| 2018-07-30 06:41:42 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. J-BOX WITH 120V HAS LINE AND LOAD END OF POWER |
| | SUPPLY IN IT ALSO. CANNOT MIX HIGH AND LOW VOLTAGE. |
| | 725.136B NEC |
| | |
| | 2. IN RESPONSE TO COMMENT THAT "TIMECLOCK IS EXISTING". |
| | TIMECLOCK MUST STILL CONFORM TO FBC CE 405.2.4. TIME |
| | CLOCK MUST BE ASTRONOMICAL WITH 10/HOUR BATTERY BACK |
| | UP. |
| | |
| | 3. NOT ALL PAGES OF PLAN ARE SIGNED/SEALED BY ENGINEER. |
| | ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND |
| | SIGNED/SEALED BY A DESIGN PROFESSIONAL OR THE |
| | ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS |
| | 471.003(2)(H); 471.025; WPB FBC 107.1 |
| | |
| | 4. UNABLE TO ISSUE ELECTRICAL SUB-PERMIT TO ES LICENSE. |
| | NEED LICENSED ELECTRICIAN TO INSTALL REQUIRED TIMECLOCK |
| | AND 120V DISCONNECT FOR SIGN. THIS WORK IS OUT OF SCOPE |
| | FOR AN ES LICENSE. PLEASE SEE SCOPE OF ES LICENSE |
| | BELOW; |
| | |
| | |
| | SIGN CONTRACTORS F.S. 489.505 (#19) AND F.A.C. |
| | 61G6-7.001 SPECIALTY ELECTRICAL CONTRACTORS (#2 SIGN |
| | SPECIALTY CONTRACTOR) |
| | |
| | THE SCOPE OF CERTIFICATION INCLUDES THE STRUCTURAL |
| | FABRICATION INCLUDING CONCRETE FOUNDATION, ERECTION, |
| | INSTALLATION, ALTERATION, REPAIR, SERVICE AND WIRING OF |
| | ELECTRICAL SIGNS AND OUTLINE LIGHTING. THE SCOPE OF |
| | CERTIFICATION SHALL NOT INCLUDE THE PROVISION OF, OR |
| | ANY ELECTRICAL WORK BEYOND, THE LAST DISCONNECT MEAN OR |
| | TERMINAL POINTS. HOWEVER, A CONTRACTOR CERTIFIED UNDER |
| | THIS SECTION MAY PROVIDE THE ELECTRICAL ENTRANCE |
| | REQUIREMENTS FOR METERING AND MAIN DISCONNECT OF REMOTE |
| | BILLBOARDS OR SIGNS WHICH ARE INDEPENDENT OF ANY |
| | STRUCTURE OR BUILDING AND WHICH REQUIRE NO MORE THAN |
| | TWENTY-FIVE (25) KILOWATTS AT TWO HUNDRED FIFTY (250) |
| | VOLTS MAXIMUM. |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |