| Plan Review Stops For Permit 18071051 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2018-08-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-08-25 |
Time |
09:33 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-08-25 |
Time |
09:33 |
Sent To |
|
|
| Notes |
| 2018-08-25 09:36:00 | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | PROVISO: A SEPARATE ROOF PERMIT IS REQUIRED PRIOR TO | | | COMMENCEMENT OF ROOF WORK | | | SUBMIT ROOF PERMIT APPLICATION AND PRODUCT APPROVALS, | | | REVIEWED BY DESIGNER OF RECORD, TO THE BUILDING | | | DIVISION. | | | FOR THE ROOF TILE, INDICATE WHICH METHOD OF ATTACHMENT | | | IS PROPOSED. IF ADHESIVE IS PROPOSED, ALSO PROVIDE THE | | | PRODUCT APPROVAL. IF AN UNDERLAYMENT PRODUCT APPROVAL | | | IS SUBMITTED, INDICATE WHICH METHOD OF ATTACHMENT IS | | | PROPOSED. | | | | | | | | 2018-08-15 16:07:00 | PLAN REVIEW FEE NOT PAID. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2018-10-30 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-10-30 |
Time |
09:11 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-10-30 |
Time |
09:11 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2018-09-19 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-09-19 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-09-19 |
Time |
13:41 |
Sent To |
|
|
| Notes |
| 2018-09-19 14:13:46 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. AFCI PROTECTION SHOWN IN NOT CODE COMPLIANT. ALL | | | BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- | | | AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY | | | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, | | | DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, | | | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS | | | SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND | | | POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH | | | AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC | | | 210.8, 210.12; FBC RE E3902 | | | 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. | | | NEC 110.9, 110.10; FBC RE E3603.3 | | | 3. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE | | | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF | | | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | | CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE. | | | FBC EC C405.1, R404.1 | | | 4. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE | | | OUTLETS IN GARAGE AND EXTERIOR RECEPTACLES. PROVIDE | | | CORRECTION. NEC 210.8; FBC RE E3902.2 | | | 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC | | | 210.8(D); FBC RE E3902.10 | | | 6. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT | | | SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 | | | 7. RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS SHALL | | | HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC | | | 210.8(A)(9); FBC RE E3902.9 | | | 8. FEED TO INTERIOR PANEL IS REQUIRED TO HAVE AN | | | EQUIPMENT GROUNDING CONDUCTOR, SIZED PER CODE. PROVIDE | | | CORRECTION. NEC 250.122; FBC RE E3704.6, 3607.3.1 | | | 9. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE | | | SUITABLE FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC | | | 410.10(D); FBC RE E4003.11 | | | 10. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF | | | EACH ROOM USED FOR SLEEPING PURPOSES. FBC RE R315.1 | | | 11. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A | | | NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-08-21 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-08-21 |
Time |
15:59 |
Sent To |
|
|
| Notes |
| 2018-08-15 16:06:43 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. FEES MUST BE PAID FOR PLAN REVIEW. WPB FBC 105.1 | | | 2. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND | | | SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE | | | ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H); | | | 471.025; WPB FBC 107.2.1, 107.3.5 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD | | | SHEETS?. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | | | 2018-08-15 14:16:15 | IGNORE PREVIOUS REVIEW COMMENTS AS DIGITIAL PLANS HAVE | | | NOT YET BEEN UPLOADED. | | 2018-08-13 16:06:43 | NO ELECTRIC SHOWN OR DOCUMENTED JLEAHY |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2018-09-19 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-09-19 |
Time |
12:31 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-09-19 |
Time |
12:31 |
Sent To |
|
|
| Notes |
| 2018-09-19 12:32:19 | GAS WILL BE BY SEPARATE SUBMITTAL. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-09-04 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-09-04 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-09-04 |
Time |
15:50 |
Sent To |
|
|
| Notes |
| 2018-09-04 15:55:15 | 1ST REVIEW: FBC 2017 6TH ED. RESIDENTIAL | | | 1ST REVIEW FBC 2017 EXISTING BUILDING | | | | | | THE PLANS DO NOT CONTAIN SUFFICIENT DETIAL TO DETERMINE | | | THE SCOPR OF WORK RELATIVE TO GAS SYSTEMS. THE | | | SUBMITTED SCOPE OF WORK FEE ESTIMATE INDICATES REPAIRS | | | OR REPLACEMENT TO A GAS SYSTEM IS INCLUDED. PRESENT GAS | | | DETAILS TO IDENTIFY THE WORK REQUIRED OR ELECT TO DEFER | | | SUCH DESIGN BY SEPARATE PERMIT. | | | | | | FBC107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN | | | UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS | | | SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING | | | OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF | | | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL | | | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT | | | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED | | | BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND | | | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM | | | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, | | | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE | | | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, | | | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE | | | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS | | | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | | INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | | SECTION 107.3.5). | | | | | | | | | | | | STEVEN KENNEDY, CBO | | | ASSISTANT BUILDING OFFICIAL | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2018-11-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-11-02 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-11-01 |
Time |
14:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-10-30 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-10-15 |
Time |
16:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-09-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-09-19 |
Time |
12:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-09-04 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-09-04 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-08-21 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2018-08-15 13:34:57 | PLANS CHANGED TO DIGITAL | | 2018-07-26 10:06:36 | R29 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2018-11-02 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2018-11-02 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2018-11-02 |
Time |
14:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2018-10-27 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2018-10-27 |
Time |
07:45 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2018-10-27 |
Time |
07:41 |
Sent To |
|
|
| Notes |
| 2018-10-27 07:45:12 | MECHANICAL PLAN REVIEW FAIL | | | | | | 1 - RETURN AIR TRANSFER DUCT FOR MASTER SUITE TO SMALL | | | SEE 2017 FLORIDA BUILDING CODE - MECHANICAL, SIXTH | | | EDITION SEC. 601.6 BALANCED RETURN AIR. | | | | | | | | | CHRIS MONTELLO | | | 561-805-6733 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2018-09-04 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2018-09-04 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2018-09-04 |
Time |
15:10 |
Sent To |
|
|
| Notes |
| 2018-08-15 14:16:33 | IGNORE PREVIOUS REVIEW COMMENTS AS DIGITIAL PLANS HAVE | | | NOT YET BEEN UPLOADED. | | 2018-08-14 14:25:52 | MECHANICAL PLAN REVIEW FAILED | | | | | | 1 - NEED MECHANICAL PLANS PER 2017 FLORIDA BUILDING | | | CODE SEC. 107.2.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS. | | | | | | CHRIS MONTELLO | | | 561-805-6733 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2018-09-19 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-09-19 |
Time |
12:32 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-09-19 |
Time |
12:32 |
Sent To |
|
|
| Notes |
| 2018-09-19 12:33:59 | FIXTURE REPLACEMENT DOES NOT REQUIRE A PERMIT, HOWEVER, | | | PLUMBING CONTRACTOR MAY HAVE TO SUBMIT A DSIGN IF WORK | | | BEYOND FIXTURE REPLACEMENT IS PERFORMED. . |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-09-04 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-09-04 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-09-04 |
Time |
15:55 |
Sent To |
|
|
| Notes |
| 2018-09-04 15:56:49 | 1ST REVIEW: FBC 2017 6TH ED. RESIDENTIAL | | | 1ST REVIEW FBC 2017 EXISTING BUILDING | | | | | | THE PLANS DO NOT CONTAIN SUFFICIENT DETIAL TO DETERMINE | | | THE SCOPE OF WORK RELATIVE TO PLUMBING SYSTEMS. THE | | | SUBMITTED SCOPE OF WORK FEE ESTIMATE INDICATES REPAIRS | | | OR REPLACEMENT TO THE PLUMBING SYSTEM IS INCLUDED. | | | PRESENT PLUMBING DETAILS TO IDENTIFY THE WORK | | | REQUIRED.. | | | | | | FBC107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN | | | UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS | | | SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING | | | OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF | | | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL | | | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT | | | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED | | | BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND | | | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM | | | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, | | | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE | | | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, | | | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE | | | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS | | | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | | INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | | SECTION 107.3.5). | | | | | | STEVEN KENNEDY, CBO | | | ASSISTANT BUILDING OFFICIAL | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2018-08-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-08-25 |
Time |
09:36 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-08-25 |
Time |
09:36 |
Sent To |
|
|
| Notes |
| 2018-08-25 09:36:48 | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | PROVISO: A SEPARATE ROOF PERMIT IS REQUIRED PRIOR TO | | | COMMENCEMENT OF ROOF WORK | | | SUBMIT ROOF PERMIT APPLICATION AND PRODUCT APPROVALS, | | | REVIEWED BY DESIGNER OF RECORD, TO THE BUILDING | | | DIVISION. | | | FOR THE ROOF TILE, INDICATE WHICH METHOD OF ATTACHMENT | | | IS PROPOSED. IF ADHESIVE IS PROPOSED, ALSO PROVIDE THE | | | PRODUCT APPROVAL. IF AN UNDERLAYMENT PRODUCT APPROVAL | | | IS SUBMITTED, INDICATE WHICH METHOD OF ATTACHMENT IS | | | PROPOSED. | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2018-11-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-11-02 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-11-02 |
Time |
14:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2018-10-30 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-10-30 |
Time |
08:56 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-10-30 |
Time |
08:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2018-09-19 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-09-19 |
Time |
13:43 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-09-19 |
Time |
13:43 |
Sent To |
|
|
| Notes |
| 2018-09-19 13:40:47 | SHEETS E1, M0, AND M1 ARE NOT DIGITALLY SIGNED/SEALED | | | PER FLORIDA STATUTES. | | | | | | E1 INCLUDES THE TITLE BLOCK FOR DAN CROSS, BUT IS NOT | | | DIGITALLY SIGNED. DOCUMENTS PREPARED BY AN ENGINEER AND | | | SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, | | | DATED ORIGINALS, FS471. | | | | | | M0, M1 INCLUDE THE TITLE BLOCK FOR DAN CROSS, BUT IS | | | NOT DIGITALLY SIGNED. DOCUMENTS PREPARED BY AN ENGINEER | | | AND SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, | | | SEALED, DATED ORIGINALS, FS471. | | | | | | S0, S1 - OK (KEVIN Z KNOWLES, PE) | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2018-08-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-08-25 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-08-25 |
Time |
09:28 |
Sent To |
|
|
| Notes |
| 2018-08-25 09:32:04 | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. SEE ELECTRICAL COMMENTS. | | | | | | 2. E0 - OK | | | E1 INCLUDES THE TITLE BLOCK FOR DAN CROSS, BUT IS NOT | | | DIGITALLY SIGNED. DOCUMENTS PREPARED BY AN ENGINEER AND | | | SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, | | | DATED ORIGINALS, FS471. | | | | | | 3. M0, M1 INCLUDE THE TITLE BLOCK FOR DAN CROSS, BUT IS | | | NOT DIGITALLY SIGNED. DOCUMENTS PREPARED BY AN ENGINEER | | | AND SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, | | | SEALED, DATED ORIGINALS, FS471. | | | | | | 4. S0, S1 - OK (KEVIN Z KNOWLES, PE) | | | | | | |
|
|