Plan Review Details - Permit 18071331
Plan Review Stops For Permit 18071331
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-04-25 Cont ID  
Sent By dbattles Date 2019-04-25 Time 16:04 Rev Time 0.00
Received By dbattles Date 2019-04-25 Time 16:04 Sent To  
Notes
2019-06-07 15:26:29PROVIDE COPY OF REVISED S1 SHEET FOR THE SECOND SET.
  
 THANK YOU,
 DYLAN BATTLES
 561-805-6718
 [email protected]
  
 THE CITY OF WEST PALM BEACH
 BUILDING PLANS EXAMINER PX4191
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-09-12 Cont ID  
Sent By dbattles Date 2018-09-12 Time 09:55 Rev Time 0.00
Received By dbattles Date 2018-09-12 Time 09:55 Sent To  
Notes
2018-09-12 09:57:06****CORRECTIONS****
 W.P.B. PERMIT: 18071331
 REVIEWED: SEPTEMBER 11, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC A = AMENDMENTS TO THE FLORIDA BUILDING CODE,6TH
 EDITION (2017)
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC AMENDED 109]PLEASE HAVE ENGINEER PROVIDE COST
 ESTIMATE BASED ON THE WORK AS IF IT WERE BEING
 PERFORMED BY A GENERAL CONTRACTOR. EVEN THOUGH YOU ARE
 OWNER/BUILDER THE BUILDING DEPARTMENT FEES ARE
 GENERATED BY INDUSTRY COST FOR SIMILAR WORK. IF COST
 ESTIMATE CANNOT BE PROVIDED WE WILL ADJUST THE VALUE
 BASED ON THE SQUARE FOOTAGE ADDED.
  
 2. [FBC R318]INDICATE THE MEANS OF TERMITE PROTECTION
 PROPOSED AND HOW IT WILL BE ACCOMPLISHED WITH AN
 EXISTING SLAB.
  
 A) [FBC A107.2.6]THE EXTISTING FOOTING WASN?T DESIGNED
 TO HOLD A MASONRY WALL AND ROOF ABOVE. PLEASE PROVIDE
 FOOTER THAT WILL MEET CODES BELOW.
 [FBC R403.1.4]MINIMUM DEPTH.
 EXTERIOR FOOTINGS SHALL BE PLACED NOT LESS THAN 12
 INCHES (305 MM) BELOW THE UNDISTURBED GROUND SURFACE.
 WHERE APPLICABLE, THE DEPTH OF FOOTINGS SHALL ALSO
 CONFORM TO SECTIONS R403.1.4.1 THROUGH R403.1.4.2.
  
 B) [FBC R404.1.6]CONCRETE AND MASONRY FOUNDATION WALLS
 SHALL EXTEND ABOVE THE FINISHED GRADE ADJACENT TO THE
 FOUNDATION AT ALL POINTS A MINIMUM OF 4 INCHES (102 MM)
 WHERE MASONRY VENEER IS USED AND A MINIMUM OF 6 INCHES
 (152 MM) ELSEWHERE.
  
 3. [FBC 2121.1.6]MINIMUM NO. 9 GAUGE TRUSS-TYPE
 HORIZONTAL JOINT REINFORCING AT EVERY ALTERNATE COURSE
 (16-INCH (406 MM) SPACING], SHALL BE PROVIDED. THIS
 REINFORCEMENT SHALL EXTEND 4 INCHES (102 MM) INTO TIE
 COLUMNS OR BE TIED TO STRUCTURAL COLUMNS WITH APPROVED
 METHODS WHERE STRUCTURAL COLUMNS REPLACE THE TIE
 COLUMNS. IN ADDITION, HORIZONTAL JOINT REINFORCEMENT
 SHALL COMPLY WITH TMS602/ACI530.1/ASCE 6 SECTIONS 2.4C
 THRU 2.4F AND SECTION 3.4B.7.
  
 4. FBC R301.4]&[FBC R301.5]PROVIDE DEAD LOAD AND LIVE
 LOAD FROM EXISTING ROOF.
 [FBC R806]ARE VENTS BEING REMOVED FROM THE OVERHANG?
 PROVIDE HOW VENTING IS BEING SUPPLIED AND IF EXISTING
 VENTS COVER THE WHOLE ATTIC SPACE.
  
 5. [FBC ENERGY R502]WHAT IS EXISTING CEILING MATERIAL
 AS IT IS CURRENTLY EXTERIOR PATIO?
 HOW WILL R-30 BE INSTALLED IN EXISTING CEILING IF ROOF
 AND CEILING ARE NOT BEING REPLACED.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-05-02 Cont ID  
Sent By ppetty Date 2019-05-02 Time 10:58 Rev Time 0.00
Received By ppetty Date 2019-05-02 Time 10:58 Sent To  
Notes
2019-05-02 10:58:44CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. AFCI PROTECTION SHOWN IN NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
 3. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1
 4. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
 5. A MINIMUM OF TWO 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY KITCHEN COUNTERTOP RECEPTACLE
 OUTLET(S). PROVIDE CORRECTION. NEC 210.11(C)(1) , FBC
 RE E3703.2
 6. OK
 7. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-28 Cont ID  
Sent By jpearson Date 2018-08-28 Time 13:23 Rev Time 0.00
Received By jpearson Date 2018-08-28 Time 13:22 Sent To  
Notes
2018-08-28 13:22:56CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. AFCI PROTECTION SHOWN IN NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
 3. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1
 4. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
 5. A MINIMUM OF TWO 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY KITCHEN COUNTERTOP RECEPTACLE
 OUTLET(S). PROVIDE CORRECTION. NEC 210.11(C)(1) , FBC
 RE E3703.2
 6. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
 7. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-04-29 Cont ID  
Sent By thunt Date 2019-04-29 Time 13:28 Rev Time 0.00
Received By thunt Date 2019-04-29 Time 13:28 Sent To  
Notes
2019-04-29 13:28:15GAS 2ND REVIEW**DENIED**THESE ARE THE SAME COMMENTS
 FROM PERMIT#19010365. PLEASE NOTE FL ST 553.80 (B)2B
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
 IT IS RECOMMENDED FOR YOU TO COME IN AND MEET WITH THE
 PLAN REVIEW STAFF BEFORE RESUBMITTING.
  
 NOTE:THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
  
 1) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE. GAS RANGE IS NOT
 SHOWING ON GAS ISOMETRIC DRAWING BUT SHOWS AS BEING
 RELOCATED. FBC-RES SEC. G2413.4.1, G2413.4.2.
  
 2) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE RANGE.
 WHERE COMBUSTION AIR IS PROVIDED BY THE BUILDING?S
 MECHANICAL VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE
 THE SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE
 REQUIRED VENTILATION AIR. 2017 FBCR G2407.9.3.
  
 3) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION.2017, FBC-RES. SEC.G2408.1
  
 4) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-RES. SEC. G 2407.1 AND G2439.4 (CLOTHES DRYERS)
  
 5) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.
  
 6) PLANS SUBMITTED ARE NOT SIGNED BY THE PERSON
 DESIGNING THE SYSTEM AS REQUIRED. FAC 471, 481
  
 7) VALUE OF JOB IS TOO LOW. $800.00 DOES NOT COVER THE
 COST OF THE DRYER AND TANKLESS WATER HEATER ALONE. COST
 MUST INCLUDE ALL MATERIAL AND LABOR. FOR OWNER BUILDER
 IT SHOULD BE VALUED AS IF WAS CONTRACTED OUT. 109.3
 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF THE
 BUILDING OFFICIAL, THE CLAIMED VALUATION OF BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR
 PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS THE
 APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR
 BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO
 MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-09-07 Cont ID  
Sent By gjohnson Date 2018-09-07 Time 12:53 Rev Time 0.00
Received By jesmith Date   Time   Sent To  
Notes
2018-09-07 12:54:19REVIEW COMPLETED BY JERALD SMITH 0017-P
  
 GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-06 Cont ID  
Sent By cpuell Date 2019-05-06 Time 16:00 Rev Time 0.00
Received By cpuell Date 2019-04-23 Time 14:33 Sent To  
Notes
2019-04-24 14:33:29R01

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-12 Cont ID  
Sent By dbattles Date 2018-09-12 Time 10:00 Rev Time 0.00
Received By dbattles Date 2018-07-27 Time 13:11 Sent To  
Notes
2018-07-30 13:11:43R02

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-09-12 Cont ID  
Sent By dbattles Date 2018-09-12 Time 09:57 Rev Time 0.00
Received By dbattles Date 2018-09-12 Time 09:57 Sent To  
Notes
2018-09-12 09:58:06[FBC AMENDED 109]PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-04-30 Cont ID  
Sent By cmontell Date 2019-04-30 Time 14:30 Rev Time 0.00
Received By cmontell Date 2019-04-30 Time 14:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-09-04 Cont ID  
Sent By cmontell Date 2018-09-04 Time 14:29 Rev Time 0.00
Received By cmontell Date 2018-09-04 Time 14:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-04-29 Cont ID  
Sent By thunt Date 2019-04-29 Time 13:44 Rev Time 0.00
Received By thunt Date 2019-04-29 Time 13:44 Sent To  
Notes
2019-04-29 13:45:27PLUMBING 2ND REVIEW**DENIED**
  
 1) ONLY 1 NEW SHT S1 WAS PROVIDE. 2 COPIES OF ALL PLANS
 ARE REQUIRED. FBC 107.1
  
 2) PLUMBING ISOMETRIC PLAN DOES NOT MATCH FLOOR PLAN
 LAY OUT OR 2ND ISOMETRIC DRAWING PROVIDED. PLEASE
 CLARIFY AND REMOVE ALL PAGES NOT PART OF THE REVIEW
 PROCESS. FBC 107.3.5
  
 3) SHT. S2 SHOWS GAS TANKLESS SHOWS INSIDE BUT SEPERATE
 SHEET FLAT DRAWING IS SHOWING IT OUTSIDE. PLEASE
 CLARIFY. FBC 107.2.1. PROVIDE DISTANCE FROM ALL DOORS
 AND WINDOWS.
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-09-06 Cont ID  
Sent By shill Date 2018-09-06 Time 11:38 Rev Time 0.00
Received By jesmith Date 2018-09-06 Time 11:34 Sent To  
Notes
2018-09-07 12:52:48REVIEW COMPLETED BY JERALD SMITH 0017-P
2018-09-06 11:38:351ST REVIEW: FBC 2017 6TH EDITION
 PERMIT 18071331
 PLUMBING COMMENTS: DENIED
  
 1. REGARDING SANITARY PLUMBING RISER ON PLAN SHEET S1:
 (A) WHAT DOES THE TERM 2" STACK NOTED ON DIAGRAM
 INDICATE? PLEASE CLARIFY.
 (B) AUTOMATIC CLOTHES WASHERS REQUIRE A FIXTURE TRAP
 PER 2017 FBC RES 3201.6 AND A VENT PER 2017 FBC RES
 3105.1. THIS IS NOTED ON A DETAIL ON PLAN SHEET S2 BUT
 MUST ALSO BE SHOWN ON THE SANITARY RISER DIAGRAM ON
 PLAN SHEET S1.
 (C) PLEASE COORDINATE WITH STRUCTURAL TO INSURE THAT
 STRUCTURAL INTEGRITY WILL NOT BE AFFECTED BY PIPING
 (REFER TO 1/4" SCALE "NEW FLOOR PLAN" ON PLAN SHEET
 S1).
  
 2. (A) THERE IS A GAS FIRED TANKLESS WATER HEATER AND A
 GAS DRYER NOTED ON PLAN SHEET S2. A GAS PLAN HAS NOT
 BEEN INCLUDED IN THIS SUBMITTAL PACKAGE. A GAS PLAN
 REVIEW HAS NOT BEEN PERFORMED AT THIS TIME. A SEPARATE
 GAS PERMIT AND PLANS WILL BE REQUIRED FOR A CONTRACTOR
 TO PERFORM THE RELATED WORK PER WPB AMEND. TO FBC SEC.
 105.1. PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1. GAS APPLIANCES SHALL BE LISTED AND LABELED PER
 THE 2017 FBC RES, SEC. G2404.3.
 (B) THE PLANS INDICATE AN EXISTING GAS RANGE. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 2017 FBC RES SECS.G2412.4, G2412.8, G2413.1, G2413.2,
 G2413.3.
 (C) A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711

Review Stop Z ZONING
Rev No 2 Status P Date 2019-05-06 Cont ID  
Sent By awooten Date 2019-05-06 Time   Rev Time 0.00
Received By awooten Date 2019-05-06 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-08-10 Cont ID  
Sent By awooten Date 2018-08-10 Time 14:45 Rev Time 0.00
Received By awooten Date 2018-08-10 Time 14:31 Sent To  
Notes
2018-08-10 14:45:21**********************************ZONING REVIEW
 FAILED******************************************
  
 PROVIDE A SURVEY/SITEPLAN SHOWING THE SETBACKS (BOTH
 CURRENT AND PROPOSED) FOR ENCLOSURE/RENOVATION.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  
  