Plan Review Details - Permit 18070946
Plan Review Stops For Permit 18070946
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-11-01 Cont ID  
Sent By dbattles Date 2018-11-01 Time 09:52 Rev Time 0.00
Received By dbattles Date 2018-11-01 Time 09:52 Sent To  
Notes
2018-11-01 09:52:15PROVISO:
 TRUSS SUBMITTAL TO INSPECTOR PRIOR TO INSTALL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-09-14 Cont ID  
Sent By dbattles Date 2018-09-14 Time 07:56 Rev Time 0.00
Received By dbattles Date 2018-09-12 Time 16:29 Sent To  
Notes
2018-09-14 07:58:08****CORRECTIONS****
 W.P.B. PERMIT: 18070946 (HOUSE)
 REVIEWED: SEPTEMBER 13, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC A = AMENDMENTS TO THE FLORIDA BUILDING CODE,6TH
 EDITION (2017)
 FBC B = FBC BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 [FBC AMENDED 105]SEPARATE PERMIT THROUGH ENGINEERING
 FOR DRIVEWAY ACCESS. CONTACT 561-494-1040, OR ON THE
 WEB: HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-
 WORKS/ENGINEERING-SERVICES
  
 1.[FBC 107.3.5.3]PROVIDE SEDIMENT CONTROL PLAN TO KEEP
 CONSTRUCTION DEBRIS FROM ENTERING ADJACENT PROPERTIES
 AND STORM DRAINS DURING CONSTRUCTION. YOU CAN FIND
 ENGINEERING STANDARD DETAILS FROM WPB WEBSITE-POLLUTION
 CONTROL
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 2. [FBC R401.3]SITE DRAINAGE PLAN.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN
 SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE
 SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE
 FIRST 10 FEET (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING.
 DRAINAGE PLAN PROVIDED SHOWS FLOW TO THE BACK OF
 PROPERTY. THIS WOULD ALLOW WATER TO ENTER SOUTH LOT.
 PLEASE ADJUST TO MAINTAIN DRAINAGE WITHIN YOUR SITE AND
 SPECIFY WHERE THE NEAREST STORM DRAINS ARE LOCATED.
  
 3. [FBC 107.2.5]SHEET 1 WIND INFORMATION-REMOVE LEVEL
 OF ALTERATION 2. THIS WOULD BE NEW CONSTRUCTION R-3.
  
 4. [FBC R408.4]PROVIDE ACCESS TO THE UNDER FLOOR SPACE
 18X24 MINIMUM.
  
 5. [FBC R301.4]DEAD LOAD AND[FBC R301.5]LIVE LOAD
 PROVIDE LOADS FOR FLOORING ON SHEET 4 AND LOADS FOR
 ROOFING ON SHEET 5.
 ALSO, ADD SPECIES ANS GRADE TO 2X12 JOISTS TO SHOW
 SPANNING MEETS SECTION R502 FOR WOOD FLOOR FRAMING.
  
 6. [FBC TABLE R301.7]ALLOWABLE DEFLECTION FOR FLOOR
 ADDED TO SHEET 4 AND CEILING DEFLECTION ADDED TO SHEET
 5.
  
 7. [FBC R302.9.1 & R302.9.2]FINISHES SHALL HAVE A FLAME
 SPEAD INDEX OF NOT GREATER THAN 200 AND SMOKE DEVELOPED
 INDEX OF NOT GREATER THAN 450.
  
 8. [FBC R602.10]WALL BRACING.
 WHICH METHOD IS BEING USED TO SATISFY BRACING
 REQUIREMENTS? PROVIDE DATA TO SUPPORT THE METHOD IN
 USE.
 HARDIE SIDING REQUIRES BRACED WOOD OR 5/8? SHEATHING.
 PROVIDE BRACING DETAILS TO MEET PRODUCT APPROVAL AND
 CO-ORDINATE BRACING WITH COMMENT ABOVE.
 NOA 18-0504.02 IS HIGHLIGHTED ON HARDIE SIDING
 SUBMITTAL. IF THIS IS BEING USED THAN SUPPLY THAT NOA.
 [FBC AMENDED 107.2.1.2]FL 17184.09 IS MISSING THE
 DRAWINGS PORTION OF PRODUCT APPROVAL. PLEASE PROVIDE 2
 COPIES OF THIS PORTION TO SHOW PRESSURES AND CONNECTOR
 DATA.
  
 9. [FBC AMENDED 107.3.4.1]SUBMIT TRUSS SHOP DRAWINGS,
 OR INDICATE THAT THE SUBMITTAL WILL BE DEFERRED.
 DEFERRED SUBMITTALS TO BE REVIEWED PRIOR TO
 INSTALLATION.
  
 10. [FBC R3-1.2(6)]PROVIDE ROOFING WIND DIAGRAM THAT
 MATCHES THE ROOF CONDITION OF THIS HOUSE FOR ZONES
 1,2,& 3.
 SHEET 5 - UPDATE CONNECTOR H10A TO REFERENCE CURRENT FL
 10456.2
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2018-11-20 Cont ID  
Sent By jpearson Date 2018-11-20 Time 09:18 Rev Time 0.00
Received By jpearson Date 2018-11-20 Time 09:17 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2018-11-09 Cont ID  
Sent By jpearson Date 2018-11-09 Time 08:55 Rev Time 0.00
Received By jpearson Date 2018-11-09 Time 08:32 Sent To  
Notes
2018-11-09 08:55:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3603.3 (NOT PROVIDED, NOTED
 THAT WILL BE PROVIDED BEFORE INSPECTION.)
 3. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9; FBC RE E3603.3 (NOT PROVIDED AS NOTED
 ON RESPONSE LETTER.)
 4. CORRECTED.
 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10 (NOT PROVIDED.)
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
 9. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. NEC 220; FBC RE E3602.2 (LOAD CALCULATION
 PROVIDED DOES NOT INCLUDE ALL LOADS, DOES NOT INCLUDE
 GARAGE PANEL, LOAD FOR TANKLESS HEATER NOT INCLUDED.
 PROVIDE LOAD CALCULATION FOR ENTIRE SERVICE AS
 REQUESTED.)
 10. CORRECTED.
 11. RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS SHALL
 HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8(A)(9); FBC RE E3902.9 (NOT PROVIDED.)
 12. LIGHTING MUST MAINTAIN PROPER CLEARANCES FROM THE
 NEAREST POINT OF STORAGE SPACE IN A CLOTHES CLOSET.
 PROVIDE CORRECTION. NEC 410.16; FBC RE E4003.12 (NOT
 CORRECTED.)
 13. CORRECTED.
 14. CORRECTED.
 15. CORRECTED.
 16. CORRECTED.
 17. CORRECTED.
 18. CORRECTED.
 19. CORRECTED.
 20. CORRECTED.
 21. CORRECTED.
 22. CORRECTED.
 23. NEW RISER PROVIDED SHOWS 4/0 ALUMINUM WIRE FROM
 METER TO SERVICE DISCONNECT AND FROM SERVICE DISCONNECT
 TO INTERIOR PANELS. THIS WIRE SIZE IS NOT RATED FOR 200
 AMPS. PROVIDE CORRECTION. NEC 310.15(B)(16); FBC RE
 E3705.1 (NOT CORRECTED.)
 24. FEED TO INTERIOR PANELS FROM SERVICE DISCONNECT IS
 REQUIRED TO HAVE AN EQUIPMENT GROUNDING CONDUCTOR,
 SIZED PER CODE. PROVIDE CORRECTION. NEC 250.122; FBC RE
 E3704.6, 3607.3.1 (ATTEMPTED CORRECTION IS NOT CODE
 COMPLIANT.)
 25. SPECIFY WIRE AND CONDUIT SIZE FOR OVERHEAD MAST TO
 FPL. WPB FBC 107.2.1; NEC 310.15(B)(7); FBC RE E3603.1
 (WIRE SIZE SPECIFIED IS NOT TO CODE.)
 26. GROUNDING ELECTRODE CONDUCTOR SHOULD NOT BE WIRED
 TO METER CAN AND SERVICE DISCONNECT AND INTERIOR PANEL.
 IT IS CONNECTED AT EITHER THE METER CAN OF THE FIRST
 MEANS OF DISCONNECT. PROVIDE CORRECTION. NEC 250.6 (NOT
 CORRECTED.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-10-11 Cont ID  
Sent By jpearson Date 2018-10-11 Time 09:29 Rev Time 0.00
Received By jpearson Date 2018-10-11 Time 08:27 Sent To  
Notes
2018-10-11 09:29:03CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. AFCI PROTECTION SHOWN IN NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902 (HAND WRITTEN NOTES ON PLAN
 ARE NOT ACCEPTABLE.)
 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3603.3 (NOT PROVIDED, NOTED
 THAT WILL BE PROVIDED BEFORE INSPECTION.)
 3. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9; FBC RE E3603.3 (NOT PROVIDED AS NOTED
 ON RESPONSE LETTER.)
 4. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1(NOT PROVIDED.)
 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10 (NOT PROVIDED.)
 6. CORRECTED.
 7. CORRECTED.
 8. A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE
 ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND
 CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF
 GROUNDING ELECTRODE SYSTEM AND WIRING. NEC 250.32; FBC
 RE E3607.3 (GROUNDING ELECTRODE CONDUCTOR SHOULD NOT BE
 INSTALLED TO SUB-PANEL AT MAIN SERVICE. THE CONDUITS
 FEEDING EACH OF THE SUB-PANELS AFTER THE FIRST MEANS OF
 DISCONNECT SHOULD INCLUDE AN EQUIPMENT GROUNDING
 CONDUCTOR SIZED PER NEC 250.122. PROVIDE CORRECTION.)
 9. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. NEC 220; FBC RE E3602.2 (LOAD CALCULATION
 PROVIDED DOES NOT INCLUDE ALL LOADS, DOES NOT INCLUDE
 GARAGE PANEL, LOAD FOR TANKLESS HEATER NOT INCLUDED.
 PROVIDE LOAD CALCULATION FOR ENTIRE SERVICE AS
 REQUESTED.)
 10. CORRECTED.
 11. RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS SHALL
 HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8(A)(9); FBC RE E3902.9 (NOT PROVIDED.)
 12. LIGHTING MUST MAINTAIN PROPER CLEARANCES FROM THE
 NEAREST POINT OF STORAGE SPACE IN A CLOTHES CLOSET.
 PROVIDE CORRECTION. NEC 410.16; FBC RE E4003.12 (NOT
 CORRECTED.)
 13. PROVIDE LOCATION OF METER CAN AND PANEL ON PLAN.
 WPB FBC 107.2.1 (HAND WRITTEN NOTES ARE NOT
 ACCEPTABLE.)
 14. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR
 ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. NEC 210.8, 210.12, 210.19, 210.20,
 215.5, 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
 (NOT PROVIDED.)
 15. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FS
 481.229; WPB FBC 107.2.1, 107.3.5.1.2 (NOT PROVIDED.
 EACH SHEET SUPPLIED AS PART OF PLAN MUST BEAR THE
 PRINTED NAME AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN. IF THAT PERSON IS LICENSED, IT MUST
 ALSO INCLUDE THAT LICENSE NUMBER.)
 16. CORRECTED.
 17. CORRECTED.
 18. CORRECTED.
 19. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14 (NOT
 PROVIDED.)
 20. CORRECTED.
 21. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN.
 PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE
 E3703.4, E3901.6 (NOT CORRECTED.)
 22. CORRECTED.
  
 NEW COMMENTS:
  
 23. NEW RISER PROVIDED SHOWS 4/0 ALUMINUM WIRE FROM
 METER TO SERVICE DISCONNECT AND FROM SERVICE DISCONNECT
 TO INTERIOR PANELS. THIS WIRE SIZE IS NOT RATED FOR 200
 AMPS. PROVIDE CORRECTION. NEC 310.15(B)(16); FBC RE
 E3705.1
 24. FEED TO INTERIOR PANELS FROM SERVICE DISCONNECT IS
 REQUIRED TO HAVE AN EQUIPMENT GROUNDING CONDUCTOR,
 SIZED PER CODE. PROVIDE CORRECTION. NEC 250.122; FBC RE
 E3704.6, 3607.3.1
 25. SPECIFY WIRE AND CONDUIT SIZE FOR OVERHEAD MAST TO
 FPL. WPB FBC 107.2.1; NEC 310.15(B)(7); FBC RE E3603.1
 26. GROUNDING ELECTRODE CONDUCTOR SHOULD NOT BE WIRED
 TO METER CAN AND SERVICE DISCONNECT AND INTERIOR PANEL.
 IT IS CONNECTED AT EITHER THE METER CAN OF THE FIRST
 MEANS OF DISCONNECT. PROVIDE CORRECTION. NEC 250.6
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-28 Cont ID  
Sent By jpearson Date 2018-08-28 Time 17:56 Rev Time 0.00
Received By jpearson Date 2018-08-28 Time 17:56 Sent To  
Notes
2018-08-28 17:11:02CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. AFCI PROTECTION SHOWN IN NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902
 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3603.3
 3. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9; FBC RE E3603.3
 4. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 6. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
 7. RISER DIAGRAM SHOWS A SINGLE GROUND ROD AS A
 SUPPLEMENTAL GROUNDING ELECTRODE. THIS SUPPLEMENTAL
 GROUNDING ELECTRODE NEEDS TO BE AUGMENTED BY AN
 ADDITIONAL ELECTRODE AT LEAST 6 FEET AWAY OR PROVIDE
 EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS.
 NEC 250.53(A)(2); FBC RE E3608.4
 8. A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE
 ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND
 CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF
 GROUNDING ELECTRODE SYSTEM AND WIRING. NEC 250.32; FBC
 RE E3607.3
 9. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. NEC 220; FBC RE E3602.2
 10. RECEPTACLES INSTALLED TO SERVE THE COUNTER TOP IN
 KITCHEN REQUIRE GFCI PROTECTION. PROVIDE CORRECTION.
 NEC 210.8; FBC RE E3902.6
 11. RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS SHALL
 HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8(A)(9); FBC RE E3902.9
 12. LIGHTING MUST MAINTAIN PROPER CLEARANCES FROM THE
 NEAREST POINT OF STORAGE SPACE IN A CLOTHES CLOSET.
 PROVIDE CORRECTION. NEC 410.16; FBC RE E4003.12
 13. PROVIDE LOCATION OF METER CAN AND PANEL ON PLAN.
 WPB FBC 107.2.1
 14. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR
 ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. NEC 210.8, 210.12, 210.19, 210.20,
 215.5, 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
 15. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FS
 481.229; WPB FBC 107.2.1, 107.3.5.1.2
 16. ONLY ONE SERVICE PER RESIDENTIAL ADDRESS IS
 PERMITTED. PROVIDE CORRECTION. WPB FBC 107.2.1; NEC
 230.2; FBC RE E3601.2
 17. A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A
 BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE
 DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE
 FEEDER OR BRANCH CIRCUIT. NEC 225.30
 18. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR PANEL A. NEC 225.31,
 225.32
 19. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
 20. PLAN SHOWS ONE SMALL APPLIANCE CIRCUIT FOR KITCHEN
 RECEPTACLE OUTLETS. A MINIMUM OF TWO 20 AMPERE BRANCH
 CIRCUIT SHALL BE PROVIDED TO SUPPLY KITCHEN COUNTERTOP
 RECEPTACLE OUTLET(S). PROVIDE CORRECTION. NEC
 210.11(C)(1) , FBC RE E3703.2
 21. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN.
 PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE
 E3703.4, E3901.6
 22. RECEPTACLE OUTLET SPAICNG IS NOT PER CODE. PROVIDE
 CORRECTION. NEC 210.52; FBC RE E3901
  
 DUE TO EXCESSIVE DEFICIENCIES, IT IS POSSIBLE THAT NOT
 ALL ITEMS ARE COVERED IN THIS REVIEW.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2018-10-29 Cont ID  
Sent By fmittner Date 2018-10-29 Time 16:30 Rev Time 0.00
Received By fmittner Date 2018-10-29 Time 16:30 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2018-08-24 Cont ID  
Sent By fmittner Date 2018-08-24 Time 16:13 Rev Time 0.00
Received By fmittner Date 2018-08-24 Time 16:13 Sent To  
Notes
2018-08-24 16:13:23REQUIRES HPB APPROVAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2018-11-20 Time   Rev Time 0.00
Received By lmarchan Date 2018-11-14 Time 15:22 Sent To  
Notes
2018-11-15 15:24:12RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-11-14 Cont ID  
Sent By cmontell Date 2018-11-14 Time 06:32 Rev Time 0.00
Received By cmontell Date 2018-11-14 Time 06:32 Sent To  
Notes
2018-11-06 12:59:16R32
 **TRAVELLING WITH 18080276**

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-01 Cont ID  
Sent By dbattles Date 2018-11-01 Time 09:52 Rev Time 0.00
Received By dbattles Date 2018-10-04 Time 15:31 Sent To  
Notes
2018-10-05 15:31:50LIBRARY
 **TRAVELLING WITH 18080276**

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-14 Cont ID  
Sent By dbattles Date 2018-09-14 Time 07:56 Rev Time 0.00
Received By dbattles Date 2018-08-06 Time 16:20 Sent To  
Notes
2018-08-14 10:33:58R30
2018-08-06 16:19:47LIBRARY

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2018-11-21 Cont ID  
Sent By dbattles Date 2018-11-21 Time 15:55 Rev Time 0.00
Received By dbattles Date 2018-11-21 Time 15:55 Sent To  
Notes
2018-11-21 15:55:44MU-2018-039114-0000
 PAID ON 11/20/18
 STAMP ON PLANS-OK

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-11-01 Cont ID  
Sent By dbattles Date 2018-11-01 Time 09:54 Rev Time 0.00
Received By dbattles Date 2018-11-01 Time 09:54 Sent To  
Notes
2018-11-01 09:54:49UPON APPROVAL OF ZONING AND ELECTRICAL CHECK OUT ONE
 SET TO TAKE TO COUNTY.
  
 [FBC AMENDED 109]PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-09-14 Cont ID  
Sent By dbattles Date 2018-09-14 Time 07:58 Rev Time 0.00
Received By dbattles Date 2018-09-14 Time 07:58 Sent To  
Notes
2018-09-14 07:59:12[FBC AMENDED 109]PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-11-14 Cont ID  
Sent By cmontell Date 2018-11-14 Time 06:32 Rev Time 0.00
Received By cmontell Date 2018-11-14 Time 06:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-10-31 Cont ID  
Sent By cmontell Date 2018-10-31 Time 14:56 Rev Time 0.00
Received By cmontell Date 2018-10-31 Time 14:56 Sent To  
Notes
2018-10-31 14:56:52NO PLANS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-09-05 Cont ID  
Sent By cmontell Date 2018-09-05 Time 14:06 Rev Time 0.00
Received By cmontell Date 2018-09-05 Time 13:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-10-30 Cont ID  
Sent By jesmith Date 2018-10-30 Time 09:21 Rev Time 0.00
Received By jesmith Date 2018-10-30 Time 09:20 Sent To  
Notes
2018-10-30 09:21:01PERMIT #18070946
 APPROVED
 PROVISO
 ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-09-06 Cont ID  
Sent By shill Date 2018-09-06 Time 16:16 Rev Time 0.00
Received By jesmith Date 2018-09-06 Time 15:53 Sent To  
Notes
2018-09-07 13:00:07REVIEW COMPLETED BY JERALD SMITH 0017-P STATUS OF
 REVIEW DENIED!
2018-09-06 16:15:56PERMIT 18070946
 PLUMBING COMMENTS: APPROVED
 1ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. RE: PLAN SHEET 7 OF 8
 A. WASHING MACHINE MAY NOT DISCHARGE INTO WET VENT FBC
 RES P3108.1
 B. PROVIDE MANUFACTURERS SPEC FOR WASHING MACHINE TO
 INSURE THAT 1 1/2" FIXTURE DRAIN AND STANDPIPE CAN
 ACCOMMODATE DISCHARGE OR INCREASE SIZE OF SAME TO 2".
 102.1.2 2017 WPB AMEND
 B. SHOWER FIXTURE DRAINS ARE UNDERSIZED. SIZE IN
 ACCORDANCE WITH FBC RES P2708.2
 C. SHOWER FIXTURE DRAINS CANNOT DUE TO THE LAW OF
 GRAVITY DISCHARGE INTO THE WASTE RISER ABOVE THE
 LAVATORIES. CONNECT THE FIXTURE DRAINS TO HORIZONTAL
 WET VENT(S) P3108.1 OR CONNECT TO BUILDING DRAIN AND
 INDIVIDUALLY VENT.P3105.1
 D. CONNECT DISHWASHER TO KITCHEN SINK TAILPIECE OR
 DISPOSAL FBC RES P2717.2
 E. ALL WET VENTED BATHROOM GROUP FIXTURE DRAINS ARE TO
 CONNECT INDEPENDENTLY TO WET VENT(S) P3108.1
  
 2. GENERAL NOTES:
 A. SHOWER CONTROL VALVE(S) SHALL BE PRESSURE BALANCED
 PB,THERMOSTATIC MIXING (TM) OR COMBINATION PB/TM VALVE
 TYPES WITH HIGH TEMPERATURE LIMITING STOP FBC RES
 2708.4
 B. ACCESSIBLE TEMPERATURE LIMITING DEVICE REQUIRED ON
 HOT WATER TO BATHTUB IS REQUIRED. FBC RES 2713.3
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2018-11-01 Cont ID  
Sent By dbattles Date 2018-11-01 Time 09:52 Rev Time 0.00
Received By dbattles Date 2018-11-01 Time 09:52 Sent To  
Notes
2018-11-01 09:53:31PRODUCT APPROVALS -OK
 5V METAL ROOF

Review Stop Z ZONING
Rev No 3 Status P Date 2018-11-13 Cont ID  
Sent By fmittner Date 2018-11-13 Time 15:56 Rev Time 0.00
Received By fmittner Date 2018-11-13 Time 15:56 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2018-10-29 Cont ID  
Sent By fmittner Date 2018-10-29 Time 16:31 Rev Time 0.00
Received By fmittner Date 2018-10-29 Time 16:31 Sent To  
Notes
2018-10-29 16:44:13REQUIRES SEPARATE LANDSCAPE PERMIT AND MASTER PERMIT
 SHALL INCLUDE A SITE PLAN SHOWING IMPERVIOUS AREA AT
 APPROACH.

Review Stop Z ZONING
Rev No 1 Status F Date 2018-08-24 Cont ID  
Sent By fmittner Date 2018-08-24 Time 16:12 Rev Time 0.00
Received By fmittner Date 2018-08-24 Time 16:12 Sent To  
Notes
2018-08-24 16:13:05REQUIRES HPB APPROVAL