Plan Review Details - Permit 18080040
Plan Review Stops For Permit 18080040
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-10-29 Cont ID  
Sent By shill Date 2018-10-29 Time 12:45 Rev Time 0.00
Received By shill Date 2018-10-29 Time 12:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-10-06 Cont ID  
Sent By shill Date 2018-10-06 Time 10:34 Rev Time 0.00
Received By shill Date 2018-10-06 Time 10:34 Sent To  
Notes
2018-10-06 10:34:38PROVISO: COMPLY WITH PLUMBING COMMENTS
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-16 Cont ID  
Sent By shill Date 2018-08-16 Time 08:31 Rev Time 0.00
Received By shill Date 2018-08-15 Time 07:49 Sent To  
Notes
2018-08-15 07:49:06SEE PLUMBING COMMENTS
  
 PLEASE HAVE ARCHITECT CONTACT ME TO DISCUSS RESOLUTIONS
 SAMANTHA HILL, [email protected], 561-805-6724

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-10-29 Cont ID  
Sent By shill Date 2018-10-29 Time 12:46 Rev Time 0.00
Received By shill Date 2018-10-23 Time 13:44 Sent To  
Notes
2018-10-24 13:45:09RESUB OF REVISION ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-06 Cont ID  
Sent By shill Date 2018-10-06 Time 10:34 Rev Time 0.00
Received By shill Date 2018-09-27 Time 15:37 Sent To  
Notes
2018-09-28 15:37:44RESUB OF REVISION ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-16 Cont ID  
Sent By shill Date 2018-08-16 Time 08:31 Rev Time 0.00
Received By shill Date 2018-08-01 Time 13:37 Sent To  
Notes
2018-08-13 07:59:308/13 TO TL DESK
  
2018-08-02 13:38:10REVISION ROUTED TO SHILL

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-10-25 Cont ID  
Sent By tklarge Date 2018-10-25 Time 13:13 Rev Time 0.00
Received By tklarge Date 2018-10-25 Time 13:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-10-01 Cont ID  
Sent By tklarge Date 2018-10-01 Time 09:40 Rev Time 0.00
Received By tklarge Date 2018-10-01 Time 06:24 Sent To B
Notes
2018-10-01 09:19:431) DETAILS HAVE TO BE SUBMITTED FOR THE INSTALLATION OF
 THE REINFORCEMENT FOR FUTURE GRAB BARS FOR THE SHOWER
 AND THE WATER CLOSET.THE DETAILS SHALL COMPLY WITH THE
 FAIR HOUSING ACT DESIGN MANUAL. THE DETAILS REQUIRED
 FOR THE REINFORCEMENT SHALL SHOW THE MINIMUM AND
 MAXIMUM HEIGHTS ABOVE THE FLOOR, THE MINIMUM WIDTH OF
 THE REINFORCEMENT AND THE MINIMUM LENGTHS.
 2) THE GRAB BAR DETAIL NOTE REFERS TO SPECIFICATIONS
 FOR TYPE OF BARS, ETC. BUT NO SPECIFICATIONS HAVE BEEN
 SUBMITTED. CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-08-14 Cont ID  
Sent By tklarge Date 2018-08-14 Time 14:59 Rev Time 0.00
Received By tklarge Date 2018-08-14 Time 06:00 Sent To  
Notes
2018-08-14 14:04:501) THE RENOVATED TOILET ROOM IN THE MASTER BATH THAT IS
 UNDER THE MASTER #18021018 DOES NOT COMPLY WITH THE
 FAIR HOUSING ACT. THE BIDET HAS BEEN REMOVED AND THE
 NEW SIZE OF THE TOILET ROOM APPEARS TO BE IN VIOLATION.
 THE TOILET REQUIRES A CLEAR FLOOR SPACE IN COMPLIANCE
 WITH THE FAIR HOUSING ACT DESIGN MANUAL. THIS TOILET
 ROOM WAS ORIGINALLY DESIGNED UNDER A SPECIFICATION "B"
 TYPE BATHROOM AND MUST MEET ONE OF THE REQUIRED CLEAR
 FLOOR SPACES FOR THE WATER CLOSET.A CLEAR FLOOR SPACE
 MEASURING A MINIMUM OF 30 INCHES WIDE BY 48 INCHES DEEP
 MUST BE PROVIDED OUTSIDE THE SWING OF THE DOOR IN THIS
 TOILET ROOM.
 2) BATH #3 DOES NOT COMPLY WITH THE FAIR HOUSING ACT
 DESIGN MANUAL.IN ORDER FOR THIS BATHROOM TO COMPLY A
 MINIMUM 30 INCH WIDE BY 48 INCH DEEP CLEAR FLOOR SPACE
 SHALL BE PROVIDED PARALLEL TO THE SHOWER, AND FLUSH
 WITH THE CONTROL WALL. THE TOILET IS NOT PERMITTED TO
 ENCROACH INTO THIS CLEAR FLOOR SPACE. AS DESIGNED, THIS
 BATHROOM DOES NOT COMPLY WITH THE FAIR HOUSING ACT AND
 DOES NOT APPEAR TO BE ABLE TO COMPLY.A CLEAR FLOOR
 SPACE MEASURING A MINIMUM OF 30 INCHES WIDE BY 48
 INCHES DEEP MUST BE PROVIDED OUTSIDE THE SWING OF THE
 DOOR IN THIS BATHROOM ALSO.
 3) THERE ARE DETAILS LACKING FOR REINFORCEMENT FOR GRAB
 BARS, THE DESIGN SPECIFICATION BATHROOM TYPE, MINIMUM
 SPACE FOR THE WATER CLOSET, HEIGHT OF THE LAVATORY,
 ETC.
 NOTE: THE 5 FOOT TURNING DIAMETER SHOWN IN BATHROOM # 3
 HAS NOTHING TO DO WITH FAIR HOUSING AND I DON'T
 UNDERSTAND WHY THIS IS BEING SHOWN ON THE PLAN.
 CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  