Plan Review Details - Permit 18071460
Plan Review Stops For Permit 18071460
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-09-18 Cont ID  
Sent By dbattles Date 2018-09-18 Time 13:54 Rev Time 0.00
Received By dbattles Date 2018-09-18 Time 13:54 Sent To  
Notes
2018-09-18 13:55:39NO ROOFING WITH THIS PERMIT OTHER THAN TEMPORARY PATCH
 GENERATOR STAND IN UNTIL NEW ROOF IS INSTALLED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-09-04 Cont ID  
Sent By dbattles Date 2018-09-04 Time 09:20 Rev Time 0.00
Received By dbattles Date 2018-09-04 Time 09:20 Sent To  
Notes
2018-09-04 09:21:43****CORRECTIONS****
 W.P.B. PERMIT: 18071460
 REVIEWED: SEPTEMBER 04, 2018
 2ND REVIEW
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1-8 OK.
  
 NEW COMMENTS:
 THE LOAD CALCULATION I WAS ASKING ABOUT IN 1ST REVIEW
 ITEM #6 WAS FOR THE WEIGHT OF THE GENERATOR TO BE
 SUPPORTED. NOW THE GENERATOR HAS SHIFTED ORIENTATION
 AND IS ON A STAND.
  
 9. [FBC 1510.10]PLEASE PROVIDE THE SIZE OF THE UNIT AND
 FOLLOW CLEARANCE REQUIREMENTS FROM TABLE 1510.10.
 ADJUST ORIENTATION OF FUTURE UNIT ON SHEET A-105R TO
 MATCH STRUCTURAL SHEETS.
  
 10. [FBC 1511.1.1]WHAT PERCENTAGE OF ROOF IS BEING
 REPLACED? IF IT EXCEEDS 25% THAN THE WHOLE ROOF SHOULD
 BE REPLACED TO MEET CURRENT CODES.
  
 AS DISCUSSED WITH THE CONTRACTOR THIS PERMIT WAS TO
 ALLOW SOME STRUCTURAL WORK TO START WHILE THE MAIN
 PERMIT WAS BEING COMPLETED.
 THE PLANS STILL SHOW WORK BEYOUND WHAT WAS DISCUSSED.
 PLEASE REMOVE ELEMENTS FROM PLANS THAT ADD SPACE OR
 THAT WOULD REQUIRE LIFE SAFETY REVIEWS.
  
 NOTE:
 ALL WORK BEING PERFORMED IN PERMIT 18071460 IS BEING
 DONE WITHOUT REVIEWS FROM MULTI-DISIPLINES. ANY
 DEVIATIONS THAT MAY OCCUR FROM THE REVIEWS OF BUILD OUT
 PERMIT WOULD BE AT THE RISK OF THE OWNER AND
 CONTRACTOR.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-16 Cont ID  
Sent By dbattles Date 2018-08-16 Time 10:50 Rev Time 0.00
Received By dbattles Date 2018-08-16 Time 10:50 Sent To  
Notes
2018-08-16 10:51:43****CORRECTIONS****
 W.P.B. PERMIT: 18071460
 REVIEWED: AUGUST 13, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. PROJECT EVALUATION SEEMS LOW FOR THE SCOPE SHOWN ON
 PLANS. THE ROOFING WOULD BE INCLUDED IN THE PROJECT
 VALUE AND WOULD BE ISSUED AS ZERO DOLLAR SUB-PERMIT.
 PLEASE PROVIDE COST ESTIMATE, OR CONTRACT TO SHOW
 VALUES OF ALL WORK THAT WILL BE PART OF THIS PERMIT
 (GENERATOR TO BE SEPARATE PERMIT WITH SEPARATE COST
 ASSOCIATED WITH IT)
  
 2. PROVIDE DETAILED DESCRIPTION OF THIS PERMIT?
 IS THERE A PERMIT COMING FOR TENANT BUILD-OUT?
 THE DRAWINGS SHOW THINGS THAT WOULD NEED MORE DESIGN.
 PLEASE ADJUST DRAWINGS TO MATCH THE SCOPE OF WORK
 INTENDED AND I CAN REVIEW.
  
 3. IT SEEMS THAT YOU ARE LOOKING TO START WORK ON
 GENERATOR. I HAVE THE FOLLOWING COMMENTS FOR JUST THAT
 PORTION, BUT I NEED MORE DETAILED PLANS FOR THE ENTRY
 WAY WORK AND THE ENCLOSING OF SEPERARTION BETWEEN THE
 BUILDINGS.
  
 4. [FBC 107.2.1.1]SUB PERMIT REQ?D FOR ROOFING.
 IS ROOFING PART OF THIS PERMIT?
  
 5. [FBC 107.2.1.2]PROVIDE PRODUCT APPROVALS FOR
 ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM DEFFERED.
  
 6. [FBC 107.2.1.1]PROVIDE ENGINEERING FOR ROOF LOADS
 INCLUDING THE FUTURE GENERATOR.
  
 7. HOW ARE 2X12?S CONNECTED AT WALLS?
  
 8. PROVIDE ROOF SHEATHING ATTACHMENT/SPACING.
  
 9. [FBC 107.2.1.1]HOW IS THE ROOF ACCESSED?
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-09-18 Cont ID  
Sent By dbattles Date 2018-09-18 Time 13:56 Rev Time 0.00
Received By dbattles Date 2018-09-07 Time 14:53 Sent To  
Notes
2018-09-18 08:53:06TO LMARCHAN
2018-09-11 14:54:15RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-04 Cont ID  
Sent By dbattles Date 2018-09-04 Time 09:21 Rev Time 0.00
Received By dbattles Date 2018-08-29 Time 15:32 Sent To  
Notes
2018-08-30 15:32:28RESUB ROUTED TO DBATTLES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-16 Cont ID  
Sent By dbattles Date 2018-08-16 Time 10:51 Rev Time 0.00
Received By dbattles Date 2018-07-31 Time 15:10 Sent To  
Notes
2018-08-02 16:55:47TO LMARCHAN
2018-08-01 15:10:47ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2018-09-18 Cont ID  
Sent By aaponte Date 2018-09-18 Time 08:52 Rev Time 0.00
Received By aaponte Date 2018-09-18 Time 08:52 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-08-02 Cont ID  
Sent By aaponte Date 2018-08-02 Time 16:55 Rev Time 0.00
Received By aaponte Date 2018-08-02 Time 16:55 Sent To B
Notes
***NONE***