| Plan Review Stops For Permit 18070905 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2018-08-08 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-08-08 |
Time |
14:36 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-08-08 |
Time |
14:32 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-10-04 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-10-04 |
Time |
06:43 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-10-04 |
Time |
06:07 |
Sent To |
G |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-07-31 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-07-31 |
Time |
05:59 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-07-30 |
Time |
05:35 |
Sent To |
FIRE |
|
| Notes |
| 2018-07-31 05:59:21 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. NEC 702.5 STATES TRANSFER EQUIPMENT WILL BE SUITABLE | | | FOR THE INTENDED USE AND DESIGNED AND INSTALLED SO AS | | | TO PREVENT THE INADVERTANT INTERCONNECTION OF NORMAL | | | AND ALTERNATE POWER SOURCES. | | | | | | THIS DESIGN DOES NOT PREVENT THAT. THE TRANSFER SWITCH | | | IS NOT SERVICE RATED AND ALSO CONNECTED TO THE LOAD | | | SIDE OF THE SERVICE DISCONNECTING MEANS FOR THE | | | APARTMENTS. IF NORMAL POWER WAS RESTORED WHILE THE | | | TRANSFER SWITCH WAS ENGAGED PROVIDING GENERATOR POWER | | | THEN THERE WOULD BE SHORT CIRCUIT. PLEASE PROVIDE | | | CORRECTIONS. | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WPB | | | [email protected] | | | CELL: 561-657-1653 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2018-07-31 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2018-07-31 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2018-07-31 |
Time |
14:33 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2018-10-15 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-10-15 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-10-15 |
Time |
13:14 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2018-10-10 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-10-10 |
Time |
05:46 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-10-10 |
Time |
05:17 |
Sent To |
I |
|
| Notes |
| 2018-10-10 05:45:59 | PER THE MANUFACTURER'S SPECIFICATIONS FOR THE MAXITROL | | | 325-5AL REGULATOR, THE MAXIMUM INDIVIDUAL LOAD ON THE | | | REGULATOR IS 300,000 BTU'S YET THE GENERATOR IS LISTED | | | AT 473,000 BTU'S. IT APPEARS AS THOUGH THIS REGULATOR | | | CANNOT BE USED FOR THE GENERATOR. CLARIFY. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-07-28 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-07-28 |
Time |
06:37 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-07-28 |
Time |
06:09 |
Sent To |
|
|
| Notes |
| 2018-07-28 06:37:05 | 1) THE GAS PLAN SHOWS THE SYSTEM BEING INCREASED TO 2 | | | PSI BUT THE SUBMITTED SIZING TABLES ARE BOTH FOR A LESS | | | THAN 2 PSI SYSTEM. CLARIFY.SUBMIT TWO COPIES OF THE | | | APPLICABLE SIZING TABLES USED TO SIZE THE GAS SYSTEM OR | | | PLACE A NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH | | | SIZING TABLE(S) FROM THE GAS CODE OR OTHER STANDARD | | | THAT WERE USED IN THE DESIGN OF THIS GAS SYSTEM. REFER | | | TO THE 2017 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND | | | TABLES 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC. | | | G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3. | | | 2) ) SUBMIT MANUFACTURER?S SPECIFICATIONS AND | | | INSTALLATION INSTRUCTIONS FOR THE PRESSURE REGULATORS. | | | REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING | | | SHALL BE APPROVED FOR OUTDOOR INSTALLATION. IDENTIFY ON | | | THE SPECIFICATION SHEETS WHICH MODEL REGULATOR IS BEING | | | INSTALLED AND THE ORIFICE SIZE TO ENSURE THE REGULATOR | | | CAN ACCOMMODATE THE BTU LOAD THROUGH THE REGULATOR.2017 | | | FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.1. | | | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX | | | CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL | | | BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE | | | GENERATOR. 2017 FBCR SEC. G2422.1 (8), 2017 FBC-FUEL | | | GAS SEC. 411.1.3.2. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-10-15 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-10-15 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-10-15 |
Time |
13:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-10-10 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-10-10 |
Time |
05:46 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-10-01 |
Time |
13:57 |
Sent To |
|
|
| Notes |
| 2018-10-02 13:58:00 | RESUB ROUTED TO FGIAQUINTO |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-08-08 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-08-08 |
Time |
14:36 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-07-19 |
Time |
14:31 |
Sent To |
|
|
| Notes |
| 2018-07-20 14:31:40 | ROUTED TO ZONING INBOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2018-07-26 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2018-07-26 |
Time |
11:46 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2018-07-25 |
Time |
13:24 |
Sent To |
|
|
| Notes |
|
|