Plan Review Details - Permit 18070900
Plan Review Stops For Permit 18070900
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-11-26 Cont ID  
Sent By rmcdouga Date 2018-11-26 Time 08:59 Rev Time 0.00
Received By rmcdouga Date 2018-11-26 Time 08:59 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-07-31 Cont ID  
Sent By rmcdouga Date 2018-07-31 Time 11:37 Rev Time 0.00
Received By rmcdouga Date 2018-07-31 Time 11:37 Sent To I
Notes
2018-07-31 11:40:41PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD ENGINEERING IS REQUIRED TO HAVE
 THE ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE.
 61G15-23.003 PROCEDURES FOR PHYSICALLY SIGNING AND
 SEALING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS.
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN
 ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025,
 F.S., AND RULE 61G15-23.001, F.A.C. MUST BE PHYSICALLY
 SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE
 USED.
 (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY
 CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY
 OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL
 NOT RENDER THE SIGNATURE ILLEGIBLE.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-07-27 Cont ID  
Sent By jleahy Date 2018-07-27 Time 13:17 Rev Time 0.00
Received By jleahy Date 2018-07-27 Time 13:17 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-11-26 Cont ID  
Sent By tklarge Date 2018-11-26 Time 05:18 Rev Time 0.00
Received By tklarge Date 2018-11-26 Time 04:57 Sent To B
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-07-28 Cont ID  
Sent By tklarge Date 2018-07-28 Time 07:06 Rev Time 0.00
Received By tklarge Date 2018-07-28 Time 06:37 Sent To  
Notes
2018-07-28 07:06:401) THE SUBMITTED GAS PLAN REFERS TO THE 2007 FBC.AND
 ALSO THE 2017 FBC. REMOVE THE REFERENCE TO THE 2007
 FBC.
 2) THE GAS PLAN REFERS TO TABLE 402.4(20). THIS SIZING
 TABLE IS FOR A LESS THAN 2 PSI SYSTEM YET THE GAS PLAN
 CALLS OUT A 2 PSI SYSTEM. CLARIFY.
 3) SHOW THE LOCATION OF ALL SHUTOFF VALVES AND
 REGULATORS. A LISTED SHUTOFF VALVE IS REQUIRED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. 2017 FBCR SEC.
 G2420.4.
 4) SHOW THE TYPE OF PIPE AND PIPE SIZE AT THE OUTLET OF
 THE 2 PSI METER . WPB AMEND. TO FBC SEC. 107.2.1.
 5) ) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX
 CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL
 BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR. 2017 FBCR SEC. G2422.1 (8), 2017 FBC-FUEL
 GAS SEC. 411.1.3.2.
 6) A SEDIMENT TRAP IS REQUIRED AT THE GENERATOR.2017
 FBC-FUEL GAS SEC.408.4.
 7) SUBMIT MANUFACTURER?S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE PRESSURE REGULATORS.
 REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING
 SHALL BE APPROVED FOR OUTDOOR INSTALLATION. IDENTIFY ON
 THE SPECIFICATION SHEETS WHICH MODEL REGULATOR IS BEING
 INSTALLED AND THE ORIFICE SIZE TO ENSURE THE REGULATOR
 CAN ACCOMMODATE THE BTU LOAD THROUGH THE REGULATOR.2017
 FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.1.
 8) AN MP REGULATOR IS REQUIRED AT THE GENERATOR.
 9) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-26 Cont ID  
Sent By rmcdouga Date 2018-11-26 Time 08:59 Rev Time 0.00
Received By rmcdouga Date 2018-11-02 Time 11:30 Sent To  
Notes
2018-11-06 11:31:02RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-31 Cont ID  
Sent By rmcdouga Date 2018-07-31 Time 11:38 Rev Time 0.00
Received By rmcdouga Date 2018-07-19 Time 14:34 Sent To  
Notes
2018-07-20 14:34:46ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 3 Status P Date 2018-11-27 Cont ID  
Sent By mcruz Date 2018-11-27 Time 11:34 Rev Time 0.00
Received By mcruz Date 2018-11-27 Time 11:30 Sent To PC
Notes
2018-11-27 11:34:12ZONING PASSED WITH PROVISO: GENERATOR SHALL BE AT LEAST
 6' FROM NORTH PROPERTY LINE.

Review Stop Z ZONING
Rev No 2 Status F Date 2018-11-09 Cont ID  
Sent By mcruz Date 2018-11-09 Time 09:21 Rev Time 0.00
Received By mcruz Date 2018-11-09 Time 09:19 Sent To G
Notes
2018-11-09 09:21:12ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) REPEAT COMMENT - PURSUANT TO 94-305(B)(4) -
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET
 INTO A SETBACK. GENERATOR SHALL BE AT LEAST 6' FROM
 NORTH PROPERTY LINE.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2018-07-25 Cont ID  
Sent By mcruz Date 2018-07-25 Time 13:24 Rev Time 0.00
Received By mcruz Date 2018-07-25 Time 13:20 Sent To  
Notes
2018-07-25 13:24:03ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) PURSUANT TO 94-305(B)(4) - MECHANICAL EQUIPMENT MAY
 NOT PROJECT MORE THAN 4 FEET INTO A SETBACK. GENERATOR
 SHALL BE AT LEAST 6' FROM NORTH PROPERTY LINE.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]