Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-08-25 Cont ID  
Sent By shill Date 2018-08-25 Time 09:33 Rev Time 0.00
Received By shill Date 2018-08-25 Time 09:33 Sent To  
Notes
2018-08-25 09:36:00SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PROVISO: A SEPARATE ROOF PERMIT IS REQUIRED PRIOR TO
 COMMENCEMENT OF ROOF WORK
 SUBMIT ROOF PERMIT APPLICATION AND PRODUCT APPROVALS,
 REVIEWED BY DESIGNER OF RECORD, TO THE BUILDING
 DIVISION.
 FOR THE ROOF TILE, INDICATE WHICH METHOD OF ATTACHMENT
 IS PROPOSED. IF ADHESIVE IS PROPOSED, ALSO PROVIDE THE
 PRODUCT APPROVAL. IF AN UNDERLAYMENT PRODUCT APPROVAL
 IS SUBMITTED, INDICATE WHICH METHOD OF ATTACHMENT IS
 PROPOSED.
  
  
2018-08-15 16:07:00PLAN REVIEW FEE NOT PAID.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-10-30 Cont ID  
Sent By jpearson Date 2018-10-30 Time 09:11 Rev Time 0.00
Received By jpearson Date 2018-10-30 Time 09:11 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-09-19 Cont ID  
Sent By jpearson Date 2018-09-19 Time 14:13 Rev Time 0.00
Received By jpearson Date 2018-09-19 Time 13:41 Sent To  
Notes
2018-09-19 14:13:46CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. AFCI PROTECTION SHOWN IN NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902
 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3603.3
 3. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 4. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE
 OUTLETS IN GARAGE AND EXTERIOR RECEPTACLES. PROVIDE
 CORRECTION. NEC 210.8; FBC RE E3902.2
 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 6. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
 7. RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS SHALL
 HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8(A)(9); FBC RE E3902.9
 8. FEED TO INTERIOR PANEL IS REQUIRED TO HAVE AN
 EQUIPMENT GROUNDING CONDUCTOR, SIZED PER CODE. PROVIDE
 CORRECTION. NEC 250.122; FBC RE E3704.6, 3607.3.1
 9. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE
 SUITABLE FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC
 410.10(D); FBC RE E4003.11
 10. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF
 EACH ROOM USED FOR SLEEPING PURPOSES. FBC RE R315.1
 11. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date   Cont ID  
Sent By jleahy Date 2018-08-21 Time 15:59 Rev Time 0.00
Received By jpearson Date 2018-08-21 Time 15:59 Sent To  
Notes
2018-08-15 16:06:43CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. FEES MUST BE PAID FOR PLAN REVIEW. WPB FBC 105.1
 2. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
2018-08-15 14:16:15IGNORE PREVIOUS REVIEW COMMENTS AS DIGITIAL PLANS HAVE
 NOT YET BEEN UPLOADED.
2018-08-13 16:06:43NO ELECTRIC SHOWN OR DOCUMENTED JLEAHY

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2018-09-19 Cont ID  
Sent By skennedy Date 2018-09-19 Time 12:31 Rev Time 0.00
Received By skennedy Date 2018-09-19 Time 12:31 Sent To  
Notes
2018-09-19 12:32:19GAS WILL BE BY SEPARATE SUBMITTAL.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-09-04 Cont ID  
Sent By skennedy Date 2018-09-04 Time 15:50 Rev Time 0.00
Received By skennedy Date 2018-09-04 Time 15:50 Sent To  
Notes
2018-09-04 15:55:151ST REVIEW: FBC 2017 6TH ED. RESIDENTIAL
 1ST REVIEW FBC 2017 EXISTING BUILDING
  
 THE PLANS DO NOT CONTAIN SUFFICIENT DETIAL TO DETERMINE
 THE SCOPR OF WORK RELATIVE TO GAS SYSTEMS. THE
 SUBMITTED SCOPE OF WORK FEE ESTIMATE INDICATES REPAIRS
 OR REPLACEMENT TO A GAS SYSTEM IS INCLUDED. PRESENT GAS
 DETAILS TO IDENTIFY THE WORK REQUIRED OR ELECT TO DEFER
 SUCH DESIGN BY SEPARATE PERMIT.
  
 FBC107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
  
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-11-02 Cont ID  
Sent By shill Date 2018-11-02 Time 14:30 Rev Time 0.00
Received By shill Date 2018-11-01 Time 14:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-10-30 Time   Rev Time 0.00
Received By lmarchan Date 2018-10-15 Time 16:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-09-19 Time   Rev Time 0.00
Received By skennedy Date 2018-09-19 Time 12:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-04 Cont ID  
Sent By skennedy Date 2018-09-04 Time 15:56 Rev Time 0.00
Received By skennedy Date 2018-08-21 Time 14:17 Sent To  
Notes
2018-08-15 13:34:57PLANS CHANGED TO DIGITAL
2018-07-26 10:06:36R29

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-11-02 Cont ID  
Sent By cmontell Date 2018-11-02 Time 14:26 Rev Time 0.00
Received By cmontell Date 2018-11-02 Time 14:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-10-27 Cont ID  
Sent By cmontell Date 2018-10-27 Time 07:45 Rev Time 0.00
Received By cmontell Date 2018-10-27 Time 07:41 Sent To  
Notes
2018-10-27 07:45:12MECHANICAL PLAN REVIEW FAIL
  
 1 - RETURN AIR TRANSFER DUCT FOR MASTER SUITE TO SMALL
 SEE 2017 FLORIDA BUILDING CODE - MECHANICAL, SIXTH
 EDITION SEC. 601.6 BALANCED RETURN AIR.
  
  
 CHRIS MONTELLO
 561-805-6733

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-09-04 Cont ID  
Sent By cmontell Date 2018-09-04 Time 15:10 Rev Time 0.00
Received By cmontell Date 2018-09-04 Time 15:10 Sent To  
Notes
2018-08-15 14:16:33IGNORE PREVIOUS REVIEW COMMENTS AS DIGITIAL PLANS HAVE
 NOT YET BEEN UPLOADED.
2018-08-14 14:25:52MECHANICAL PLAN REVIEW FAILED
  
 1 - NEED MECHANICAL PLANS PER 2017 FLORIDA BUILDING
 CODE SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 CHRIS MONTELLO
 561-805-6733

Review Stop P PLUMBING
Rev No 2 Status N Date 2018-09-19 Cont ID  
Sent By skennedy Date 2018-09-19 Time 12:32 Rev Time 0.00
Received By skennedy Date 2018-09-19 Time 12:32 Sent To  
Notes
2018-09-19 12:33:59FIXTURE REPLACEMENT DOES NOT REQUIRE A PERMIT, HOWEVER,
 PLUMBING CONTRACTOR MAY HAVE TO SUBMIT A DSIGN IF WORK
 BEYOND FIXTURE REPLACEMENT IS PERFORMED. .

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-09-04 Cont ID  
Sent By skennedy Date 2018-09-04 Time 15:55 Rev Time 0.00
Received By skennedy Date 2018-09-04 Time 15:55 Sent To  
Notes
2018-09-04 15:56:491ST REVIEW: FBC 2017 6TH ED. RESIDENTIAL
 1ST REVIEW FBC 2017 EXISTING BUILDING
  
 THE PLANS DO NOT CONTAIN SUFFICIENT DETIAL TO DETERMINE
 THE SCOPE OF WORK RELATIVE TO PLUMBING SYSTEMS. THE
 SUBMITTED SCOPE OF WORK FEE ESTIMATE INDICATES REPAIRS
 OR REPLACEMENT TO THE PLUMBING SYSTEM IS INCLUDED.
 PRESENT PLUMBING DETAILS TO IDENTIFY THE WORK
 REQUIRED..
  
 FBC107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2018-08-25 Cont ID  
Sent By shill Date 2018-08-25 Time 09:36 Rev Time 0.00
Received By shill Date 2018-08-25 Time 09:36 Sent To  
Notes
2018-08-25 09:36:48SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PROVISO: A SEPARATE ROOF PERMIT IS REQUIRED PRIOR TO
 COMMENCEMENT OF ROOF WORK
 SUBMIT ROOF PERMIT APPLICATION AND PRODUCT APPROVALS,
 REVIEWED BY DESIGNER OF RECORD, TO THE BUILDING
 DIVISION.
 FOR THE ROOF TILE, INDICATE WHICH METHOD OF ATTACHMENT
 IS PROPOSED. IF ADHESIVE IS PROPOSED, ALSO PROVIDE THE
 PRODUCT APPROVAL. IF AN UNDERLAYMENT PRODUCT APPROVAL
 IS SUBMITTED, INDICATE WHICH METHOD OF ATTACHMENT IS
 PROPOSED.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2018-11-02 Cont ID  
Sent By shill Date 2018-11-02 Time 14:29 Rev Time 0.00
Received By shill Date 2018-11-02 Time 14:29 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2018-10-30 Cont ID  
Sent By jpearson Date 2018-10-30 Time 08:56 Rev Time 0.00
Received By jpearson Date 2018-10-30 Time 08:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-09-19 Cont ID  
Sent By jpearson Date 2018-09-19 Time 13:43 Rev Time 0.00
Received By jpearson Date 2018-09-19 Time 13:43 Sent To  
Notes
2018-09-19 13:40:47SHEETS E1, M0, AND M1 ARE NOT DIGITALLY SIGNED/SEALED
 PER FLORIDA STATUTES.
  
 E1 INCLUDES THE TITLE BLOCK FOR DAN CROSS, BUT IS NOT
 DIGITALLY SIGNED. DOCUMENTS PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS, FS471.
  
 M0, M1 INCLUDE THE TITLE BLOCK FOR DAN CROSS, BUT IS
 NOT DIGITALLY SIGNED. DOCUMENTS PREPARED BY AN ENGINEER
 AND SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED,
 SEALED, DATED ORIGINALS, FS471.
  
 S0, S1 - OK (KEVIN Z KNOWLES, PE)
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-08-25 Cont ID  
Sent By shill Date 2018-08-25 Time 09:28 Rev Time 0.00
Received By shill Date 2018-08-25 Time 09:28 Sent To  
Notes
2018-08-25 09:32:04SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SEE ELECTRICAL COMMENTS.
  
 2. E0 - OK
 E1 INCLUDES THE TITLE BLOCK FOR DAN CROSS, BUT IS NOT
 DIGITALLY SIGNED. DOCUMENTS PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS, FS471.
  
 3. M0, M1 INCLUDE THE TITLE BLOCK FOR DAN CROSS, BUT IS
 NOT DIGITALLY SIGNED. DOCUMENTS PREPARED BY AN ENGINEER
 AND SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED,
 SEALED, DATED ORIGINALS, FS471.
  
 4. S0, S1 - OK (KEVIN Z KNOWLES, PE)
  
  