Plan Review Details - Permit 18071403
Plan Review Stops For Permit 18071403
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-10-15 Cont ID  
Sent By shill Date 2018-10-15 Time 08:43 Rev Time 0.00
Received By shill Date 2018-10-15 Time 08:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-09-27 Cont ID  
Sent By shill Date 2018-09-27 Time 07:14 Rev Time 0.00
Received By shill Date 2018-09-27 Time 07:13 Sent To  
Notes
2018-09-27 07:17:22****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 2ND REVIEW:
  
 1.PLAN WAS REVISED TO "VINYL PLANK" PROPOSED.
  
 PREVIOUS COMMENT LIST REQUESTED AN EMAIL WITH THE
 FLOORING AND UNDERLAYMENT TO FACILITATE THIS REVIEW (NO
 EMAIL WAS RECEIVED).
  
 NO INFORMATION WAS PROVIDED REGARDING THE UNDERLAYMENT
 PRODUCT AND NO TEST REPORTS WERE PROVIDED.
  
 IF THE UNDERLAYMENT PRODUCT PROPOSED IS NOT ONE FOR
 WHICH WE HAVE TEST REPORTS ON FILE, THE FOLLOWING
 REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-25 Cont ID  
Sent By shill Date 2018-08-25 Time 18:03 Rev Time 0.00
Received By shill Date 2018-08-25 Time 18:03 Sent To  
Notes
2018-08-25 18:04:14****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. PLEASE ADVISE, WHAT FLOORING AND UNDERLAYMENT ARE
 PROPOSED? PLEASE ADVISE VIA EMAIL. IF THE UNDERLAYMENT
 PRODUCT PROPOSED IS NOT ONE FOR WHICH WE HAVE TEST
 REPORTS ON FILE, THE FOLLOWING REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-09-19 Cont ID  
Sent By jpearson Date 2018-09-19 Time 08:03 Rev Time 0.00
Received By jpearson Date 2018-09-19 Time 06:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-16 Cont ID  
Sent By jpearson Date 2018-08-16 Time 09:23 Rev Time 0.00
Received By jpearson Date 2018-08-16 Time 09:23 Sent To  
Notes
2018-08-16 09:23:34CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4
 2. PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC
 215.5; WPB FBC 107.2.1
 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30
 4. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-09-14 Cont ID  
Sent By scaldero Date 2018-09-14 Time 10:22 Rev Time 0.00
Received By scaldero Date 2018-09-14 Time 10:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-08-06 Cont ID  
Sent By scaldero Date 2018-08-06 Time 11:48 Rev Time 0.00
Received By scaldero Date 2018-08-06 Time 11:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-27 Cont ID  
Sent By shill Date 2018-09-27 Time 07:17 Rev Time 0.00
Received By shill Date 2018-09-05 Time 11:14 Sent To  
Notes
2018-09-06 11:15:03B03

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-25 Cont ID  
Sent By shill Date 2018-08-25 Time 18:04 Rev Time 0.00
Received By shill Date 2018-07-30 Time 11:19 Sent To  
Notes
2018-07-31 11:19:13B04

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-10-12 Cont ID  
Sent By tklarge Date 2018-10-12 Time 10:45 Rev Time 0.00
Received By tklarge Date 2018-10-12 Time 10:45 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-09-27 Cont ID  
Sent By shill Date 2018-09-27 Time 07:06 Rev Time 0.00
Received By jesmith Date 2018-09-27 Time 07:06 Sent To  
Notes
2018-09-27 07:10:05FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 PLUMBING COMMENTS: DENIED
  
 1. PROVIDE PIPING MATERIALS TYPE & FIRE RATED
 ASSEMBLIES FOR RELOCATED DRAIN FLOOR PENETRATION, FBC
 107.2.1.
  
 2. ACESSIBLE TEMP LIMITING DEVICE REQUIRED FOR TUB FILL
 VALVE, FBC P 424.3.
  
 3. HI LIMIT THERMOSTATIC / PB CONTROL RQUIRED FOR
 SHOWER VALVE, FBC P 424.5.
  
 4. SHOWER PAN REQUIRED, FBC P 417.8.2.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL: [email protected]
 561-805-6715
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-08-24 Cont ID  
Sent By gjohnson Date 2018-08-24 Time 12:49 Rev Time 0.00
Received By gjohnson Date 2018-08-24 Time 06:41 Sent To  
Notes
***NONE***