Plan Review Details - Permit 18071301
Plan Review Stops For Permit 18071301
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-12-26 Cont ID  
Sent By dbattles Date 2018-12-26 Time 12:58 Rev Time 0.00
Received By dbattles Date 2018-12-26 Time 12:44 Sent To  
Notes
2018-12-26 12:59:33PROVISO:
 OWNER TO SIGN ENERGY CALCULATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-12-03 Cont ID  
Sent By dbattles Date 2018-12-03 Time 15:04 Rev Time 0.00
Received By dbattles Date 2018-12-03 Time 15:04 Sent To  
Notes
2018-12-03 15:31:59****CORRECTIONS****
 W.P.B. PERMIT: 18071301
 REVIEWED: AUGUST 24, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FLOOD ZONE = X
  
 2ND REVIEW
 DECEMBER 03,2018
  
 1. [FBC R401.3]PROVIDE SITE DRAINAGE PLAN.
  
 2ND REVIEW - DRAINAGE PLAN HAS NOT BEEN SUBMITTED.
 IT SHOULD INCLUDE KEY ELEVATIONS SUCH AS BASE FLOOR
 ELEVATION (B.F.E.) SINCE GRADE NEEDS TO BE 4 INCHES
 BELOW SLAB YOU WOULD START DRAINAGE FROM FOUNDATION -4
 INCHES.
 OTHER KEY POINTS ARE 2% GRADE FROM BACK YARD TO STORM
 DRAIN AT STREET.
 PLEASE CALL IF ANY QUESTIONS ABOUT DRAINAGE PLAN.
  
 [FBC R403.1.7.3] FOUNDATION ELEVATION. ON GRADED SITES,
 THE TOP OF ANY EXTERIOR FOUNDATION SHALL EXTEND ABOVE
 THE ELEVATION OF THE STREET GUTTER AT POINT OF
 DISCHARGE OR THE INLET OF AN APPROVED DRAINAGE DEVICE A
 MINIMUM OF 12 INCHES (305 MM) PLUS 2 PERCENT. ALTERNATE
 ELEVATIONS ARE PERMITTED SUBJECT TO THE APPROVAL OF THE
 BUILDING OFFICIAL, PROVIDED IT CAN BE DEMONSTRATED THAT
 REQUIRED DRAINAGE TO THE POINT OF DISCHARGE AND AWAY
 FROM THE STRUCTURE IS PROVIDED AT ALL LOCATIONS ON THE
 SITE.
  
 [FBC AMENDED 107.2.5] 107.2.5 SITE PLAN. THE
 CONSTRUCTION DOCUMENTS SUBMITTED WITH THE APPLICATION
 FOR PERMIT SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING
 TO SCALE THE SIZE AND LOCATION OF NEW CONSTRUCTION AND
 EXISTING STRUCTURES ON THE SITE, DISTANCES FROM LOT
 LINES, THE ESTABLISHED STREET GRADES AND THE PROPOSED
 FINISHED GRADES, DEPICTING THE PROPOSED LOT DRAINAGE
 AND, AS APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND
 DESIGN FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN
 ACCORDANCE WITH AN ACCURATE AND INCLUDED ON A BOUNDARY
 LINE SURVEY.
  
 2. [FBC R401.4]PROVIDE SOIL REPORT TO SHOW BEARING
 CAPACITY AND FOUNDATION RECOMMENDATIONS.
  
 2ND REVIEW - SOIL REPORT NOT PROVIDED. ACCORDING TO
 SOIL MAP WE MAINTAIN AT BLDG. DEPT. YOUR SITE IS IN AN
 AREA THAT DOES REQUIRE SOIL REPORT.
 PLEASE PROVIDE SOIL REPORT WITH RE-SUBMITTAL.
  
 3. OK
  
 4. OK
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-24 Cont ID  
Sent By dbattles Date 2018-08-24 Time 13:19 Rev Time 0.00
Received By dbattles Date 2018-08-24 Time 09:02 Sent To  
Notes
2018-08-24 13:21:01****CORRECTIONS****
 W.P.B. PERMIT: 18071301
 REVIEWED: AUGUST 24, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FLOOD ZONE = X
  
 1. [FBC R401.3]PROVIDE SITE DRAINAGE PLAN.
  
 [FBC R403.1.7.3] FOUNDATION ELEVATION. ON GRADED SITES,
 THE TOP OF ANY EXTERIOR FOUNDATION SHALL EXTEND ABOVE
 THE ELEVATION OF THE STREET GUTTER AT POINT OF
 DISCHARGE OR THE INLET OF AN APPROVED DRAINAGE DEVICE A
 MINIMUM OF 12 INCHES (305 MM) PLUS 2 PERCENT. ALTERNATE
 ELEVATIONS ARE PERMITTED SUBJECT TO THE APPROVAL OF THE
 BUILDING OFFICIAL, PROVIDED IT CAN BE DEMONSTRATED THAT
 REQUIRED DRAINAGE TO THE POINT OF DISCHARGE AND AWAY
 FROM THE STRUCTURE IS PROVIDED AT ALL LOCATIONS ON THE
 SITE.
  
 [FBC AMENDED 107.2.5] 107.2.5 SITE PLAN. THE
 CONSTRUCTION DOCUMENTS SUBMITTED WITH THE APPLICATION
 FOR PERMIT SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING
 TO SCALE THE SIZE AND LOCATION OF NEW CONSTRUCTION AND
 EXISTING STRUCTURES ON THE SITE, DISTANCES FROM LOT
 LINES, THE ESTABLISHED STREET GRADES AND THE PROPOSED
 FINISHED GRADES, DEPICTING THE PROPOSED LOT DRAINAGE
 AND, AS APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND
 DESIGN FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN
 ACCORDANCE WITH AN ACCURATE AND INCLUDED ON A BOUNDARY
 LINE SURVEY.
  
 2. [FBC R401.4]PROVIDE SOIL REPORT TO SHOW BEARING
 CAPACITY AND FOUNDATION RECOMMENDATIONS.
  
 3. [FBC AMENDED 107.3.4.1]SUBMIT TRUSS SHOP DRAWINGS,
 OR INDICATE THAT THE SUBMITTAL WILL BE DEFERRED.
 DEFERRED SUBMITTALS TO BE REVIEWED PRIOR TO
 INSTALLATION.
  
 4. [FBC TABLE R301.2(4)]THE ELEVATION FOR GARAGE DOOR
 ON 2-4 SHOWS PRESSURES OF +37.08/-50.61. THIS EXCEEDS
 THE ALLOWED PRESSURE IN PRODUCT APPROVAL. HOWEVER, IF
 YOU USE TABLE R301.2(4)THE GARAGE DOOR PRESSURE CAN BE
 ADJUSTED AND WILL MEET THE DESIGN PRESSURE IN NOA
 17-1010.16.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-11-29 Cont ID  
Sent By jpearson Date 2018-11-29 Time 10:02 Rev Time 0.00
Received By jpearson Date 2018-11-29 Time 09:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-17 Cont ID  
Sent By jpearson Date 2018-08-17 Time 16:04 Rev Time 0.00
Received By jpearson Date 2018-08-17 Time 16:04 Sent To  
Notes
2018-08-17 16:03:57CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. AFCI PROTECTION SHOWN IN NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902
 2. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9; FBC RE E3603.3
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3603.3
 4. LOAD CALCULATION ONLY SHOWS ONE SMALL APPLIANCE
 CIRCUIT INCLUDED IN CALCULATION, THERE MUST BE A
 MINIMUM OF TWO AND EACH LISTED IN PANEL SCHEDULE SHOULD
 BE INCLUDED. PROVIDE CORRECTION. NEC 215.2, 220,
 408.30; FBC RE E3602.2
 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 6. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE
 OUTLETS IN GARAGE, INCLUDING GARAGE DOOR OPENER.
 PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-01-11 Cont ID  
Sent By dbattles Date 2019-01-11 Time 16:58 Rev Time 0.00
Received By dbattles Date 2019-01-10 Time 09:42 Sent To  
Notes
2019-01-11 09:42:47ROUTED TO DBATTLES

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-01-07 Cont ID  
Sent By cpuell Date 2019-01-07 Time 11:01 Rev Time 0.00
Received By cpuell Date 2018-12-19 Time 13:35 Sent To  
Notes
2018-12-20 13:35:50R21

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-11 Cont ID  
Sent By jesmith Date 2018-12-11 Time 14:25 Rev Time 0.00
Received By jesmith Date 2018-12-11 Time 14:25 Sent To  
Notes
2018-12-08 10:40:0612/8 REMOVED FROM BOARD, TO JESMITH DESK
  
  
2018-11-07 15:28:50R05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-04 Cont ID  
Sent By shill Date 2018-09-04 Time 10:38 Rev Time 0.00
Received By shill Date 2018-07-27 Time 11:46 Sent To  
Notes
2018-07-30 11:46:37R28

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-01-11 Cont ID  
Sent By dbattles Date 2019-01-11 Time 16:57 Rev Time 0.00
Received By dbattles Date 2019-01-11 Time 16:57 Sent To  
Notes
2019-01-11 16:58:20STAMP ON PLANS - OK
 MU-2019-000852-0000

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-08-24 Cont ID  
Sent By dbattles Date 2018-08-24 Time 09:10 Rev Time 0.00
Received By dbattles Date 2018-08-24 Time 09:10 Sent To  
Notes
2018-12-26 13:01:53UPON ZONING REVIEW CHECK OUT ONE SET OF PLANS TO TAKE
 TO PBC IMPACT REVIEW.
 RETURN THE SET WITH STAMP ON PLANS.
 PROVIDE A COPY OF RECEIPT TO SHOW MU NUMBER.
  
2018-08-24 09:13:02[FBC AMENDED 109]PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-12-21 Cont ID  
Sent By cmontell Date 2018-12-21 Time 14:37 Rev Time 0.00
Received By cmontell Date 2018-12-21 Time 14:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-08-08 Cont ID  
Sent By cmontell Date 2018-08-08 Time 14:23 Rev Time 0.00
Received By cmontell Date 2018-08-08 Time 14:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-12-11 Cont ID  
Sent By jesmith Date 2018-12-11 Time 14:24 Rev Time 0.00
Received By jesmith Date 2018-12-11 Time 14:23 Sent To  
Notes
2018-12-11 14:24:23APPROVED
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-09-04 Cont ID  
Sent By shill Date 2018-09-04 Time 10:37 Rev Time 0.00
Received By jesmith Date 2018-09-04 Time 10:36 Sent To  
Notes
2018-09-07 12:32:20REVIEW COMPLETED BY JERALD SMITH 0017-P
2018-09-04 10:36:531ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS: DENIED
  
 1. EACH WET VENTED FIXTURE DRAIN SHALL CONNECT
 INDEPENDENTLY TO THE HORIZONTAL WET VENT PER FBC RES
 P3108.1. THE TUB AND THE SHOWER FIXTURE DRAINS IN
 BATHROOMS ARE CONNECTED TO WATER CLOSET FIXTURE DRAIN;
 THE RESULTING FIXTURE BRANCH IS CONNECTED TO THE WET
 VENT; THIS IS NOT ACCEPTABLE.
  
 2. WATER HEATER IS ON RAISED FLOOR AT SAME ELEVATION AS
 LIVING AREA ADJACENT TO LIVING AREA FLOOR. IF STORAGE
 TYPE THEN PROVIDE PAN PER FBC RES 2801.6.
  
 3. ADDITIONAL INFO/DATA REQUIRED FOR WATER HEATER (FBC
 107.2.1) TO INCLUDE TYPE AND CAPACITY; WATER HEATER
 SHALL COMPLY WITH ENERGY CODE.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2018-08-24 Cont ID  
Sent By dbattles Date 2018-08-24 Time 13:18 Rev Time 0.00
Received By dbattles Date 2018-08-24 Time 13:18 Sent To  
Notes
2018-08-24 13:18:58SHINGLE ROOF PRODUCT APPROVAL OK FOR 5:12 PITCH.

Review Stop Z ZONING
Rev No 3 Status N Date 2019-01-04 Cont ID  
Sent By awooten Date 2019-01-04 Time 15:02 Rev Time 0.00
Received By awooten Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By awotten Date 2018-12-06 Time   Rev Time 0.00
Received By   Date 2018-12-06 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2018-08-13 Time   Rev Time  
Received By   Date 2018-08-13 Time   Sent To  
Notes
2018-08-13 14:33:46**************************************ZONING REVIEW FAI
 LED****************************************************
  
 PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT. SHOWING THE FOLLOWING:
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 O GROSS LOT SQUARE FOOTAGE MINUS
 O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
  
 PROPOSED DRIVEWAY REQUIRES A SEPARATE PERMIT.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVSION
 561-822-1449
 [email protected]
  