  
 1. GUEST BATH BATH:FIXTURE DRAINS FOR SHOWER AND
 BATHTUB IN MUST CONNECT INDEPENDENTLY TO THE WET VENT.
 P3801.1
 2. KITCHEN SINK: DISHWASHERS TO CONNECT TO SINK
 TAILPIECE ABOVE THE TRAP INLET.
 3. GENERAL NOTE: ALL FIXTURE DRAINS MUST CONNECT TO
 VENT IN ACCORDANCE WITH P3105.1 & TABLE P3105.1;
 MAXIMUM DISTANCE OF TRAP TO VENT.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL: [email protected]
 PHONE: 561-805-6715

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-09-06 Cont ID  
Sent By shill Date 2018-09-06 Time 09:33 Rev Time 0.00
Received By jesmith Date 2018-09-06 Time 09:34 Sent To  
Notes
2018-09-07 12:37:34REVIEW COMPLETED BY JERALD SMITH 0017-P
2018-09-06 09:32:461ST REVIEW: FBC 2017 6TH EDITION
 PERMIT 18080193
 PLUMBING COMMENTS: DENIED
  
 1. REGARDING SANITARY PLUMBING RISER ON PLAN SHEET S-1:
 A. PLEASE ID BATHROOMS ON RISER DIAGRAM, MATCHING THEM
 TO THE BATHROOMS ON PLAN SHEET A-201 AND A-202; PROVIDE
 DISTINCTIVE ID, I.E. BATH #1, BATH #2. NOTE THAT "PWDR"
 ON PLAN SHEET A-201 APPEARS TO BE "CABANA" ON THE RISER
 DIAGRAM. PLEASE CLARIFY.
  
 B. SHOWER BATH ADJACENT TO "PWDR" BATH ON PLAN SHEET
 A-201 SHOWS TWO INDIVIDUAL SHOWER DRAINS. PLUMBING
 RISER ON PLAN SHEET S-1 SHOWS ONLY ONE FIXTURE DRAIN.
 SHOW SECOND FIXTURE DRAIN FOR THE SECOND SHOWER DRAIN
 AND CONNECT TO THE WET VENT. 2017 FBC RES 3108.1
  
 C. FIXTURE DRAINS FOR SHOWERS AND WATER CLOSETS IN BOTH
 UPSTAIRS SHOWER BATHS MUST CONNECT INDEPENDENTLY TO THE
 WET VENT. CORRECT ON THE SANITARY RISER DIAGRAM ON PLAN
 SHEET S-1 TO SHOW THE SAME. 2017 FBC RES 3108.1
  
 2. THERE IS A GAS FIRED TANKLESS WATER HEATER AND A BBQ
 GRILL NOTED ON PLAN SHEET A-201. A GAS PLAN HAS NOT
 BEEN INCLUDED IN THIS SUBMITTAL PACKAGE. A GAS PLAN
 REVIEW HAS NOT BEEN PERFORMED AT THIS TIME. A SEPARATE
 GAS PERMIT AND PLANS WILL BE REQUIRED FOR A CONTRACTOR
 TO PERFORM THE RELATED WORK PER WPB AMEND. TO FBC SEC.
 105.1. PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
  
 3. NOTE: SEE FOLLOWING COMMENTS
 A. HAND HELD SHOWER REQUIRES AN ATMOSPHERIC VACUUM
 BREAKER AT SHOWER ARM OUTLET FBC RES 2708.5
  
 B. SHOWER CONTROL VALVE(S) SHALL BE PRESSURE BALANCED
 PB,THERMOSTATIC MIXING (TM) OR COMBINATION PB/TM VALVE
 TYPES WITH HIGH TEMPERATURE LIMITING STOP FBC RES
 2708.4
  
 C. ACCESSIBLE TEMPERATURE LIMITING CONTROL DEVICE
 REQUIRED ON HOT WATER TO BATHTUB IS REQUIRED. FBC RES
 2713.3
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2018-10-29 Cont ID  
Sent By rmcdouga Date 2018-10-29 Time 08:28 Rev Time 0.00
Received By rmcdouga Date 2018-10-29 Time 08:28 Sent To  
Notes
2018-10-29 08:33:48ROOFING PRODUCT APPROVALS
 1) CROWN BUILDING PRODUCTS, SANIBEL CONCRETE ROOF TILE,
 NOA NO.14-0102.04
 2) ICP, AH-160, NOA NO. 17-0322.03
 3) TARCO, ROOFING MEMBRANES AND UNDERLAYMENTS, NOA
 NO.16-1116.09

Review Stop Z ZONING
Rev No 2 Status P Date 2018-10-30 Cont ID  
Sent By awooten Date 2018-10-30 Time   Rev Time 0.00
Received By awooten Date 2018-10-30 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-08-16 Cont ID  
Sent By awooten Date 2018-08-16 Time 14:07 Rev Time 0.00
Received By awooten Date 2018-08-15 Time 16:33 Sent To  
Notes
2018-08-16 14:07:01*****************************ZONING REVEIW
 FAILED*************************************
  
 THE LANDSCAPE PLAN SUBMITTED WITH THIS PERMIT NEEDS TO
 BE SUBMITTED ON ITS OWN AS A LANDSCAPE PERMIT.
  
 THE DRIVEWAY, FENCE AND POOL REQUIRE A SEPARATE PERMIT.
  
 PROVIDE THE SETBACKS FOR ALL THE MECHANICAL EQUIPMENT
 (IT CANNOT GO MORE THAN 4 FEET INTO THE SETBACK).
  
 FRONT AND REAR SETBACKS ARE MISSING FROM THE SITE PLAN.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  