| Plan Review Stops For Permit 18080127 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2018-11-20 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-11-20 |
Time |
12:19 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-11-20 |
Time |
12:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2018-10-25 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-10-25 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-10-25 |
Time |
08:28 |
Sent To |
I |
|
| Notes |
| 2018-10-25 09:48:57 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE FLOOR PLAN AND PARTIAL ELEVATION ON SHEET AME-1 | | | SPECIFIES A NEW IMPACT RESISTANT SINGLE HUNG WINDOW NOA | | | #17-0918.09. THE NOA NO. 17-0918.09 THAT IS ATTACHED TO | | | THE PLANS IS FOR A CGI HORIZONTAL SLIDING WINDOW. THE | | | TYPICAL WALL SECTION ON SHEET AME-1 SPECIFIES A NEW | | | IMPACTRATED SINGLE HUNG WINDOW NOA NO. 18-0124.06. | | | PLEASE CORRECT THE DRAWINGS AND PROVIDE TWO SETS OF THE | | | PRODUCT APPROVALS FOR THE PROPOSED WINDOW THAT HAVE | | | BEEN REVIEWED AND APPROVED BY THE DESIGNER OF RECORD. | | | FBC 107.3.4 | | | | | | 2) FBC 404.1.6 REQUIRES THE TOP OF THE MONOLITHIC SLAB | | | TO BE A MINIMUM OF 4" ABOVE THE ADJACENT FINISH GRADE. | | | | | | 3) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-09-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-09-18 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-09-18 |
Time |
07:13 |
Sent To |
I |
|
| Notes |
| 2018-09-18 09:41:34 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE VALUATION FOR THIS PROJECT ON THE APPLICATION OF | | | $5,000.00 APPEARS TO BE LOW. SUBMIT A COPY OF THE | | | SIGNED CONTRACT TO VERIFY THE VALUATION. FBC 109.3 | | | BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES, | | | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL | | | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC, | | | PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE | | | WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, | | | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED | | | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES | | | (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | | | 2) OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY | | | EFFICIENCY FORM PER FBC ENERGY CONSERVATION SECTION | | | R103.1.1.2. | | | | | | 3) SPECIFY THE WIND DESIGN DATA (WIND SPEED, EXPOSURE | | | CATEGORY, ETC.) FOR THIS PROJECT ON THE PLANS. FBC | | | 107.2.1 & FBC-R301.2.1 | | | | | | 4) THE SINGLE HUNG WINDOW PRODUCT APPROVAL THAT WAS | | | SUBMITTED, NOA NO. 18-0124.06, DOES NOT MEET THE | | | PRESSURES THAT ARE LISTED ON THE PARTIAL ELEVATION ON | | | SHEET 1 OF THE PLANS. THESE PRESSURES APPEAR TO BE | | | HIGHER THAN THEY SHOULD BE FOR A ONE STORY STRUCTURE | | | LOCATED IN EXPOSURE C WITH A 170 MPH WIND SPEED. | | | FBC-R301.2.1 | | | | | | 5) FBC 107.1 REQUIRES A MINIMUM OF TWO SETS OF | | | CONSTRUCTION DOCUMENTS TO BE SUBMITTED WITH THE PERMIT | | | APPLICATION. PLEASE SUBMIT AN ADDITIONAL COPY OF THE | | | SINGLE HUNG WINDOW PRODUCT APPROVAL. | | | | | | 6) SPECIFY THE REQUIRED DESIGN PRESSURES FOR THE | | | SMALLER 27 X 27 WINDOW THAT IS TO BE REPLACED. FBC | | | 107.2.1 & FBC-R301.2.1 | | | | | | 7) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2018-11-20 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-11-20 |
Time |
05:37 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-11-20 |
Time |
05:27 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-10-24 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-10-24 |
Time |
18:18 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-10-24 |
Time |
18:18 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2018-08-29 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-08-29 |
Time |
11:20 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-08-29 |
Time |
10:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-11-20 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-11-20 |
Time |
12:20 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-11-07 |
Time |
13:38 |
Sent To |
|
|
| Notes |
| 2018-11-08 13:38:13 | RESUB ROUTED TO ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-10-25 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-10-25 |
Time |
09:52 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-10-19 |
Time |
16:00 |
Sent To |
|
|
| Notes |
| 2018-10-22 16:00:28 | RESUB ROUTED TO ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-09-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-09-18 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-08-02 |
Time |
11:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2018-11-27 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-11-27 |
Time |
11:58 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-11-27 |
Time |
11:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2018-09-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-09-18 |
Time |
07:12 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-09-18 |
Time |
07:08 |
Sent To |
|
|
| Notes |
| 2018-11-20 12:21:24 | ONE SET OF PLANS CAN BE CHECKED OUT NOW TO TAKE TO PBC | | | FOR IMPACT FEE REVIEW. | | 2018-09-18 07:12:53 | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | | (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE | | | PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE | | | RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS | | | APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE | | | FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD | | | MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2018-09-15 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2018-09-15 |
Time |
08:42 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2018-09-15 |
Time |
08:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2018-11-09 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2018-11-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2018-11-09 |
Time |
|
Sent To |
E |
|
| Notes |
| 2018-11-09 11:07:02 | VALUE OF IMPROVEMENT ($5,000) DOES NOT EXCEED 50% VALUE | | | OF THE EXISTING STRUCTURE ($77,589). |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2018-10-24 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2018-10-24 |
Time |
11:44 |
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2018-10-24 |
Time |
11:44 |
Sent To |
E |
|
| Notes |
| 2018-10-24 11:44:05 | VALUE OF IMPROVEMENT ($5,000) DOES NOT EXCEED 50% VALUE | | | OF THE EXISTING STRUCTURE ($77,589). | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2018-08-14 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2018-08-14 |
Time |
|
Rev Time |
|
| Received By |
llouie |
Date |
2018-08-14 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-08-14 14:50:10 | VALUE OF IMPROVEMENT ($5,000) DOES NOT EXCEED 50% VALUE | | | OF THE EXISTING STRUCTURE ($77,589). | | | |
|
|