Plan Review Details - Permit 18080002
Plan Review Stops For Permit 18080002
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-02-19 Cont ID  
Sent By dbattles Date 2019-02-19 Time 14:13 Rev Time 0.00
Received By dbattles Date 2019-02-19 Time 09:36 Sent To  
Notes
2019-02-19 14:13:38PROVISO:
 PROVIDE SUBMITTAL FOR UNDERLAYMENT WITH TEST REPORT TO
 MEET FLAME SPREAD REQUIREMENTS FOR PLITEQ GENIEMAT
 RST-10.
  
 [FBC 603.1]ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 IIC AND STC REPORT PROVIDED WITH SUPPORTING DOCUMENTS -
 OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-12-28 Cont ID  
Sent By dbattles Date 2018-12-28 Time 09:09 Rev Time 0.00
Received By dbattles Date 2018-12-26 Time 15:01 Sent To  
Notes
2018-12-28 09:13:40PROVISO:
 PROVIDE SUBMITTAL FOR UNDERLAYMENT WITH TEST REPORT TO
 MEET FLAME SPREAD REQUIREMENTS FOR PLITEQ GENIEMAT
 RST-10.
  
 [FBC 603.1]ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 IIC AND STC REPORT PROVIDED WITH SUPPORTING DOCUMENTS -
 OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-22 Cont ID  
Sent By dbattles Date 2018-10-22 Time 16:23 Rev Time 0.00
Received By dbattles Date 2018-10-22 Time 11:29 Sent To  
Notes
2018-10-22 16:24:35****CORRECTIONS****
 W.P.B. PERMIT: 18080002
 REVIEWED: OCTOBER 22, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. PLEASE CHANGE GOVERNING CODES FOR THIS UNIT TO BE
 FBC 2010. THIS IS DUE TO THE FACT THAT THE BUILDING HAS
 NO C.O. THE BUILDING OFFICIAL HAS REQUESTED ALL WORK TO
 BE DONE UNDER 2010 CODE ADDITION AT THIS TIME.
  
 2. [FBC AMENDED 107.3.5]PROVIDE DATA FOR EXISTING FLOOR
 LIVE/DEAD LOADING DESIGN AND PROPOSED LIVE/DEAD LOADS.
  
 3. [FBC AMENDED 107.3.5]PROVIDE AREA TABULATIONS FOR
 LIVING SPACE UNDER AIR AND OUTDOOR SPACE.
  
 4. PROVIDE SUBMITTAL FOR FLOORING WITH UNDERLAYMENT TO
 BE USED FOR EACH TYPE OF FLOORING, OR INDICATE THAT THE
 SUBMITTAL WILL BE DEFERRED.
 INCLUDE LOCATION, AREA, FLOORING TYPE, CEILING ASSEMBLY
 BELOW AND FLOOR THICKNESS. TWO COMPLETE COLLATED SETS
 OF ALL DOCUMENTS REQUIRED.
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON-COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 5. [FBC 107.3.5]PROVIDE INTERIOR ELEVATIONS FOR KITCHEN
 AND TYPICAL BATHROOM.
  
 6. ARE PLUMBING PIPES IN THE SLAB ALREADY OR WILL THE
 FLOORS BE CUT?
  
 7. SEPARATE PERMIT REQ'D FOR SMOKE ALARM.
  
 NOTE:
 -THE CONTRACTOR WILL BE RESPONSIBLE TO MAINTAIN THE
 INTEGRITY OF THE EXISTING POST TENSION FLOORS. ANY
 MODIFICATIONS THAT INVOLVE CHANGES IN THE POST TENSION
 FLOORS WILL REQUIRE A SPECIAL INSPECTOR AT THE EXPENSE
 OF THE PERMIT HOLDER.
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-01-08 Cont ID  
Sent By jleahy Date 2019-01-08 Time 16:17 Rev Time 0.00
Received By jleahy Date 2019-01-08 Time 16:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-09-26 Cont ID  
Sent By jpearson Date 2018-09-26 Time 13:48 Rev Time 0.00
Received By jpearson Date 2018-09-26 Time 13:48 Sent To  
Notes
2018-09-26 13:48:52CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ALL RECEPTACLES IN BATHROOMS REQUIRE GFCI
 PROTECTION, INCLUDING RECEPTACLE CLOSE TO TOILET.
 PROVIDE CORRECTION. NEC 210.8
 2. ALL RECEPTACLES FOR COUNTER TOP USE IN KITCHEN
 REQUIRE GFCI PROTECTION, INCLUDING THE ISLAND. PROVIDE
 CORRECTION. NEC 210.8
 3. PER CODE, LIGHTING WITH OPEN OR PARTIALLY ENCLOSED
 LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT
 BE PERMITTED IN CLOTHES CLOSETS. PROVIDE SPEC SHEET OF
 FIXTURES IN CLOTHES CLOSETS, OR A NOTE TO SPECIFY THAT
 THEY WILL COMPLY WITH CODE. NEC 410.16
 4. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE
 SUITABLE FOR DAMP LOCATIONS. PROVIDE SPEC SHEET FOR
 LIGHTING OVER TUBS AND SHOWERS, OR A NOTE THEY WILL
 COMPLY WITH CODE. NEC 410.10(D)
 5. AFCI PROTECTION SHOWN IN PANEL SCHEDULE IS NOT CODE
 COMPLIANT. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12
 6. LOAD CALCULATIONS FOR PANELS NEEDS TO BE COMPLETED,
 THEY ARE CURRENTLY BLANK. WPB FBC 107.2.1; NEC 408.30,
 408.36
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-12-28 Cont ID  
Sent By pleduc Date 2018-12-28 Time   Rev Time 0.00
Received By pleduc Date 2018-12-28 Time 11:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-09-04 Cont ID  
Sent By pleduc Date 2018-09-04 Time   Rev Time 0.00
Received By pleduc Date 2018-08-31 Time 13:42 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2019-01-17 Cont ID  
Sent By gjohnson Date 2019-01-17 Time 09:17 Rev Time 0.00
Received By gjohnson Date 2019-01-17 Time 09:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-03-19 Time   Rev Time 0.00
Received By lmarchan Date 2019-02-13 Time 13:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-01-17 Cont ID  
Sent By gjohnson Date 2019-01-17 Time 09:17 Rev Time 0.00
Received By gjohnson Date 2018-12-21 Time 08:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-28 Cont ID  
Sent By cpuell Date 2018-10-28 Time 09:44 Rev Time 0.00
Received By cpuell Date 2018-08-23 Time 10:33 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2019-03-19 Cont ID  
Sent By dbattles Date 2019-03-19 Time 10:10 Rev Time 0.00
Received By dbattles Date 2019-03-19 Time 10:10 Sent To  
Notes
2019-03-19 10:11:56FEES PAID UNDER MAIN STRUCTURE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-12-28 Cont ID  
Sent By dbattles Date 2018-12-28 Time 09:14 Rev Time 0.00
Received By dbattles Date 2018-12-28 Time 09:13 Sent To  
Notes
2018-12-28 09:14:45FBC AMENDED 109]PLANS WILL BE REVIEWED BY THE PBC
 IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON
 NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR
 WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE
 WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY
 UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE
 R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU
 ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE
 UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected]

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-10-22 Cont ID  
Sent By dbattles Date 2018-10-22 Time 16:24 Rev Time 0.00
Received By dbattles Date 2018-10-22 Time 16:24 Sent To  
Notes
2018-10-22 16:26:33[FBC AMENDED 109]PLANS WILL BE REVIEWED BY THE PBC
 IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON
 NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR
 WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE
 WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY
 UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE
 R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU
 ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE
 UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-03-19 Cont ID  
Sent By ccole Date 2019-03-19 Time 08:38 Rev Time 0.00
Received By ccole Date 2019-03-18 Time 16:11 Sent To I
Notes
2019-03-19 08:39:04MECHANICAL PROVISOS
  
 1) SMOKE DETECTORS REQUIRED IN THE HP SUPPLY SYSTEMS
 AND RETURN AIR CLOSETS.
 2) NON-COMBUSTIBLE DOORS REQUIRED FOR ALL AC CLOSETS.
 3) DRYER AND KITCHEN COOKING EXHAUST DUCTS SHALL NOT
 RUN THROUGH PLENUMS.
 4) DRYER BOOSTER FAN SHALL BE UL LISTED AND LABELED
 5) ACCESS REQUIRED FOR THE DRYER BOOSTER FAN.
 6) MANUFACTURER'S SPECIFICATIONS FOR THE ELECTRIC AND
 GAS-FIRED COOKING APPLIANCES, KITCHEN HOOD AND EXHAUST
 DUCT, DRYER AND DRYER BOOSTER FAN SHALL BE ONSITE AT
 TIME OF INSPECTION.
 7) ALL ELECTRIC COOKING APPLIANCES SHALL BE UL LISTED
 AND LABELED FOR RESIDENTIAL USE.
 8) KITCHEN EXHAUST HOOD SHALL BE A TYPE II HEAT HOOD
 LISTED AND LABELED FOR DOMESTIC USE.
 9) FIRE DAMPERS NOT ALLOWED IN THE KITCHEN EXHAUST
 DUCT.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-01-14 Cont ID  
Sent By ccole Date 2019-01-14 Time 13:33 Rev Time 0.00
Received By ccole Date 2019-01-11 Time 17:08 Sent To  
Notes
2019-01-14 13:36:451ST REVIEW FBC-2010 MECHANICAL
 PERMIT #18080002
 10/3/2018
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE- 2010
 FBC M- FLORIDA MECHANICAL CODE- 2010
 FBC EC- FLORIDA ENERGY CONSERVATION CODE- 2010
 FBC FG- FLORIDA FUEL GAS CODE- 2010
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC 2010
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M100: THE REQUIRED SMOKE DETECTORS IN BOTH THE
 PLENUM CLOSETS AND SUPPLY DUCTS WERE NOT PROVIDED FOR
 HP- B,C, & E.
  
 2) M100 & M101: PLEASE CHOOSE ONE SMOKE DETECTOR
 IDENTIFICATION SYMBOL OR THE OTHER- S OR SD.
  
 3) M101: THE FIRE DAMPERS IN THE KITCHEN EXHAUST AND
 MAKEUP AIR DUCTS ARE NOT REQUIRED PER SECTION 607.5.5
 (5). PLEASE REMOVE THE DAMPER AND PROVIDE PROTECTION
 FOR THE BOTTOM OF THE SHAFT ENCLOSURE IN COMPLIANCE
 WITH SECTION 607.5.5.1 FBC M, AND 713.1.1 FBC B.
  
 4) M101: AS PREVIOUSLY REQUESTED PLEASE INDICATE THE
 TYPE OF EXHAUST AND MAKEUP AIR DUCTS TO BE INSTALLED
 AND PROVIDE PRODUCT SUBMITTALS FOR THE DUCTS AND THE
 THE KITCHEN EXHAUST HOOD.
  
 5) M101: PLACE A NOTE INDICATING AN ACCESS PANEL WILL
 BE PROVIDED FOR THE DRYER BOOSTER FAN.
  
 6) COMMENTS #7, 8, & 10 FROM THE 1ST REVIEW PRINTED
 BELOW STILL EXIST- PLEASE COMPLY.
  
 7) PROVIDE A CALCULATION TABLE ON THE PLAN SHOWING THE
 TOTAL LENGTH OF THE DRYER EXHAUST DUCT RUN, AND THE
 MAXIMUM ALLOWABLE RUN DISTANCE PER THE MANUFACTURER'S
 SPECIFICATIONS FOR THE DRYER AND THE NEW BOOSTER FAN--
 SECTIONS 504.6.4.1 & 506.4.2 FBC M. (THIS COMMENT IS
 NOW MODIFIED TO INLUDE THE NEW DRYER BOOSTER FAN.
 PLEASE SEE THE EXCEPTION UNDER SECTION 504.6.4.1 FOR
 REQUIRED BOOSTER FAN LABEL).
  
 8) PROVIDE CONSTRUCTION DETAILS FOR THE DRYER EXHAUST
 DUCT ENCLOSURE AND VERIFY THAT THE EQUIVALENT LENGTH OF
 THE EXHAUST DUCT SHALL BE INDENTIFIED ON A PERMANENT
 LABEL OR TAG- SECTION 504.6.5 FBC M. (THE REQUIRED
 DETAIL WAS NOT PROVIDED ON THE ARCHITECTURAL PLANS AS
 WAS STATED IN RESPONSE NARRATIVE. PLEASE PROVIDE THE
 DETAIL.)
  
 10) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYER,
 THE COOKING APPLIANCES, THE WALK-IN COOLER, AND THE
 FIREPLACE.(PRIOR TO PURCHASE AND INSTALLATION, IT IS
 ESSENTIAL TO VERIFY ALL APPLIANCES AND EQUIPMENT ARE
 LISTED AND LABELED IN ACCORDANCE WITH THE FLORIDA
 CODES.)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-10-03 Cont ID  
Sent By ccole Date 2018-10-03 Time 10:57 Rev Time 0.00
Received By ccole Date 2018-10-03 Time 09:45 Sent To  
Notes
2018-10-03 11:46:541ST REVIEW FBC-2010 MECHANICAL
 PERMIT #18080002
 10/3/2018
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE- 2010
 FBC M- FLORIDA MECHANICAL CODE- 2010
 FBC EC- FLORIDA ENERGY CONSERVATION CODE- 2010
 FBC FG- FLORIDA FUEL GAS CODE- 2010
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC 2010
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES, INCLUDING THE REQUIRED O/A AND THE
 EXHAUST.
  
 2) SUBMIT AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW HEAT PUMPS- SECTION 503.2.1 FBC EC.
  
 3) SUBMIT AN ENERGY EFFICIENCY COMPLIANCE REPORT IN
 ACCORDANCE WITH SECTIONS 101.5 AND 501.2 FBC EC.
  
 4) SHEETS M100 & M101: SMOKE DETECTORS REQUIRED IN THE
 RETURN AIR PLENUM- SECTION 606.2.2 FBC M. PLEASE
 PROVIDE A DETECTOR IN EACH HP CLOSER TO MEET THE
 REQUIREMENT. A) INDICATE THE CONTROLS OPERATION FOR THE
 DETECTORS RELATING TO THE SHUTDOWN OF THE HP'S, AND HOW
 THE DETECTORS WILL BE SUPERVISED- SECTIONS 606.4 &
 606.4.1 FBC M.
  
 5) M100: IDENTIFY THE HP LOCATED IN THE CLOSET BY HALL
 135- SECTION 107.2.1 WPB.
  
 6) M101: PLEASE REVIEW SECTION 504.8 FBC M PRINTED
 BELOW AND REVISE THE PLANS AND DETAILS TO SHOW
 COMPLIANCE. PROVIDE SUBMITTALS FOR THE KITCHEN HOOD,
 EXHAUST FAN, AND EXHAUST DUCT.
  
 504.8 COMMON EXHAUST SYSTEMS FOR DOMESTIC KITCHENS
 LOCATED IN MULTISTORY STRUCTURES.
  
 WHERE A COMMON MULTISTORY DUCT SYSTEM IS DESIGNED AND
 INSTALLED TO CONVEY EXHAUST FROM MULTIPLE DOMESTIC
 KITCHEN EXHAUST SYSTEMS, THE CONSTRUCTION OF THE SYSTEM
 SHALL BE IN ACCORDANCE WITH ALL OF THE FOLLOWING:
  
 1.THE SHAFT IN WHICH THE DUCT IS INSTALLED SHALL BE
 CONSTRUCTED AND FIRE-RESISTANCE RATED AS REQUIRED BY
 THE FLORIDA BUILDING CODE, BUILDING.
  
 2.DAMPERS SHALL BE PROHIBITED IN THE EXHAUST DUCT,
 EXCEPT AS SPECIFIED IN SECTION 505.1. PENETRATIONS OF
 THE SHAFT AND DUCTWORK SHALL BE PROTECTED IN ACCORDANCE
 WITH SECTION 607.5.5, EXCEPTION 2.
  
 3.RIGID METAL DUCTWORK SHALL BE INSTALLED WITHIN THE
 SHAFT TO CONVEY THE EXHAUST. THE DUCTWORK SHALL BE
 CONSTRUCTED OF SHEET STEEL HAVING A MINIMUM THICKNESS
 OF 0.0187 INCH (0.4712 MM) (NO. 26 GAGE) AND IN
 ACCORDANCE WITH SMACNA DUCT CONSTRUCTION STANDARDS.
  
 4.THE DUCTWORK WITHIN THE SHAFT SHALL BE DESIGNED AND
 INSTALLED WITHOUT OFFSETS.
  
 5.THE EXHAUST FAN MOTOR DESIGN SHALL BE IN ACCORDANCE
 WITH SECTION 503.2.
  
 6. THE EXHAUST FAN MOTOR SHALL BE LOCATED OUTSIDE OF
 THE AIRSTREAM.
  
 7.THE EXHAUST FAN SHALL RUN CONTINUOUSLY, AND SHALL BE
 CONNECTED TO A STANDBY POWER SOURCE.
  
 8. EXHAUST FAN OPERATION SHALL BE MONITORED IN AN
 APPROVED LOCATION AND SHALL INITIATE AN AUDIBLE OR
 VISUAL SIGNAL WHEN THE FAN IS NOT IN OPERATION.
  
 9.WHERE THE EXHAUST RATE FOR AN INDIVIDUAL KITCHEN
 EXCEEDS 400 CFM (0.19 M3/S) MAKEUP AIR SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 505.2.
  
 10.A CLEANOUT OPENING SHALL BE LOCATED AT THE BASE OF
 THE SHAFT TO PROVIDE ACCESS TO THE DUCT TO ALLOW FOR
 CLEANOUT AND INSPECTION. THE FINISHED OPENINGS SHALL BE
 NOT LESS THAN 12 INCHES BY 12 INCHES (305 MM BY 305
 MM).
  
 11.SCREENS SHALL NOT BE INSTALLED AT THE TERMINATION.
  
 12.THE COMMON MULTISTORY DUCT SYSTEM SHALL SERVE ONLY
 KITCHEN EXHAUST AND SHALL BE INDEPENDENT OF OTHER
 EXHAUST SYSTEMS.
  
 7) PROVIDE A CALCULATION TABLE ON THE PLAN SHOWING THE
 TOTAL LENGTH OF THE DRYER EXHAUST DUCT RUN, AND THE
 MAXIMUM ALLOWABLE RUN DISTANCE PER THE MANUFACTURER'S
 SPECIFICATIONS-- SECTIONS 504.6.4.1 & 506.4.2 FBC M.
  
 8) PROVIDE CONSTRUCTION DETAILS FOR THE DRYER EXHAUST
 DUCT ENCLOSURE AND VERIFY THAT THE EQUIVALENT LENGTH OF
 THE EXHAUST DUCT SHALL BE INDENTIFIED ON A PERMANENT
 LABEL OR TAG- SECTION 504.6.5 FBC M.
  
 9) PROVIDE DETAILS FOR THE TOILET, DRYER, AND KITCHEN
 SUBDUCTS.
  
 10) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYER,
 THE COOKING APPLIANCES, THE WALK-IN COOLER, AND THE
 FIREPLACE.
  
 11) SHOW THE LOCATION OF THE WALK-IN COOLER CONDENSER
 AND PROVIDE ENGINEERING FOR INSTALLATION- SECTION
 301.12 FBC M.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-03-15 Cont ID  
Sent By thunt Date 2019-03-15 Time 12:26 Rev Time 0.00
Received By thunt Date 2019-03-15 Time 12:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-01-17 Cont ID  
Sent By gjohnson Date 2019-01-17 Time 08:30 Rev Time 0.00
Received By gjohnson Date 2019-01-17 Time 08:30 Sent To  
Notes
2019-01-17 09:16:49 
 2ND REVIEW: 18080002
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 PREVIOUS COMMENT NOT COMPLIED 1. PLEASE PROVIDE DETAILS
 SHOWING THE HEIGHT DIMENSIONS FOR THE GRAB BAR BACKING.
 PER FHA DESIGN MANUAL REQUIREMENT #6 PG. 6.3 - 6.13
  
 NEW COMMENTS:
  
 1. PLEASE SHOW COMPLIANCE GRAB BAR BACKING IS REQUIRED
 IN ALL THE BATHROOMS REGARDLESS IF IT'S SPEC A OR B.
 PER FHA DESIGN MANUAL CH 6 PG. 6.3
  
 2. SHT. P401 ON SOIL STACK S1 FOR BATH 3-4 THE
 HORIZONTAL WET VENT FOR THE TWO SHOWERS SHALL NOT BE
 OFFSET, THE MAIN SECTION OF THE HORIZONTAL WET VENT
 PIPE IS INTENDED TO BE INSTALLED HORIZONTALLY WITHOUT
 ANY OFFSETS WITH EACH DRAIN CONNECTED INDEPENDENTLY TO
 THE HORIZONTAL DRAIN IN ORDER TO KEEP FLOW TURBULENCE
 AT A MINIMUM. FBC PL 912.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-01-17 Cont ID  
Sent By gjohnson Date 2018-10-10 Time 08:30 Rev Time 0.00
Received By gjohnson Date 2018-10-09 Time 16:40 Sent To  
Notes
2018-10-10 13:40:431ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE DETAILS SHOWING THE HEIGHT DIMENSIONS
 FOR THE GRAB BAR BACKING. PER FHA DESIGN MANUAL
 REQUIREMENT #6 PG. 6.3 - 6.13
  
 2. SHOW CLEAR FLOOR SPACE FOR THE TOILET YOU SHOW A
 30'X48" IT SHALL BE 48X56 THE ROOM IT IS IN SHOWS A
 DIMENSION OF 47 1/4" PLEASE CLARIFY. PER FHA DESIGN
 MANUAL REQUIREMENT #7 PG. 7.43
  
 3. THE CLEAR FLOOR SPACE FOR THE SHOWER AND THE
 LAVATORY SHALL BE SHOWN FLUSH AGAINST THE FIXTURE WITH
 THE SPACE FOR THE LAVATORY CENTERED ON THE LAVATORY AND
 THE ONE FOR THE SHOWER THE END EVEN WITH THE CONTROL
 WALL . PER FHA DESIGN MANUAL REQUIREMENT #7 PG 7.47
 +7.53 + 7.56
  
 4. PLEASE PROVIDE ISOMETRIC DRAWINGS FOR THE SANITARY,
 WATER AND GAS. PER WPB AMEND TO FBC 107.3.5.1.3(13) +
 107.3.5.1.5(9)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-03-19 Cont ID  
Sent By ccole Date 2019-03-19 Time 08:41 Rev Time 0.00
Received By ccole Date 2019-03-19 Time 08:41 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2018-12-28 Cont ID  
Sent By dbattles Date 2018-12-28 Time 09:02 Rev Time 0.00
Received By dbattles Date 2018-12-26 Time 15:01 Sent To  
Notes
2018-12-28 09:03:17IF COMMENTS PROVIDED AT 2ND REVIEW NEW SHEETS WILL NEED
 TO BE CHECKED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-09-26 Cont ID  
Sent By jpearson Date 2018-09-26 Time 09:06 Rev Time 0.00
Received By jpearson Date 2018-09-26 Time 09:06 Sent To  
Notes
2018-09-26 09:06:31SIGNATURES OK, WILL NEED TO BE CHECKED UPON
 RE-SUBMITTAL. FS 471, 481; WPB FBC 107.1