| 2018-08-06 16:33:53 | 08/06/2018 1ST GAS REVIEW **DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. SUBMIT ON THE ISOMETRIC DRAWING THAT CLEARLY SHOWS |
| | THE LENGTH OF PIPE AND TYPE OF CUT SECTIONS OF PIPE TO |
| | GENERATOR PER 2017 FBC FUEL GAS RES SECS. G2413.4.1, |
| | G2413.4.2. |
| | 2. SUBMIT TWO COPIES MANUFACTURER?S SPECIFICATIONS FOR |
| | THE PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION AND THEIR LOCATIONS, IF APPLICABLE AND OR |
| | AVAILABLE AND SHALL BE ON SITE, 2017 FBC FUEL GAS RES. |
| | SEC. G2421.1. |
| | 3. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| | CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR |
| | EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 4. ON ISOMETRIC PLEASE SHOW THE TYPE OF PIPE MATERIAL |
| | BEING INSTALLED, ALL PIPE SIZES, AND THE CORRESPONDING |
| | EHD NUMBER OF THE CORRUGATED STAINLESS STEEL TUBING (IF |
| | APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO THE |
| | FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC |
| | FUEL GAS SEC. 402.4.1 OR 2017 FBC FUEL GAS RES. SEC. |
| | G2413.4.1 |
| | 6. PLEASE PROVIDE THE ADDRESS OF THE HOUSE ON ISOMETRIC |
| | DRAWING, WPB AMENDMENTS TO THE FBC WPB A 107.1 |
| | 7. THERE SEEM TO BE TWO PRIOR GAS INSTALLATIONS ON THIS |
| | ADDRESS. I HAVE PRINTED THE TWO PREVIOUS INSTALLATION |
| | OF THE SYSTEMS (FOR REFERENCE ONLY) SO YOU CAN |
| | CORRECTLY ADDRESS THE BTU LOAD OF EACH APPLIANCE AND |
| | THE TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC |
| | FUEL GAS SECS. 401.8 THROUGH 402.6.1 AND TABLES 402.4 |
| | (1) THROUGH 402.4 (37) OR 2017 FBC FUEL GAS RES. SEC. |
| | G2413. |
| | 8. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| | THE GAS CODE OR ANOTHER STANDARD THAT WAS USED IN THE |
| | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC FUEL |
| | GAS RES. SEC. G2412.4, G2412.8, G2413.1, G2413.2, & |
| | G2413.3. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |