Plan Review Details - Permit 18071393
Plan Review Stops For Permit 18071393
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-09-18 Cont ID  
Sent By skennedy Date 2018-09-18 Time 08:58 Rev Time 0.00
Received By skennedy Date 2018-09-18 Time 08:58 Sent To P
Notes
2018-09-18 08:59:493RD REVIEW: FBC 2017 6TH EDITION
 3RD REVIEW FBC 2017 EXISTING BUILDING
  
 1) COMPLIED - LOW VALUE, VALUE INCRESSED TO CONTRACT
 AMOUNT.
 2) COMPLIED - REQUEST TO COMPLY WITH FAIR HOUSING
 DESIGN GUIDELINES- APPLICANT HAS RIGHTLY INDICATED THE
 FAIR HOUSING DESIGN GUIDELINES DO NOT APPLY PURSUANT TO
 FAIR HOUSING ACT SECTION 804 ONLY APPLIES TO NEW
 COSTRUCTION.
 3) COMPLIED - FLOORING UNDERLAYMENT APPROVED.
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-08-30 Cont ID  
Sent By cthroop Date 2018-08-30 Time 09:04 Rev Time 0.00
Received By cthroop Date 2018-08-30 Time 09:04 Sent To I
Notes
2018-08-30 11:07:26BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. VALUE HAS NOT BEEN DETERMINED. ORIGINAL STATED VALUE
 WAS 12,600. COPY OF PROPOSAL STATES VALUE TO BE 21,100.
 THIS VALUE IS FOR LABOR ONLY. PERMIT VALUE MUST INCLUDE
 ALL LABOR AND MATERIALS, INCLUDING ANY RENTAL
 EQUIPMENT.
 THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE OF
 WORK.
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 CITY OF WPB CHPT. 1 ? VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 2. DEMONSTRATE COMPLIANCE WITH FAIR HOUSING PER
 PLUMBING REVIEW COMMENTS.
 FAIR HOUSING GUIDELINES. 2017 FLORIDA ACCESSIBILITY
 CODE/ FAIR HOUSING ACCESSIBILITY GUIDELINES. SECTION 3.
 FAIR HOUSING ACT DESIGN AND CONSTRUCTION REQUIREMENTS.
 FOR PURPOSES OF THIS SECTION, A COVERED MULTIFAMILY
 DWELLING SHALL BE DEEMED TO BE DESIGNED AND CONSTRUCTED
 FOR FIRST OCCUPANCY ON OR BEFORE MARCH 13, 1991, IF
 THEY ARE OCCUPIED BY THAT DATE OR IF THE LAST BUILDING
 PERMIT OR RENEWAL THEREOF FOR THE COVERED MULTIFAMILY
 DWELLINGS IS ISSUED BY A STATE, COUNTY OR LOCAL
 GOVERNMENT ON OR BEFORE JANUARY 13, 1990.
  
 3. ADVISORY - 6 MIL CORK IS AN APPROVED UNDERLAYMENT
 FOR CERAMIC TILE. MANY CONDO ASSOCIATIONS DO NOT ALLOW
 CORK TO BE USED. CHECK WITH THE CONDO ASSOCIATION
 BEFORE PROCEEDING.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-08 Cont ID  
Sent By cthroop Date 2018-08-08 Time 14:49 Rev Time 0.00
Received By cthroop Date 2018-08-08 Time 14:47 Sent To P
Notes
2018-08-08 14:54:04BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 THE FOLLOWING INFORMATION IS REQUIRED FOR ALL FLOORING
 SUBMITTALS:
  
 1. FLOOR PLAN WITH DIMENSIONS AND LOCATION OF WORK.
 *DESIGNER TO PRINT NAME AND SIGN PLAN PER FBC 107 *
 2. TOTAL SQUARE FOOTAGE OF NEW FLOORING.
 3. TYPE OF PROPOSED FLOORING
 (TILE/MARBLE/LAMINATE/WOOD/OTHER).
 4. STATED VALUE OF WORK.
 5. EXISTING SITE CONDITIONS:
 A) THICKNESS OF SLAB. B) CEILING ASSEMBLY (OPEN
 CONCRETE/SUSPENDED GYPSUM/ACOUSTICAL)
 6. PROPOSED UNDERLAYMENT.
 7. TEST REPORTS FOR PROPOSED UNDERLAYMENT BASED ON
 EXISTING SITE CONDITIONS.
 8. TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM?S,
 E-84, E-90 & E-492.
 9. ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE.
  
 FBC 603.1 FLAME SPREAD ? ASTM E-84-09
  
 FBC 1207.2 AIR-BORNE SOUND. ASTM E ? 90-04
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E ? 492-09
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC SPACE OR SERVICE
 AREA WITHIN THE STRUCTURE SHALL HAVE AN IMPACT
 INSULATION CLASS (IIC) RATING OF NOT LESS THAN 50 (45
 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E
 492.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-09-19 Cont ID  
Sent By skennedy Date 2018-09-19 Time 11:17 Rev Time 0.00
Received By skennedy Date 2018-09-18 Time 08:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-30 Cont ID  
Sent By cthroop Date 2018-08-30 Time 11:07 Rev Time 0.00
Received By cthroop Date 2018-08-22 Time 12:53 Sent To  
Notes
2018-08-23 12:53:33RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-08 Cont ID  
Sent By tklarge Date 2018-08-08 Time 14:56 Rev Time 0.00
Received By tklarge Date 2018-07-30 Time 11:01 Sent To  
Notes
2018-07-31 11:01:34ROUTED TO PLUMBING INBOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-09-19 Cont ID  
Sent By skennedy Date 2018-09-19 Time 11:17 Rev Time 0.00
Received By skennedy Date 2018-09-19 Time 11:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-08-29 Cont ID  
Sent By tklarge Date 2018-08-29 Time 10:43 Rev Time 0.00
Received By tklarge Date 2018-08-29 Time 09:57 Sent To  
Notes
2018-08-29 10:38:08NONE OF THE PREVIOUS PLUMBING REVIEW COMMENTS HAVE BEEN
 ADDRESSED.
 1) THIS STRUCTURE WAS BUILT IN 2001 AND THEREFORE WAS
 DESIGNED UNDER THE FAIR HOUSING ACT AND THE FAIR
 HOUSING ACT DESIGN MANUAL AS NOTED ON THE ORIGINAL
 PLANS ON FILE IN CITY RECORDS. THIS UNIT WAS DESIGNED
 AS A SPECIFICATION "A" TYPE BATHROOM.
 THE FAIR HOUSING ACT DESIGN MANUAL REQUIRES A 30 INCH
 WIDE BY 48 INCH DEEP CLEAR FLOOR SPACE BE PROVIDED AT
 SHOWER STALLS, PARALLEL TO THE FIXTURE AND FLUSH WITH
 THE CONTROL WALL. NO OTHER FIXTURE MAY OVERLAP THE
 CLEAR FLOOR SPACE AT SHOWERS EXCEPT AS PROVIDED IN THE
 FAIR HOUSING ACT DESIGN MANUAL. THE EXISTING DESIGN
 DOES NOT MEET ANY OF THE EXCEPTIONS. THE FLOOR PLAN
 SHOWS A WATER CLOSET NEXT TO WHERE THE PROPOSED SHOWER
 WOULD BE AND THEREFORE WOULD CREATE A VIOLATION OF THE
 FAIR HOUSING ACT. THE SHOWER CANNOT BE INSTALLED IN
 LIEU OF THE BATHTUB.
 2) INDICATE ON THE PLAN IF THE KITCHEN SINK WILL BE
 REPLACED.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-08-08 Cont ID  
Sent By tklarge Date 2018-08-06 Time 14:55 Rev Time 0.00
Received By tklarge Date 2018-08-06 Time 06:12 Sent To I
Notes
2018-08-06 06:17:001) THIS STRUCTURE WAS BUILT IN 2001 AND THEREFORE WAS
 DESIGNED UNDER THE FAIR HOUSING ACT AND THE FAIR
 HOUSING ACT DESIGN MANUAL AS NOTED ON THE ORIGINAL
 PLANS ON FILE IN CITY RECORDS. THIS UNIT WAS DESIGNED
 AS A SPECIFICATION "A" TYPE BATHROOM.
 THE FAIR HOUSING ACT DESIGN MANUAL REQUIRES A 30 INCH
 WIDE BY 48 INCH DEEP CLEAR FLOOR SPACE BE PROVIDED AT
 SHOWER STALLS, PARALLEL TO THE FIXTURE AND FLUSH WITH
 THE CONTROL WALL. NO OTHER FIXTURE MAY OVERLAP THE
 CLEAR FLOOR SPACE AT SHOWERS EXCEPT AS PROVIDED IN THE
 FAIR HOUSING ACT DESIGN MANUAL. THE EXISTING DESIGN
 DOES NOT MEET ANY OF THE EXCEPTIONS. THE FLOOR PLAN
 SHOWS A WATER CLOSET NEXT TO WHERE THE PROPOSED SHOWER
 WOULD BE AND THEREFORE WOULD CREATE A VIOLATION OF THE
 FAIR HOUSING ACT. THE SHOWER CANNOT BE INSTALLED IN
 LIEU OF THE BATHTUB.
 2) INDICATE ON THE PLAN IF THE KITCHEN SINK WILL NE
 REPLACED.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  