Plan Review Details - Permit 18071384
Plan Review Stops For Permit 18071384
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-10-26 Cont ID  
Sent By rmcdouga Date 2018-10-26 Time 16:18 Rev Time 0.00
Received By rmcdouga Date 2018-10-26 Time 15:18 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-29 Cont ID  
Sent By rmcdouga Date 2018-08-29 Time 18:42 Rev Time 0.00
Received By rmcdouga Date 2018-08-29 Time 10:44 Sent To B
Notes
2018-08-29 15:04:15PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHEET ID-1.3 OF THE PLANS REFERENCES TO THE 2014 FBC
 UNDER GENERAL NOTES. UNDER THE BUILDING CODE IN EFFECT
 SECTION THE FIFTH EDITION IS SPECIFIED FOR THE 2017 FBC
 AND IT SHOULD BE THE SIXTH EDITION. THE FBC SIXTH
 EDITION (2017) WENT INTO EFFECT ON JANUARY 1, 2018. ALL
 NEW PERMITS APPLIED FOR ON OR AFTER THAT DATE ARE
 REQUIRED TO COMPLY WITH AND REFERENCE THE FBC SIXTH
 EDITION (2017).
 FS CHAPTER 553
  
 2) SPECIFY THE FOLLOWING DESIGN CRITERIA: 1) TYPE OF
 CONSTRUCTION, 2) OCCUPANCY TYPE 3) FIRE SPRINKLERED, 4)
 WIND SPEED AND 5) EXPOSURE CATEGORY FBC 107.2.1
  
 3) IT DOES NOT APPEAR THAT THE KITCHEN AREA WOULD BE
 REQUIRED TO HAVE ONE HOUR FIRE RATED WALLS AND
 CEILINGS. PLEASE EXPLAIN. FBC 107.2.1
  
 4) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-10-03 Cont ID  
Sent By jpearson Date 2018-10-03 Time 09:27 Rev Time 0.00
Received By jpearson Date 2018-10-03 Time 09:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-20 Cont ID  
Sent By jpearson Date 2018-08-20 Time 14:41 Rev Time 0.00
Received By jpearson Date 2018-08-20 Time 14:41 Sent To  
Notes
2018-08-20 14:41:43CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 2. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC EC C405.2
 3. PROVIDE LOAD CALCULATION FOR PANEL AC, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-09-26 Cont ID  
Sent By scaldero Date 2018-09-26 Time 10:40 Rev Time 0.00
Received By scaldero Date 2018-09-26 Time 10:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-08-06 Cont ID  
Sent By scaldero Date 2018-08-06 Time 12:07 Rev Time 0.00
Received By scaldero Date 2018-08-06 Time 11:55 Sent To  
Notes
2018-08-06 12:07:24PERMIT # 18071384
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 2) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 3) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 4) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE HOOD SUPPRESSION
 SYSTEM.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-10-16 Cont ID  
Sent By jesmith Date 2018-10-16 Time 14:54 Rev Time 0.00
Received By jesmith Date 2018-10-16 Time 14:53 Sent To  
Notes
2018-10-16 14:53:542ND REVIEW:
 GAS COMMENTS: APPROVED
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-08-28 Cont ID  
Sent By gjohnson Date 2018-08-28 Time 18:02 Rev Time 0.00
Received By gjohnson Date 2018-08-28 Time 18:02 Sent To  
Notes
2018-08-28 18:02:571ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GAS COMMENTS:
 1. OUR RECORDS SHOW THAT THERE IS EXITING LP GAS TANK
 PROVIDING GAS FOR THE KITCHEN WITH A TOTAL BTU LOAD OF
 500,000 UNDER PERMIT #05090527 IT LIST NATURAL GAS ON
 THE NEW PLANS PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
 2. PLEASE SHOW THE EXISTING BTU LOAD ON THE PLAN THE
 PIPING FROM THE LP TANK TO THE BRANCH FOR THE NEW LOAD
 BE NEED TO BE RESIZED. PER FBC FG 402.4
 3. SHOW EXITING PIPING ON RISER WITH SIZE BACK TO THE
 LP TANK. PER WPB AMEND TO FBC 107.2.1
 4. THE TOTAL BTU LOAD SHOWN ON THE RISER ADDS UP TO
 493,000 BTU THE TOTAL LOAD LISTED ON SIZING TABLE NOTES
 IS 547,000 BTU PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR
 2017 FBC-RES. SEC. G 2407.1 AND G2439.4 (.
 6. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT AND
 REGULATORS TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1.
 7. THE DISTANCE ON YOUR .5LB SYSTEM IS LISTED AS 106?
 PER FBC FG (1) THE PIPING SHALL BE 2? PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-11-19 Time   Rev Time 0.00
Received By lmarchan Date 2018-11-07 Time 13:53 Sent To  
Notes
2018-11-08 13:54:05RESUB ROUTED TO JESMITH

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-26 Cont ID  
Sent By rmcdouga Date 2018-10-26 Time 16:18 Rev Time 0.00
Received By rmcdouga Date 2018-09-21 Time 11:29 Sent To  
Notes
2018-09-25 11:29:29B20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-29 Cont ID  
Sent By rmcdouga Date 2018-08-29 Time 18:42 Rev Time 0.00
Received By rmcdouga Date 2018-07-30 Time 15:48 Sent To  
Notes
2018-07-31 15:48:59B22

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-08-29 Cont ID  
Sent By rmcdouga Date 2018-08-29 Time 11:33 Rev Time 0.00
Received By rmcdouga Date 2018-08-29 Time 11:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-11-19 Cont ID  
Sent By ccole Date 2018-11-19 Time 08:14 Rev Time 0.00
Received By ccole Date 2018-11-19 Time 07:48 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-10-11 Cont ID  
Sent By ccole Date 2018-10-11 Time 09:06 Rev Time 0.00
Received By ccole Date 2018-10-11 Time 07:27 Sent To  
Notes
2018-10-11 09:24:092ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18071384
 10/12/18
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMMENTS #3- 7 FROM THE 1ST REVIEW PRINTED BELOW
 HAVE NOT BEEN COMPLETETY ADDRESSED AND STILL EXIST.
  
 3) VERIFY COMPLIANCE WITH SECTION 508.1.1 FBC M- SEE
 BELOW.
  
 508.1.1 MAKEUP AIR TEMPERATURE.
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10
 DEGREES F (6 DEGREES C) EXCEPT WHERE THE ADDED HEATING
 AND COOLING LOADS OF THE MAKEUP AIR DO NOT EXCEED THE
 CAPACITY OF THE HVAC SYSTEM.
  
 (IN RESPONSE TO COMMENT #3 THE ENGINEER STATES IN HIS
 RESPONSE THAT THE MAKEUP AIR IS LOCATED IN THE HOOD,
 HOWEVER THIS IN NOT THE CASE AS THE MAKEUP AIR IS
 DELIVERED VIA AN AIR CURTAIN AT THE FRONT FACE OF THE
 HOOD. PLEASE CONSULT WITH CAPTIVEAIRE FOR THE
 PERCENTAGE OF AIR THAT IS DIFFUSED INTO THE SPACE AND
 HOW THAT HOT AIR IS BEING COOLED TO WITHIN 10 DEGREES
 OF THE TEMPERATURE IN THE KITCHEN).
  
 4) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEM- SECTION C403.2.1 FBC EC. PLEASE NOTE THAT IF
 THE SYSTEM WILL BE USED TO SHOW COMPLIANCE WITH COMMENT
 #3 ABOVE, THEN THE CALCS SHOULD SPECIFICALLY ADDRESS
 THE HEAT LOAD IN BTUH GAINED FROM THE PERCENTAGE OF
 UNCONDITIONED MAKE UP AIR THAT IS NOT EXHAUSTED BY THE
 HOOD.
  
 ( NO AC CALCULATIONS WERE SUBMITTED. PLEASE NOTE THAT
 THE CALCULATIONS SHALL INDICATE THE HEAT LOADS FOR
 COOKING APPLIANCES, AND ANY OF THE LOAD FROM THE MAKEUP
 AIR FOR THE HOOD THAT MAY BE IMPACTING THE KITCHEN
 SPACE).
  
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL
 GAS-FIRED COOKING APPLIANCES- SECTION 623.1 FBC FG.
  
 (NOT SUBMITTED).
  
 6) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 GAS-FIRED COOKING APPLIANCES AND INDICATE HOW THE AIR
 IS BEING PROVIDED- SECTION 304.1 FBC FG.
  
 (NOT PROVIDED).
  
 7) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 THE EXTERIOR CONDENSER- SECTION 301.15 FBC M.
  
 (NOT PROVIDED).
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-08-23 Cont ID  
Sent By ccole Date 2018-08-23 Time 10:23 Rev Time 0.00
Received By ccole Date 2018-08-23 Time 10:11 Sent To  
Notes
2018-08-23 11:04:431ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18071384
 8/23/18
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ADVISORY: THE CITY OF WEST PALM BEACH BUILDING
 DEPARTMENT REQUIRES SEPARATE PERMITS FOR KITCHEN
 EXHAUST HOODS AND FIRE SUPPRESSION SYSTEMS- SEE SECTION
 107.2.1 WPB AMENDMENTS TO THE FBC HOWEVER COMMENTS #2 &
 3 BELOW PERTAINING TO THE HOOD SHOULD BE ADDRESSED NOW
 TO AVOID CONFLICTS LATER WITH THE HOOD PERMIT.
  
 2) THE LOCATION OF THE KEF EXHAUST FAN DOES NOT APPEAR
 TO BE IN COMPLIANCE WITH SECTIONS 506.3.13.2 AND
 506.3.13.3 FBC M. PLEASE REVIEW THE CODE SECTIONS BELOW
 AND VERIFY COMPLIANCE OR RELOCATE THE TERMINATION.
  
 506.3.13.2 TERMINATION THROUGH AN EXTERIOR WALL.
 EXHAUST OUTLETS SHALL BE PERMITTED TO TERMINATE THROUGH
 EXTERIOR WALLS WHERE THE SMOKE, GREASE, GASES, VAPORS
 AND ODORS IN THE DISCHARGE FROM SUCH TERMINATIONS DO
 NOT CREATE A PUBLIC NUISANCE OR A FIRE HAZARD. SUCH
 TERMINATIONS SHALL NOT BE LOCATED WHERE PROTECTED
 OPENINGS ARE REQUIRED BY THE FLORIDA BUILDING CODE,
 BUILDING. OTHER EXTERIOR OPENINGS SHALL NOT BE LOCATED
 WITHIN 3 FEET (914 MM) OF SUCH TERMINATIONS.
  
 506.3.13.3 TERMINATION LOCATION.
 EXHAUST OUTLETS SHALL BE LOCATED NOT LESS THAN 10 FEET
 (3048 MM) HORIZONTALLY FROM PARTS OF THE SAME OR
 CONTIGUOUS BUILDINGS, ADJACENT BUILDINGS AND ADJACENT
 PROPERTY LINES AND SHALL BE LOCATED NOT LESS THAN 10
 FEET (3048 MM) ABOVE THE ADJOINING GRADE LEVEL. EXHAUST
 OUTLETS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048
 MM) HORIZONTALLY FROM OR NOT LESS THAN 3 FEET (914 MM)
 ABOVE AIR INTAKE OPENINGS INTO ANY BUILDING.
  
 3) VERIFY COMPLIANCE WITH SECTION 508.1.1 FBC M- SEE
 BELOW.
  
 508.1.1 MAKEUP AIR TEMPERATURE.
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10
 DEGREES F (6 DEGREES C) EXCEPT WHERE THE ADDED HEATING
 AND COOLING LOADS OF THE MAKEUP AIR DO NOT EXCEED THE
 CAPACITY OF THE HVAC SYSTEM.
  
 4) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEM- SECTION C403.2.1 FBC EC. PLEASE NOTE THAT IF
 THE SYSTEM WILL BE USED TO SHOW COMPLIQNCE WITH COMMENT
 #3 ABOVE, THEN THE CALCS SHOULD SPECIFICALLY ADDRESS
 THE HEAT LOAD IN BTUH GAINED FROM THE PERCENTAGE OF
 UNCONDITIONED MAKE UP AIR THAT IS NOT EXHAUSTED BY THE
 HOOD.
  
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL
 GAS-FIRED COOKING APPLIANCES- SECTION 623.1 FBC FG.
  
 6) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 GAS-FIRED COOKING APPLIANCES AND INDICATE HOW THE AIR
 IS BEING PROVIDED- SECTION 304.1 FBC FG.
  
 7) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 THE EXTERIOR CONDENSER- SECTION 301.15 FBC M.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-11-08 Cont ID  
Sent By jesmith Date 2018-11-08 Time 14:23 Rev Time 0.00
Received By jesmith Date 2018-11-08 Time 14:22 Sent To  
Notes
2018-11-08 14:23:35APPROVED
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-10-16 Cont ID  
Sent By jesmith Date 2018-10-16 Time 14:13 Rev Time 0.00
Received By jesmith Date 2018-10-16 Time 14:12 Sent To  
Notes
2018-10-16 14:13:15CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 2ND REVIEW:
 PLUMBING COMMENTS: DENIED
  
 1. RE: PLAN SHEET P-1; PLAN SHOWS CONNECTION OF NEW 3"
 KITCHEN GREASY WASTE TO AN EXISTING 4" GREASY WASTE
 BUILDING DRAIN WHICH IS CONNECTED TO AN EXISTING 2000
 GALLON GREASE INTERCEPTOR. WHERE IS 4" GREASY WASTE
 COMING FROM? PROVIDE SIZING CALCULATIONS FOR EXISTING
 FACILITY AS WELL AS SIZING CALCULATIONS FOR NEW WORK TO
 DETERMINE THAT THE INTERCEPTOR IS SIZED TO ACCOMMODATE
 ALL PER WPB FBC 107.2.1.
 2. RE: PLAN SHEET P-2; SANITARY ISOMETRIC SHOWS A
 COMMON INDIRECT WASTE FROM TWO (2) ITEM #20 HOT FOOD
 WELLS TO THE FLOOR SINK. PROVIDE INDEPENDENT INDIRECT
 WASTE FOR EACH WELL IN ACCORDANCE WITH 802.1.1 .
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-08-28 Cont ID  
Sent By gjohnson Date 2018-08-28 Time 18:03 Rev Time 0.00
Received By gjohnson Date 2018-08-28 Time 18:03 Sent To  
Notes
2018-08-28 18:10:101ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE SANITARY AND WATER ISOMETRIC. PER WPB AMEND
 TO FBC 107.3.5.1.3(13)
 2. I THE PLUMBING FIXTURES ARE OVER 50' FROM HOT WATER
 SOURCE A RECIRCULATION SYSTEM IS REQUIRED. PER FBC PL
 607.2
 3. PROVIDE SIZING CALCULATIONS FOR GREASE INTERCEPTOR
 FROM MANUFACTURE SCHIER PROVIDES THEM ON THEIR WEB
 SITE. PER WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  