| Plan Review Stops For Permit 18080002 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2019-02-19 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-02-19 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-02-19 |
Time |
09:36 |
Sent To |
|
|
| Notes |
| 2019-02-19 14:13:38 | PROVISO: | | | PROVIDE SUBMITTAL FOR UNDERLAYMENT WITH TEST REPORT TO | | | MEET FLAME SPREAD REQUIREMENTS FOR PLITEQ GENIEMAT | | | RST-10. | | | | | | [FBC 603.1]ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | | OR UL 723. | | | | | | IIC AND STC REPORT PROVIDED WITH SUPPORTING DOCUMENTS - | | | OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2018-12-28 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-12-28 |
Time |
09:09 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-12-26 |
Time |
15:01 |
Sent To |
|
|
| Notes |
| 2018-12-28 09:13:40 | PROVISO: | | | PROVIDE SUBMITTAL FOR UNDERLAYMENT WITH TEST REPORT TO | | | MEET FLAME SPREAD REQUIREMENTS FOR PLITEQ GENIEMAT | | | RST-10. | | | | | | [FBC 603.1]ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | | OR UL 723. | | | | | | IIC AND STC REPORT PROVIDED WITH SUPPORTING DOCUMENTS - | | | OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-10-22 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-10-22 |
Time |
16:23 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-10-22 |
Time |
11:29 |
Sent To |
|
|
| Notes |
| 2018-10-22 16:24:35 | ****CORRECTIONS**** | | | W.P.B. PERMIT: 18080002 | | | REVIEWED: OCTOBER 22, 2018 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER I | | | [email protected] | | | 561-805-6718 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC ENERGY = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. PLEASE CHANGE GOVERNING CODES FOR THIS UNIT TO BE | | | FBC 2010. THIS IS DUE TO THE FACT THAT THE BUILDING HAS | | | NO C.O. THE BUILDING OFFICIAL HAS REQUESTED ALL WORK TO | | | BE DONE UNDER 2010 CODE ADDITION AT THIS TIME. | | | | | | 2. [FBC AMENDED 107.3.5]PROVIDE DATA FOR EXISTING FLOOR | | | LIVE/DEAD LOADING DESIGN AND PROPOSED LIVE/DEAD LOADS. | | | | | | 3. [FBC AMENDED 107.3.5]PROVIDE AREA TABULATIONS FOR | | | LIVING SPACE UNDER AIR AND OUTDOOR SPACE. | | | | | | 4. PROVIDE SUBMITTAL FOR FLOORING WITH UNDERLAYMENT TO | | | BE USED FOR EACH TYPE OF FLOORING, OR INDICATE THAT THE | | | SUBMITTAL WILL BE DEFERRED. | | | INCLUDE LOCATION, AREA, FLOORING TYPE, CEILING ASSEMBLY | | | BELOW AND FLOOR THICKNESS. TWO COMPLETE COLLATED SETS | | | OF ALL DOCUMENTS REQUIRED. | | | | | | PLEASE NOTE THAT TEST REPORTS ARE REQUIRED - | | | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO | | | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST | | | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE | | | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) | | | | | | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. | | | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM | | | CEILING. PROVIDE A COPY OF THE TEST REPORT. | | | | | | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED | | | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. | | | | | | C. FBC 603.1, ALLOWABLE MATERIALS IN NON-COMBUSTIBLE | | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | | OR UL 723. | | | | | | 5. [FBC 107.3.5]PROVIDE INTERIOR ELEVATIONS FOR KITCHEN | | | AND TYPICAL BATHROOM. | | | | | | 6. ARE PLUMBING PIPES IN THE SLAB ALREADY OR WILL THE | | | FLOORS BE CUT? | | | | | | 7. SEPARATE PERMIT REQ'D FOR SMOKE ALARM. | | | | | | NOTE: | | | -THE CONTRACTOR WILL BE RESPONSIBLE TO MAINTAIN THE | | | INTEGRITY OF THE EXISTING POST TENSION FLOORS. ANY | | | MODIFICATIONS THAT INVOLVE CHANGES IN THE POST TENSION | | | FLOORS WILL REQUIRE A SPECIAL INSPECTOR AT THE EXPENSE | | | OF THE PERMIT HOLDER. | | | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW | | | OF MATERIALS REQUESTED. | | | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS | | | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) | | | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT | | | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER | | | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" | | | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS | | | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE | | | NEED "VOID", RENDERING THEM NOT USABLE. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2019-01-08 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-01-08 |
Time |
16:17 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-01-08 |
Time |
16:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-09-26 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-09-26 |
Time |
13:48 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-09-26 |
Time |
13:48 |
Sent To |
|
|
| Notes |
| 2018-09-26 13:48:52 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. ALL RECEPTACLES IN BATHROOMS REQUIRE GFCI | | | PROTECTION, INCLUDING RECEPTACLE CLOSE TO TOILET. | | | PROVIDE CORRECTION. NEC 210.8 | | | 2. ALL RECEPTACLES FOR COUNTER TOP USE IN KITCHEN | | | REQUIRE GFCI PROTECTION, INCLUDING THE ISLAND. PROVIDE | | | CORRECTION. NEC 210.8 | | | 3. PER CODE, LIGHTING WITH OPEN OR PARTIALLY ENCLOSED | | | LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT | | | BE PERMITTED IN CLOTHES CLOSETS. PROVIDE SPEC SHEET OF | | | FIXTURES IN CLOTHES CLOSETS, OR A NOTE TO SPECIFY THAT | | | THEY WILL COMPLY WITH CODE. NEC 410.16 | | | 4. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE | | | SUITABLE FOR DAMP LOCATIONS. PROVIDE SPEC SHEET FOR | | | LIGHTING OVER TUBS AND SHOWERS, OR A NOTE THEY WILL | | | COMPLY WITH CODE. NEC 410.10(D) | | | 5. AFCI PROTECTION SHOWN IN PANEL SCHEDULE IS NOT CODE | | | COMPLIANT. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, | | | SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN | | | KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, | | | PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, | | | RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND | | | SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS | | | INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES. | | | SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION. | | | PROVIDE CORRECTION. NEC 210.8, 210.12 | | | 6. LOAD CALCULATIONS FOR PANELS NEEDS TO BE COMPLETED, | | | THEY ARE CURRENTLY BLANK. WPB FBC 107.2.1; NEC 408.30, | | | 408.36 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2018-12-28 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-12-28 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-12-28 |
Time |
11:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2018-09-04 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-09-04 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-08-31 |
Time |
13:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2019-01-17 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-01-17 |
Time |
09:17 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-01-17 |
Time |
09:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-03-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-02-13 |
Time |
13:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-01-17 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-01-17 |
Time |
09:17 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-12-21 |
Time |
08:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-10-28 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2018-10-28 |
Time |
09:44 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2018-08-23 |
Time |
10:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
N |
Date |
2019-03-19 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-03-19 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-03-19 |
Time |
10:10 |
Sent To |
|
|
| Notes |
| 2019-03-19 10:11:56 | FEES PAID UNDER MAIN STRUCTURE. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2018-12-28 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-12-28 |
Time |
09:14 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-12-28 |
Time |
09:13 |
Sent To |
|
|
| Notes |
| 2018-12-28 09:14:45 | FBC AMENDED 109]PLANS WILL BE REVIEWED BY THE PBC | | | IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON | | | NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR | | | WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE | | | WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY | | | UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO | | | YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE | | | R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU | | | ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE | | | UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2018-10-22 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-10-22 |
Time |
16:24 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-10-22 |
Time |
16:24 |
Sent To |
|
|
| Notes |
| 2018-10-22 16:26:33 | [FBC AMENDED 109]PLANS WILL BE REVIEWED BY THE PBC | | | IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON | | | NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR | | | WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE | | | WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY | | | UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO | | | YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE | | | R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU | | | ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE | | | UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2019-03-19 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-03-19 |
Time |
08:38 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-03-18 |
Time |
16:11 |
Sent To |
I |
|
| Notes |
| 2019-03-19 08:39:04 | MECHANICAL PROVISOS | | | | | | 1) SMOKE DETECTORS REQUIRED IN THE HP SUPPLY SYSTEMS | | | AND RETURN AIR CLOSETS. | | | 2) NON-COMBUSTIBLE DOORS REQUIRED FOR ALL AC CLOSETS. | | | 3) DRYER AND KITCHEN COOKING EXHAUST DUCTS SHALL NOT | | | RUN THROUGH PLENUMS. | | | 4) DRYER BOOSTER FAN SHALL BE UL LISTED AND LABELED | | | 5) ACCESS REQUIRED FOR THE DRYER BOOSTER FAN. | | | 6) MANUFACTURER'S SPECIFICATIONS FOR THE ELECTRIC AND | | | GAS-FIRED COOKING APPLIANCES, KITCHEN HOOD AND EXHAUST | | | DUCT, DRYER AND DRYER BOOSTER FAN SHALL BE ONSITE AT | | | TIME OF INSPECTION. | | | 7) ALL ELECTRIC COOKING APPLIANCES SHALL BE UL LISTED | | | AND LABELED FOR RESIDENTIAL USE. | | | 8) KITCHEN EXHAUST HOOD SHALL BE A TYPE II HEAT HOOD | | | LISTED AND LABELED FOR DOMESTIC USE. | | | 9) FIRE DAMPERS NOT ALLOWED IN THE KITCHEN EXHAUST | | | DUCT. | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2019-01-14 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-01-14 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-01-11 |
Time |
17:08 |
Sent To |
|
|
| Notes |
| 2019-01-14 13:36:45 | 1ST REVIEW FBC-2010 MECHANICAL | | | PERMIT #18080002 | | | 10/3/2018 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE- 2010 | | | FBC M- FLORIDA MECHANICAL CODE- 2010 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE- 2010 | | | FBC FG- FLORIDA FUEL GAS CODE- 2010 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC 2010 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M100: THE REQUIRED SMOKE DETECTORS IN BOTH THE | | | PLENUM CLOSETS AND SUPPLY DUCTS WERE NOT PROVIDED FOR | | | HP- B,C, & E. | | | | | | 2) M100 & M101: PLEASE CHOOSE ONE SMOKE DETECTOR | | | IDENTIFICATION SYMBOL OR THE OTHER- S OR SD. | | | | | | 3) M101: THE FIRE DAMPERS IN THE KITCHEN EXHAUST AND | | | MAKEUP AIR DUCTS ARE NOT REQUIRED PER SECTION 607.5.5 | | | (5). PLEASE REMOVE THE DAMPER AND PROVIDE PROTECTION | | | FOR THE BOTTOM OF THE SHAFT ENCLOSURE IN COMPLIANCE | | | WITH SECTION 607.5.5.1 FBC M, AND 713.1.1 FBC B. | | | | | | 4) M101: AS PREVIOUSLY REQUESTED PLEASE INDICATE THE | | | TYPE OF EXHAUST AND MAKEUP AIR DUCTS TO BE INSTALLED | | | AND PROVIDE PRODUCT SUBMITTALS FOR THE DUCTS AND THE | | | THE KITCHEN EXHAUST HOOD. | | | | | | 5) M101: PLACE A NOTE INDICATING AN ACCESS PANEL WILL | | | BE PROVIDED FOR THE DRYER BOOSTER FAN. | | | | | | 6) COMMENTS #7, 8, & 10 FROM THE 1ST REVIEW PRINTED | | | BELOW STILL EXIST- PLEASE COMPLY. | | | | | | 7) PROVIDE A CALCULATION TABLE ON THE PLAN SHOWING THE | | | TOTAL LENGTH OF THE DRYER EXHAUST DUCT RUN, AND THE | | | MAXIMUM ALLOWABLE RUN DISTANCE PER THE MANUFACTURER'S | | | SPECIFICATIONS FOR THE DRYER AND THE NEW BOOSTER FAN-- | | | SECTIONS 504.6.4.1 & 506.4.2 FBC M. (THIS COMMENT IS | | | NOW MODIFIED TO INLUDE THE NEW DRYER BOOSTER FAN. | | | PLEASE SEE THE EXCEPTION UNDER SECTION 504.6.4.1 FOR | | | REQUIRED BOOSTER FAN LABEL). | | | | | | 8) PROVIDE CONSTRUCTION DETAILS FOR THE DRYER EXHAUST | | | DUCT ENCLOSURE AND VERIFY THAT THE EQUIVALENT LENGTH OF | | | THE EXHAUST DUCT SHALL BE INDENTIFIED ON A PERMANENT | | | LABEL OR TAG- SECTION 504.6.5 FBC M. (THE REQUIRED | | | DETAIL WAS NOT PROVIDED ON THE ARCHITECTURAL PLANS AS | | | WAS STATED IN RESPONSE NARRATIVE. PLEASE PROVIDE THE | | | DETAIL.) | | | | | | 10) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYER, | | | THE COOKING APPLIANCES, THE WALK-IN COOLER, AND THE | | | FIREPLACE.(PRIOR TO PURCHASE AND INSTALLATION, IT IS | | | ESSENTIAL TO VERIFY ALL APPLIANCES AND EQUIPMENT ARE | | | LISTED AND LABELED IN ACCORDANCE WITH THE FLORIDA | | | CODES.) | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-10-03 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-10-03 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-10-03 |
Time |
09:45 |
Sent To |
|
|
| Notes |
| 2018-10-03 11:46:54 | 1ST REVIEW FBC-2010 MECHANICAL | | | PERMIT #18080002 | | | 10/3/2018 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE- 2010 | | | FBC M- FLORIDA MECHANICAL CODE- 2010 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE- 2010 | | | FBC FG- FLORIDA FUEL GAS CODE- 2010 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC 2010 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | | ROOMS AND SPACES, INCLUDING THE REQUIRED O/A AND THE | | | EXHAUST. | | | | | | 2) SUBMIT AC COOLING AND HEATING CALCULATIONS FOR THE | | | NEW HEAT PUMPS- SECTION 503.2.1 FBC EC. | | | | | | 3) SUBMIT AN ENERGY EFFICIENCY COMPLIANCE REPORT IN | | | ACCORDANCE WITH SECTIONS 101.5 AND 501.2 FBC EC. | | | | | | 4) SHEETS M100 & M101: SMOKE DETECTORS REQUIRED IN THE | | | RETURN AIR PLENUM- SECTION 606.2.2 FBC M. PLEASE | | | PROVIDE A DETECTOR IN EACH HP CLOSER TO MEET THE | | | REQUIREMENT. A) INDICATE THE CONTROLS OPERATION FOR THE | | | DETECTORS RELATING TO THE SHUTDOWN OF THE HP'S, AND HOW | | | THE DETECTORS WILL BE SUPERVISED- SECTIONS 606.4 & | | | 606.4.1 FBC M. | | | | | | 5) M100: IDENTIFY THE HP LOCATED IN THE CLOSET BY HALL | | | 135- SECTION 107.2.1 WPB. | | | | | | 6) M101: PLEASE REVIEW SECTION 504.8 FBC M PRINTED | | | BELOW AND REVISE THE PLANS AND DETAILS TO SHOW | | | COMPLIANCE. PROVIDE SUBMITTALS FOR THE KITCHEN HOOD, | | | EXHAUST FAN, AND EXHAUST DUCT. | | | | | | 504.8 COMMON EXHAUST SYSTEMS FOR DOMESTIC KITCHENS | | | LOCATED IN MULTISTORY STRUCTURES. | | | | | | WHERE A COMMON MULTISTORY DUCT SYSTEM IS DESIGNED AND | | | INSTALLED TO CONVEY EXHAUST FROM MULTIPLE DOMESTIC | | | KITCHEN EXHAUST SYSTEMS, THE CONSTRUCTION OF THE SYSTEM | | | SHALL BE IN ACCORDANCE WITH ALL OF THE FOLLOWING: | | | | | | 1.THE SHAFT IN WHICH THE DUCT IS INSTALLED SHALL BE | | | CONSTRUCTED AND FIRE-RESISTANCE RATED AS REQUIRED BY | | | THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 2.DAMPERS SHALL BE PROHIBITED IN THE EXHAUST DUCT, | | | EXCEPT AS SPECIFIED IN SECTION 505.1. PENETRATIONS OF | | | THE SHAFT AND DUCTWORK SHALL BE PROTECTED IN ACCORDANCE | | | WITH SECTION 607.5.5, EXCEPTION 2. | | | | | | 3.RIGID METAL DUCTWORK SHALL BE INSTALLED WITHIN THE | | | SHAFT TO CONVEY THE EXHAUST. THE DUCTWORK SHALL BE | | | CONSTRUCTED OF SHEET STEEL HAVING A MINIMUM THICKNESS | | | OF 0.0187 INCH (0.4712 MM) (NO. 26 GAGE) AND IN | | | ACCORDANCE WITH SMACNA DUCT CONSTRUCTION STANDARDS. | | | | | | 4.THE DUCTWORK WITHIN THE SHAFT SHALL BE DESIGNED AND | | | INSTALLED WITHOUT OFFSETS. | | | | | | 5.THE EXHAUST FAN MOTOR DESIGN SHALL BE IN ACCORDANCE | | | WITH SECTION 503.2. | | | | | | 6. THE EXHAUST FAN MOTOR SHALL BE LOCATED OUTSIDE OF | | | THE AIRSTREAM. | | | | | | 7.THE EXHAUST FAN SHALL RUN CONTINUOUSLY, AND SHALL BE | | | CONNECTED TO A STANDBY POWER SOURCE. | | | | | | 8. EXHAUST FAN OPERATION SHALL BE MONITORED IN AN | | | APPROVED LOCATION AND SHALL INITIATE AN AUDIBLE OR | | | VISUAL SIGNAL WHEN THE FAN IS NOT IN OPERATION. | | | | | | 9.WHERE THE EXHAUST RATE FOR AN INDIVIDUAL KITCHEN | | | EXCEEDS 400 CFM (0.19 M3/S) MAKEUP AIR SHALL BE | | | PROVIDED IN ACCORDANCE WITH SECTION 505.2. | | | | | | 10.A CLEANOUT OPENING SHALL BE LOCATED AT THE BASE OF | | | THE SHAFT TO PROVIDE ACCESS TO THE DUCT TO ALLOW FOR | | | CLEANOUT AND INSPECTION. THE FINISHED OPENINGS SHALL BE | | | NOT LESS THAN 12 INCHES BY 12 INCHES (305 MM BY 305 | | | MM). | | | | | | 11.SCREENS SHALL NOT BE INSTALLED AT THE TERMINATION. | | | | | | 12.THE COMMON MULTISTORY DUCT SYSTEM SHALL SERVE ONLY | | | KITCHEN EXHAUST AND SHALL BE INDEPENDENT OF OTHER | | | EXHAUST SYSTEMS. | | | | | | 7) PROVIDE A CALCULATION TABLE ON THE PLAN SHOWING THE | | | TOTAL LENGTH OF THE DRYER EXHAUST DUCT RUN, AND THE | | | MAXIMUM ALLOWABLE RUN DISTANCE PER THE MANUFACTURER'S | | | SPECIFICATIONS-- SECTIONS 504.6.4.1 & 506.4.2 FBC M. | | | | | | 8) PROVIDE CONSTRUCTION DETAILS FOR THE DRYER EXHAUST | | | DUCT ENCLOSURE AND VERIFY THAT THE EQUIVALENT LENGTH OF | | | THE EXHAUST DUCT SHALL BE INDENTIFIED ON A PERMANENT | | | LABEL OR TAG- SECTION 504.6.5 FBC M. | | | | | | 9) PROVIDE DETAILS FOR THE TOILET, DRYER, AND KITCHEN | | | SUBDUCTS. | | | | | | 10) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYER, | | | THE COOKING APPLIANCES, THE WALK-IN COOLER, AND THE | | | FIREPLACE. | | | | | | 11) SHOW THE LOCATION OF THE WALK-IN COOLER CONDENSER | | | AND PROVIDE ENGINEERING FOR INSTALLATION- SECTION | | | 301.12 FBC M. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2019-03-15 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2019-03-15 |
Time |
12:26 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2019-03-15 |
Time |
12:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2019-01-17 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-01-17 |
Time |
08:30 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-01-17 |
Time |
08:30 |
Sent To |
|
|
| Notes |
| 2019-01-17 09:16:49 | | | | 2ND REVIEW: 18080002 | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: | | | | | | PREVIOUS COMMENT NOT COMPLIED 1. PLEASE PROVIDE DETAILS | | | SHOWING THE HEIGHT DIMENSIONS FOR THE GRAB BAR BACKING. | | | PER FHA DESIGN MANUAL REQUIREMENT #6 PG. 6.3 - 6.13 | | | | | | NEW COMMENTS: | | | | | | 1. PLEASE SHOW COMPLIANCE GRAB BAR BACKING IS REQUIRED | | | IN ALL THE BATHROOMS REGARDLESS IF IT'S SPEC A OR B. | | | PER FHA DESIGN MANUAL CH 6 PG. 6.3 | | | | | | 2. SHT. P401 ON SOIL STACK S1 FOR BATH 3-4 THE | | | HORIZONTAL WET VENT FOR THE TWO SHOWERS SHALL NOT BE | | | OFFSET, THE MAIN SECTION OF THE HORIZONTAL WET VENT | | | PIPE IS INTENDED TO BE INSTALLED HORIZONTALLY WITHOUT | | | ANY OFFSETS WITH EACH DRAIN CONNECTED INDEPENDENTLY TO | | | THE HORIZONTAL DRAIN IN ORDER TO KEEP FLOW TURBULENCE | | | AT A MINIMUM. FBC PL 912.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2019-01-17 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-10-10 |
Time |
08:30 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-10-09 |
Time |
16:40 |
Sent To |
|
|
| Notes |
| 2018-10-10 13:40:43 | 1ST REVIEW: | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. PLEASE PROVIDE DETAILS SHOWING THE HEIGHT DIMENSIONS | | | FOR THE GRAB BAR BACKING. PER FHA DESIGN MANUAL | | | REQUIREMENT #6 PG. 6.3 - 6.13 | | | | | | 2. SHOW CLEAR FLOOR SPACE FOR THE TOILET YOU SHOW A | | | 30'X48" IT SHALL BE 48X56 THE ROOM IT IS IN SHOWS A | | | DIMENSION OF 47 1/4" PLEASE CLARIFY. PER FHA DESIGN | | | MANUAL REQUIREMENT #7 PG. 7.43 | | | | | | 3. THE CLEAR FLOOR SPACE FOR THE SHOWER AND THE | | | LAVATORY SHALL BE SHOWN FLUSH AGAINST THE FIXTURE WITH | | | THE SPACE FOR THE LAVATORY CENTERED ON THE LAVATORY AND | | | THE ONE FOR THE SHOWER THE END EVEN WITH THE CONTROL | | | WALL . PER FHA DESIGN MANUAL REQUIREMENT #7 PG 7.47 | | | +7.53 + 7.56 | | | | | | 4. PLEASE PROVIDE ISOMETRIC DRAWINGS FOR THE SANITARY, | | | WATER AND GAS. PER WPB AMEND TO FBC 107.3.5.1.3(13) + | | | 107.3.5.1.5(9) | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2019-03-19 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-03-19 |
Time |
08:41 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-03-19 |
Time |
08:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2018-12-28 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-12-28 |
Time |
09:02 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-12-26 |
Time |
15:01 |
Sent To |
|
|
| Notes |
| 2018-12-28 09:03:17 | IF COMMENTS PROVIDED AT 2ND REVIEW NEW SHEETS WILL NEED | | | TO BE CHECKED. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2018-09-26 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-09-26 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-09-26 |
Time |
09:06 |
Sent To |
|
|
| Notes |
| 2018-09-26 09:06:31 | SIGNATURES OK, WILL NEED TO BE CHECKED UPON | | | RE-SUBMITTAL. FS 471, 481; WPB FBC 107.1 |
|
|