Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-08-13 Cont ID  
Sent By tklarge Date 2018-08-13 Time 14:00 Rev Time 0.00
Received By tklarge Date 2018-08-13 Time 13:53 Sent To I
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-07-28 Cont ID  
Sent By tklarge Date 2018-07-28 Time 05:03 Rev Time 0.00
Received By tklarge Date 2018-07-28 Time 04:44 Sent To IMPACT
Notes
2018-07-28 04:46:281) THE PLANS INDICATE AN EXISTING GAS METER AND CITY
 RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS ADDRESS.
 THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED
 INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE
 EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE
 EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE
 OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM
 THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD
 OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO
 EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH
 OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
 PLEASE NOTE: IN THE FUTURE IT IS NOT NECCESSARY TO
 SUBMIT THE ENTIRE INSTALLATION MANUAL.THE MANUAL MUST
 BE ON THE JOBSITE FOR INSPECTION. SPECIFICATION SHEETS
 SHALL BE SUBMITTED SHOWING THE PRODUCT IS LISTED AND
 LABELED AND THAT THE GAS POOL HEATER HAS A MINIMUM
 THERMAL EFFICIENCY OF 82%.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-13 Cont ID  
Sent By tklarge Date 2018-08-13 Time 14:00 Rev Time 0.00
Received By tklarge Date 2018-08-07 Time 13:46 Sent To  
Notes
2018-08-08 13:46:57RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-28 Cont ID  
Sent By tklarge Date 2018-07-28 Time 05:02 Rev Time 0.00
Received By tklarge Date 2018-07-19 Time 14:41 Sent To  
Notes
2018-07-20 14:41:33PLUMB<5K