Plan Review Details - Permit 18071320
Plan Review Stops For Permit 18071320
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-09-15 Cont ID  
Sent By shill Date 2018-09-15 Time 15:51 Rev Time 0.00
Received By shill Date 2018-09-15 Time 15:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-09-02 Cont ID  
Sent By shill Date 2018-09-02 Time 12:52 Rev Time 0.00
Received By shill Date 2018-09-02 Time 12:52 Sent To  
Notes
2018-09-02 12:52:18****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC 107, REVISION 5 CLOUDS ARE NOT ON THE PLAN. AS I
 DID NOT REVIEW THE ORIGINAL PLAN, I AM NOT FAMILIAR
 WITH THE PROJECT. I WILL REVIEW ONLY ITEMS WHICH
 CHANGED AND ARE CLEARLY INDICATED WITH CLOUDS AND A
 TRANSMITTAL LETTER AND WILL AVOID A NEW REVIEW OF
 PREVIOUSLY APPROVED ITEMS IF POSSIBLE.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-08-20 Cont ID  
Sent By jpearson Date 2018-08-20 Time 11:02 Rev Time 0.00
Received By jpearson Date 2018-08-20 Time 10:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-08-10 Cont ID  
Sent By pleduc Date 2018-08-10 Time   Rev Time 0.00
Received By pleduc Date 2018-08-09 Time 16:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-15 Cont ID  
Sent By shill Date 2018-09-15 Time 15:51 Rev Time 0.00
Received By shill Date 2018-09-15 Time 15:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-02 Cont ID  
Sent By shill Date 2018-09-02 Time 12:52 Rev Time 0.00
Received By shill Date 2018-07-27 Time 13:43 Sent To  
Notes
2018-07-30 13:43:48C34

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-08-22 Cont ID  
Sent By ccole Date 2018-08-22 Time 17:46 Rev Time 0.00
Received By ccole Date 2018-08-22 Time 17:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-08-28 Cont ID  
Sent By gjohnson Date 2018-08-28 Time 14:42 Rev Time 0.00
Received By gjohnson Date 2018-08-28 Time 14:42 Sent To  
Notes
2018-09-28 12:55:319/29/18 PROVISO COMPLIED CONTRACTOR SUBMITTED
 LETTERS/GPJ
2018-08-28 14:47:41APPROVED WITH PROVISO PROVIDE THE FOLLOWING BEFORE NEXT
 INSPECTION.
  
 I CAN APPROVE THE DELETION OF THE DECONTAMINATION
 HOLDING TANK UNDER THE FOLLOWING CONDITIONS:
 PROVIDE THE FOLLOWING DOCUMENTS:
  
 1) TWO ORIGINAL SIGNED AND SEALED COPIES OF A LETTER
 FROM THE DESIGN PROFESSIONAL OF RECORD FOR THIS PERMIT
 REQUESTING THE DELETION OF THE TANK SHALL BE SUBMITTED
 TO THE CITY OF WEST PALM BEACH BUILDING DEPARTMENT FOR
 REVIEW AND APPROVAL.
  
 2) TWO ORIGINAL SIGNED COPIES OF THE LETTER FROM
 GREGORY A. DALTON SHALL ALSO BE SUBMITTED WITH THE PLAN
 REVISION. PLEASE REVISE THE LETTER TO READ " FACILITY
 GUIDELINES INSTITUTE" IN LIEU OF THE ACRONYM "FGI".
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By llouie Date 2018-08-21 Time   Rev Time  
Received By   Date 2018-08-21 Time   Sent To  
Notes
2018-08-21 15:37:56SEPERATE PERMITS AND REVIEW REQUIRED FOR: LANDSCAPING
 AND SIGNAGE PRIOR TO CERTIFICATE OF OCCUPANCY (C.O.)