Plan Review Details - Permit 18071182
Plan Review Stops For Permit 18071182
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-10-24 Cont ID  
Sent By rmcdouga Date 2018-10-24 Time 19:06 Rev Time 0.00
Received By rmcdouga Date 2018-10-24 Time 18:26 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-10-22 Cont ID  
Sent By pvalenti Date 2018-10-22 Time 16:10 Rev Time 0.00
Received By pvalenti Date 2018-10-22 Time 16:09 Sent To  
Notes
2018-10-22 17:01:49****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 THE COMMENTS FROM THE LAST REVIEW HAVE NOT BEEN
 COMPLETELY ADDRESSED.
 PLEASE REVIEW LAST PACKAGE OF SUBMITTED PLANS AND
 SPECIFICATIONS INCLUDING THE FOLLOWING COMMENTS LISTED
 BELOW, ADDRESS THE COMMENTS AND RESUBMIT.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING
 DATA SHALL BEAR THE NAME OF THE PERSON RESPONSIBLE FOR
 THE DESIGN. THERE ARE SEVERAL SIGNATURES FROM DIFFERENT
 INDIVIDUALS ON THE SUBMITTED PLAN INFORMATION. THESE
 SUBMITTED PLANS AND SPECIFICATIONS NEED TO BE SIGNED
 AND SEALED BY THE DESIGN PROFESSIONAL OF RECORD.
  
 FBC 603.1 FLAME SPREAD FOR THE UNDERLAYMENT INSTALLED
 WITH THE WOOD FLOORING STILL NEEDS TO BE TESTED PER
 SECTION 603.1. THE TEST PROCEDURE THAT WAS SUBMITTED
 WAS TESTED PER SECTION 804.3.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-10-01 Cont ID  
Sent By rmcdouga Date 2018-10-01 Time 15:58 Rev Time 0.00
Received By rmcdouga Date 2018-10-01 Time 11:43 Sent To I
Notes
2018-10-01 15:57:58PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PERSON THAT SIGNED THE PLANS IS AND ENGINEER.
 FLORIDA STATUTES 471 AND FAC 61G15 - 23.003 REQUIRE
 PLANS FROM AN ENGINEER TO BE SIGNED, SEALED AND DATED
 BY THE ENGINEER. FBC 107.2.1 - INFORMATION ON
 CONSTRUCTION DOCUMENTS. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
 2) COMPLIED. THE PLANS THAT WERE SUBMITTED SHOW WOOD
 FRAMING AT THE DOOR OPENINGS. TYPE I AND II
 CONSTRUCTION REQUIRES NONCOMBUSTIBLE MATERIALS FOR THIS
 APPICATION. FBC 603.1 ALLOWS FIRE-RETARDANT-TREATED
 WOOD IN NONBEARING PARTITIONS WHERE THE FIRE-RESISTANCE
 RATING IS 2 HOURS OR LESS. SPECIFY ON THE PLANS THAT
 THE WOOD STUDS AT THE DOOR OPENINGS WILL BE
 FIRE-RETARDANT-TREATED WOOD (FRTW).
  
 3) PARTICAL COMPLIANCE. STILL NEED THE SMOKE AND FLAME
 SPREAD TEST REPORTS FOR THE WHISPER MAT SOUND
 UNDERLAYMENT. ASTM E 84-09
 PROVIDE THE FOLLOWING INFORMATION FOR FLOORING
 SUBMITTALS:
  
 1. FLOOR PLAN WITH DIMENSIONS AND LOCATION OF WORK.
 > DESIGNER TO PRINT NAME AND SIGN PLAN PER FBC 107.
 2. TOTAL SQUARE FOOTAGE OF NEW FLOORING.
 3. TYPE OF PROPOSED HARD FLOORING (TILE, LAMINATE,
 WOOD, MARBLE, ETC.).
 4. STATED VALUE OF WORK.
 5. DESCRIPTION OF EXISTING SITE CONDITIONS:
 (A) THICKNESS OF SLAB (B) FLOOR/CEILING ASSEMBLY BELOW
 (EXPOSED CONCRETE, SUSPENDED GYPSUM OR ACOUSTICAL ).
 6. PROPOSED UNDERLAYMENT.
 7. TEST REPORTS FOR THE PROPOSED UNDERLAYMENT BASED ON
 THE EXISTING SITE CONDITIONS.
 8. TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM'S:
 E-84, E-90 & E-492.
 9. ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE.
  
 FBC 603.1 FLAME SPREAD - ASTM E 84-09
  
 FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
  
 SUBMIT TWO COPIES OF THE TEST REPORTS FOR THE SOUND
 INSULATION INCLUDING FLAME SPREAD AND SMOKE DEVELOPED
 FOR THE APPLICABLE CONSTRUCTION CONDITIONS.
  
  
 FBC 603 COMBUSTIBLE MATERIAL IN TYPE I AND II
 CONSTRUCTION
 603.1 ALLOWABLE MATERIALS.
 COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS
 OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING
 APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1
 THROUGH 603.1.3:
 2. THERMAL AND ACOUSTICAL INSULATION, OTHER THAN FOAM
 PLASTICS, HAVING A FLAME SPREAD INDEX OF NOT MORE THAN
 25.
 EXCEPTIONS:
 1. INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND
 SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 200.
  
 3. FOAM PLASTICS IN ACCORDANCE WITH CHAPTER 26.
  
  
 FBC 2603 FOAM PLASTIC INSULATION
 2603.3 SURFACE-BURNING CHARACTERISTICS.
 UNLESS OTHERWISE INDICATED IN THIS SECTION, FOAM
 PLASTIC INSULATION AND FOAM PLASTIC CORES OF
 MANUFACTURED ASSEMBLIES SHALL HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 75 AND A SMOKE-DEVELOPED INDEX OF NOT
 MORE THAN 450 WHERE TESTED IN THE MAXIMUM THICKNESS
 INTENDED FOR USE IN ACCORDANCE WITH ASTM E 84 OR UL
 723. LOOSE FILL-TYPE FOAM PLASTIC INSULATION SHALL BE
 TESTED AS BOARD STOCK FOR THE FLAME SPREAD AND
 SMOKE-DEVELOPED INDEXES.
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-21 Cont ID  
Sent By rmcdouga Date 2018-08-21 Time 13:39 Rev Time 0.00
Received By rmcdouga Date 2018-08-20 Time 19:28 Sent To I
Notes
2018-08-21 11:18:57PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 2) THE PLANS THAT WERE SUBMITTED SHOW WOOD FRAMING AT
 THE DOOR OPENINGS. TYPE I AND II CONSTRUCTION REQUIRES
 NONCOMBUSTIBLE MATERIALS FOR THIS APPICATION. FBC 603.1
 ALLOWS FIRE-RETARDANT-TREATED WOOD IN NONBEARING
 PARTITIONS WHERE THE FIRE-RESISTANCE RATING IS 2 HOURS
 OR LESS. SPECIFY ON THE PLANS THAT THE WOOD STUDS AT
 THE DOOR OPENINGS WILL BE FIRE-RETARDANT-TREATED WOOD
 (FRTW).
  
 3) PROVIDE THE FOLLOWING INFORMATION FOR FLOORING
 SUBMITTALS:
  
 1. FLOOR PLAN WITH DIMENSIONS AND LOCATION OF WORK.
 > DESIGNER TO PRINT NAME AND SIGN PLAN PER FBC 107.
 2. TOTAL SQUARE FOOTAGE OF NEW FLOORING.
 3. TYPE OF PROPOSED HARD FLOORING (TILE, LAMINATE,
 WOOD, MARBLE, ETC.).
 4. STATED VALUE OF WORK.
 5. DESCRIPTION OF EXISTING SITE CONDITIONS:
 (A) THICKNESS OF SLAB (B) FLOOR/CEILING ASSEMBLY BELOW
 (EXPOSED CONCRETE, SUSPENDED GYPSUM OR ACOUSTICAL ).
 6. PROPOSED UNDERLAYMENT.
 7. TEST REPORTS FOR THE PROPOSED UNDERLAYMENT BASED ON
 THE EXISTING SITE CONDITIONS.
 8. TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM'S:
 E-84, E-90 & E-492.
 9. ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE.
  
 FBC 603.1 FLAME SPREAD - ASTM E 84-09
  
 FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
  
 SUBMIT TWO COPIES OF THE TEST REPORTS FOR THE SOUND
 INSULATION INCLUDING FLAME SPREAD AND SMOKE DEVELOPED
 FOR THE APPLICABLE CONSTRUCTION CONDITIONS.
  
  
 FBC 603 COMBUSTIBLE MATERIAL IN TYPE I AND II
 CONSTRUCTION
 603.1 ALLOWABLE MATERIALS.
 COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS
 OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING
 APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1
 THROUGH 603.1.3:
 2. THERMAL AND ACOUSTICAL INSULATION, OTHER THAN FOAM
 PLASTICS, HAVING A FLAME SPREAD INDEX OF NOT MORE THAN
 25.
 EXCEPTIONS:
 1. INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND
 SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 200.
  
 3. FOAM PLASTICS IN ACCORDANCE WITH CHAPTER 26.
  
  
 FBC 2603 FOAM PLASTIC INSULATION
 2603.3 SURFACE-BURNING CHARACTERISTICS.
 UNLESS OTHERWISE INDICATED IN THIS SECTION, FOAM
 PLASTIC INSULATION AND FOAM PLASTIC CORES OF
 MANUFACTURED ASSEMBLIES SHALL HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 75 AND A SMOKE-DEVELOPED INDEX OF NOT
 MORE THAN 450 WHERE TESTED IN THE MAXIMUM THICKNESS
 INTENDED FOR USE IN ACCORDANCE WITH ASTM E 84 OR UL
 723. LOOSE FILL-TYPE FOAM PLASTIC INSULATION SHALL BE
 TESTED AS BOARD STOCK FOR THE FLAME SPREAD AND
 SMOKE-DEVELOPED INDEXES.
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-09-20 Cont ID  
Sent By jpearson Date 2018-09-20 Time 08:47 Rev Time 0.00
Received By jpearson Date 2018-09-20 Time 07:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-10 Cont ID  
Sent By jpearson Date 2018-08-10 Time 16:48 Rev Time 0.00
Received By jpearson Date 2018-08-10 Time 16:48 Sent To  
Notes
2018-08-10 16:48:03CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (BOTH
 COPIES) IS REQUIRED TO BEAR THE NAME AND BE SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. THIS
 PERSON MUST BE A LICENSED DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION.
 WPB FBC 107.1, 107.2; FS 471, 481
 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC
 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-09-14 Cont ID  
Sent By scaldero Date 2018-09-14 Time 10:29 Rev Time 0.00
Received By scaldero Date 2018-09-14 Time 10:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-07-31 Cont ID  
Sent By scaldero Date 2018-07-31 Time 10:54 Rev Time 0.00
Received By scaldero Date 2018-07-31 Time 10:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-10-25 Cont ID  
Sent By rmcdouga Date 2018-10-25 Time 07:10 Rev Time 0.00
Received By rmcdouga Date 2018-10-24 Time 19:07 Sent To  
Notes
2018-10-24 19:07:25SENT TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-10-22 Cont ID  
Sent By pvalenti Date 2018-10-22 Time 17:04 Rev Time 0.00
Received By pvalenti Date 2018-10-05 Time 14:29 Sent To I
Notes
2018-10-09 14:29:57RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-01 Cont ID  
Sent By rmcdouga Date 2018-10-01 Time 15:59 Rev Time 0.00
Received By rmcdouga Date 2018-09-07 Time 15:48 Sent To  
Notes
2018-09-11 15:48:09B19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-21 Cont ID  
Sent By rmcdouga Date 2018-08-21 Time 13:39 Rev Time 0.00
Received By rmcdouga Date 2018-07-25 Time 14:34 Sent To  
Notes
2018-07-26 14:34:45B02

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-10-22 Cont ID  
Sent By ccole Date 2018-10-22 Time 08:58 Rev Time 0.00
Received By ccole Date 2018-10-22 Time 08:58 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-09-20 Cont ID  
Sent By ccole Date 2018-09-20 Time 11:21 Rev Time 0.00
Received By ccole Date 2018-09-20 Time 11:21 Sent To  
Notes
2018-09-20 11:22:161ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18071182
 9/20/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) CLARIFY IF THE 3.0 TON BOSCH UNIT IS A EXACT SIZE
 REPLACEMENT AND SUBMIT AN AC CHANGE OUT FORM IF
 APPLICABLE. PLEASE NOTE THAT THE SUBMITTED ACCA MANUAL
 J AC CALCULATIONS CANNOT BE USED TO DETERMINE SYSTEM
 SIZING IIN MULTI-FAMILY BUILDINGS OVER THREE STORIES.
 PLEASE SUBMIT CALCULATIONS IN ACCORDANCE WITH ACCA
 MANUAL N- SECTION C403.2.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-08-07 Cont ID  
Sent By ccole Date 2018-08-07 Time 17:19 Rev Time 0.00
Received By ccole Date 2018-08-07 Time 17:11 Sent To  
Notes
2018-08-07 17:25:211ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18071182
 8/7/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AN ENLARGED MECHANICAL THAT SHOWS THE DUCT
 RELOCATIONS, THE TYPE OF DUCTWORK, THE DUCT SIZES, AND
 THE CFM SUPPLY AT EACH RELOCATED DIFFUSER- SECTION
 107.2.1 WPB.
  
 2) DESIGN CRITERIA: PROVIDE A LIST OF CURRENT CODES AND
 STANDARDS USED IN THE DESIGN OF THE PROJECT, INCLUDING
 THE LEVEL OF ALTERATION PER THE FBC EX.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-10-15 Cont ID  
Sent By gjohnson Date 2018-10-15 Time 15:41 Rev Time 0.00
Received By gjohnson Date 2018-10-15 Time 15:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-09-27 Cont ID  
Sent By jesmith Date 2018-09-27 Time 12:11 Rev Time 0.00
Received By jesmith Date 2018-09-27 Time 12:10 Sent To  
Notes
2018-09-27 12:11:05CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 2ND REVIEW:
 PLUMBING COMMENTS: DENIED
  
 1. PROVIDE PIPING MATERIALS TYPE & FIRE RATED
 ASSEMBLIES FOR NEW OR RELOCATED PIPING FLOOR
 PENETRATIONS PER WPB FBC 107.2.1
 2. PROVIDE NOTE AT SHOWER STATING "SHOWER CONTROL
 VALVE(S) SHALL BE PRESSURE BALANCED PB,THERMOSTATIC
 MIXING (TM) OR COMBINATION PB/TM VALVE TYPES WITH HIGH
 TEMPERATURE LIMITING STOP." FBC PL 424.3
 3. PROVIDE THERMAL EXPANSION DEVICE REQUIRED ON COLD
 WATER SUPPLY TO WATER HEATER. A MEANS FOR CONTROLLING
 INCREASED PRESSURE CAUSED BY THERMAL EXPANSION SHALL BE
 INSTALLED WHERE REQUIRED IN ACCORDANCE WITH SECTION FBC
 PL 607.3
 4. PROVIDE DETAIL OF REPLACED WATER HEATER SHOWING
 HEATER W/STORAGE CAPACITY, PIPING INCLUDING CW, HW,
 VALVING, THERMAL EXPANSION CONTROL DEVICE, T&P
 DISCHARGE( INCLUDING TERMINATION) AND WATER HEATER PAN
 AND DRAIN (INCLUDING TERMINATION)PER WPB FPC 107.2.1;
 COMPLY WITH FBC PL 607.3, 503.1, 504.1, 504.4, 504.4.1,
 504.5, 504.6, 504.7, 504.7.1 AND 504.7.2.
 6. PROVIDE WATER HAMMER ARRESTORS AT WATER SUPPLIES TO
 ICE LINE, DISHWASHER AND CLOTHES WASHER PER FPC PL
 604.9; INDICATE SAME ON THE PLANS PER WPB FPC 107.2.1
 7. PLUMBING CONTRACTOR AS DESIGNER OF RECORD IS TO SIGN
 TWO SETS OF EACH PLUMBING PLAN PAGE PER FS 471 & FAC
 61G15
  
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-08-20 Cont ID  
Sent By gjohnson Date 2018-08-20 Time 16:26 Rev Time 0.00
Received By gjohnson Date 2018-08-20 Time 16:26 Sent To  
Notes
2018-08-20 16:34:571ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. WILL THERE BE ANY CHANGES IN LOCATION OR TYPES OF
 PLUMBING FIXTURES PLEASE PLACE NOT ON THE PLAN TO
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. WHAT TYPE OF SHOWER PAN IS BEING USED PLACE NOTE ON
 PLAN, IF ANYTHING OTHER THAN VINYL PLEASE PROVIDE
 MANUFACTURE SPECIFICATIONS AND INSTALLATION GUIDE. .
 PER WPB AMEND TO FBC 107.2.1
  
 3. SHOW LOCATION AND TYPE OF WATER HEATER. . PER WPB
 AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  