Plan Review Details - Permit 18070905
Plan Review Stops For Permit 18070905
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-08-08 Cont ID  
Sent By cthroop Date 2018-08-08 Time 14:36 Rev Time 0.00
Received By cthroop Date 2018-08-08 Time 14:32 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-10-04 Cont ID  
Sent By fgiaquin Date 2018-10-04 Time 06:43 Rev Time 0.00
Received By fgiaquin Date 2018-10-04 Time 06:07 Sent To G
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-31 Cont ID  
Sent By fgiaquin Date 2018-07-31 Time 05:59 Rev Time 0.00
Received By fgiaquin Date 2018-07-30 Time 05:35 Sent To FIRE
Notes
2018-07-31 05:59:21ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NEC 702.5 STATES TRANSFER EQUIPMENT WILL BE SUITABLE
 FOR THE INTENDED USE AND DESIGNED AND INSTALLED SO AS
 TO PREVENT THE INADVERTANT INTERCONNECTION OF NORMAL
 AND ALTERNATE POWER SOURCES.
  
 THIS DESIGN DOES NOT PREVENT THAT. THE TRANSFER SWITCH
 IS NOT SERVICE RATED AND ALSO CONNECTED TO THE LOAD
 SIDE OF THE SERVICE DISCONNECTING MEANS FOR THE
 APARTMENTS. IF NORMAL POWER WAS RESTORED WHILE THE
 TRANSFER SWITCH WAS ENGAGED PROVIDING GENERATOR POWER
 THEN THERE WOULD BE SHORT CIRCUIT. PLEASE PROVIDE
 CORRECTIONS.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-07-31 Cont ID  
Sent By scaldero Date 2018-07-31 Time 14:35 Rev Time 0.00
Received By scaldero Date 2018-07-31 Time 14:33 Sent To B
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2018-10-15 Cont ID  
Sent By tklarge Date 2018-10-15 Time 13:14 Rev Time 0.00
Received By tklarge Date 2018-10-15 Time 13:14 Sent To I
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-10-10 Cont ID  
Sent By tklarge Date 2018-10-10 Time 05:46 Rev Time 0.00
Received By tklarge Date 2018-10-10 Time 05:17 Sent To I
Notes
2018-10-10 05:45:59PER THE MANUFACTURER'S SPECIFICATIONS FOR THE MAXITROL
 325-5AL REGULATOR, THE MAXIMUM INDIVIDUAL LOAD ON THE
 REGULATOR IS 300,000 BTU'S YET THE GENERATOR IS LISTED
 AT 473,000 BTU'S. IT APPEARS AS THOUGH THIS REGULATOR
 CANNOT BE USED FOR THE GENERATOR. CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-07-28 Cont ID  
Sent By tklarge Date 2018-07-28 Time 06:37 Rev Time 0.00
Received By tklarge Date 2018-07-28 Time 06:09 Sent To  
Notes
2018-07-28 06:37:051) THE GAS PLAN SHOWS THE SYSTEM BEING INCREASED TO 2
 PSI BUT THE SUBMITTED SIZING TABLES ARE BOTH FOR A LESS
 THAN 2 PSI SYSTEM. CLARIFY.SUBMIT TWO COPIES OF THE
 APPLICABLE SIZING TABLES USED TO SIZE THE GAS SYSTEM OR
 PLACE A NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH
 SIZING TABLE(S) FROM THE GAS CODE OR OTHER STANDARD
 THAT WERE USED IN THE DESIGN OF THIS GAS SYSTEM. REFER
 TO THE 2017 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND
 TABLES 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC.
 G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3.
 2) ) SUBMIT MANUFACTURER?S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE PRESSURE REGULATORS.
 REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING
 SHALL BE APPROVED FOR OUTDOOR INSTALLATION. IDENTIFY ON
 THE SPECIFICATION SHEETS WHICH MODEL REGULATOR IS BEING
 INSTALLED AND THE ORIFICE SIZE TO ENSURE THE REGULATOR
 CAN ACCOMMODATE THE BTU LOAD THROUGH THE REGULATOR.2017
 FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.1.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX
 CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL
 BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR. 2017 FBCR SEC. G2422.1 (8), 2017 FBC-FUEL
 GAS SEC. 411.1.3.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-10-15 Cont ID  
Sent By tklarge Date 2018-10-15 Time 13:14 Rev Time 0.00
Received By tklarge Date 2018-10-15 Time 13:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-10 Cont ID  
Sent By tklarge Date 2018-10-10 Time 05:46 Rev Time 0.00
Received By tklarge Date 2018-10-01 Time 13:57 Sent To  
Notes
2018-10-02 13:58:00RESUB ROUTED TO FGIAQUINTO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-08 Cont ID  
Sent By cthroop Date 2018-08-08 Time 14:36 Rev Time 0.00
Received By cthroop Date 2018-07-19 Time 14:31 Sent To  
Notes
2018-07-20 14:31:40ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2018-07-26 Cont ID  
Sent By mcruz Date 2018-07-26 Time 11:46 Rev Time 0.00
Received By mcruz Date 2018-07-25 Time 13:24 Sent To  
Notes
***NONE***