Plan Review Details - Permit 18070884
Plan Review Stops For Permit 18070884
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-01-25 Cont ID  
Sent By dbattles Date 2019-01-25 Time 12:04 Rev Time 0.00
Received By dbattles Date 2019-01-25 Time 12:04 Sent To  
Notes
2019-01-30 09:37:37**********************************ZONING
 PROVISO*******************************************
  
 PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY,
 THE FOLLOWING CONDITIONS SHALL BE ADDRESSED:
  
 1. A LANDSCAPE PERMIT, WHICH INCLUDES A LANDSCAPE PLAN,
 SHALL BE SUBMITTED TO THE BUILDING DIVISION FOR REVIEW.
  
 2. THE LANDSCAPE MATERIAL SHOWN ON THE APPROVED
 LANDSCAPE PERMIT SHALL BE INSTALLED AND PASS A FINAL
 LANDSCAPE INSPECTION.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISON
 561-822-1449
 [email protected]
2019-01-25 12:06:03PROVISOS:
 1. PROVIDE STAIRCASE AND GUARD RAIL ENGINEERING.
 2. PROVIDE PRODUCT APPROVALS FOR ALL EXTERIOR OPENINGS
 EXCEPT GARAGE DOOR. GARAGE DOOR WAS REVIEWED NOA
 17-0215.09

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-01-11 Cont ID  
Sent By dbattles Date 2018-12-21 Time 07:44 Rev Time 0.00
Received By dbattles Date 2018-12-21 Time 07:43 Sent To  
Notes
2018-12-21 07:49:03PROVISOS:
 1. PROVIDE STAIRCASE AND GUARD RAIL ENGINEERING.
 2. PROVIDE PRODUCT APPROVALS FOR ALL EXTERIOR OPENINGS
 EXCEPT GARAGE DOOR. GARAGE DOOR WAS REVIEWED NOA
 17-0215.09

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-09-24 Cont ID  
Sent By dbattles Date 2018-09-24 Time 12:30 Rev Time 0.00
Received By dbattles Date 2018-09-21 Time 15:20 Sent To  
Notes
2018-09-24 12:31:40****CORRECTIONS****
 W.P.B. PERMIT: 18070884
 REVIEWED: SEPTEMBER 24, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 I DID A PARTIAL REVIEW TO TRY AND GET THE INFORMATION
 NEEDED FOR A FULL REVIEW ON THE RE-SUBMITTAL.
 ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 1. IN DRAWING FOLDER THE PLANS CS-1 AND A001-A601 ARE
 IN DWG. FORMAT. PLEASE UPLOAD NEW PLANS IN PDF. FORMAT
 WITH DIGITAL SIGNATURE AND PLACE A DIGITALLY CREATED
 IMAGE OF YOUR SEAL AND THE FOLLOWING SENTENCES WHERE AN
 ORIGINAL SIGNATURE WOULD APPEAR IF THE ITEM WERE BEING
 PHYSICALLY SIGNED, DATED AND SEALED. THE SENTENCES CAN
 BE PART OF THE DIGITAL SIGNATURE CUSTOM APPEARANCE
 AVAILABLE IN THE SIGNING TOOL, OR THEY CAN BE PLACED ON
 THE DOCUMENT OUTSIDE OF THE DIGITAL SIGNATURE BLOCK.
 "THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY
 [LICENSEE, RA, OR LS] ON THE DATE AND/OR TIME STAMP
 SHOWN USING A DIGITAL SIGNATURE". (SEE SIGNATURE REVIEW
 FOR ADDITIONAL REVIEWERS COMMENTS)
  
 2. LAYOUTS & FABRICATION DRAWINGS (320 PAGES) WERE
 UPLOADED IN BOTH SUPPORTING DOCUMENTS AND DRAWINGS
 FOLDER. THIS IS PROBABLY BECAUSE SOME OF THE
 INFORMATION IS TYPICALLY IN DRAWINGS (FRAMING PLANS AND
 STRUCTURAL PLANS), AND TRUSS ENGINEERING IS USUALLY A
 SUPPORTING DOCUMENT.
 CAN THIS BE SPLIT UP SO THAT STRUCTURAL DRAWINGS ARE IN
 THE DRAWING FOLDER AND SUPPORTING TRUSS PLANS CAN GO IN
 SUPPORTING DOCS?
 IDEALLY, I WOULD LIKE TO SEE FLOOR FRAMING PLAN, ROOF
 FRAMING PLAN AND STRUCTURAL DETAILS ON INDIVIDUAL
 DRAWINGS SHEETS TO THE DRAWINGS FOLDER AND THE TRUSS
 SHOP DWG?S CAN BE A MULTI PAGE FILE UPLOADED TO THE
 SUPPORTING DOCS FILE.
 THE TRUSS SUBMITTAL CAN BE APPROVED NOW IF PUT IN
 SUPPORTING DOCUMENTS AS A SUBMITTAL, OR IT CAN BE
 DEFERRED. IF DEFERED THE TRUSS PACKAGE NEEDS TO BE
 REVIEWED BY BUILDING INSPECTOR PRIOR TO INSTALLATION.
 EXCERT FROM DIGITAL PLAN REVIEW GUIDE:
 EACH PLAN PAGE SHALL BE SAVED AS A SEPARATE PDF FILE
 AND SHOULD BE IN LANDSCAPE FORMAT. CAD DRAWINGS SHALL
 BE SAVED INTO A PDF FILE FORMATTED IN SINGLE LAYER
 BLACK AND WHITE (MONOCHROME) SETTING.
  
 3. IS THIS A PRE-FABRICATED STRUCTURE? IF SO THE
 DOCUMENTS FOR THAT PORTION CAN GO INTO THE SUPPORTING
 DOCUMENT FOLDER WHILE ON-SITE CONSTRUCTION DRAWINGS
 SHOULD BE IN THE DRAWING FOLDER.
  
 4. THE PLANS CALL FOR A SPECIAL INSPECTOR. IS THAT
 INSPECTOR NEEDED FOR ON-SITE INSPECTIONS?
 IF SO CONTACT ME SO I CAN SEND YOU INFORMATION ON WHAT
 IS REQUIRED FOR SPECIAL INSPECTOR, OR INDICATE THAT THE
 SPECIAL INSPECTOR IS JUST FOR OFF-SITE PRE-FABRICATION.
  
 5. SHEET A202 HAS NO DRAWINGS IN IT. PLEASE ADD
 DRAWINGS OR REMOVE FROM SET. ARE THE FOUR IDF
 RENDERINGS SUPPOSED TO BE IN SHEET A202? THEY WOULD BE
 BETTER OFF IN A DRAWING SHEET AS JUST A JPG MAKES THE
 DRAWING SET HARDER TO PRINT OUT AS A COMPLETE FIELD
 SET. IF THOSE JPGS ARE BEING LOADED TO ATTACH TO A DWG
 THEY WILL NOT BE NEEDED ONCE PDF'S REPLACE THE DWG
 SHEETS. PLEASE REMOVE THE FOUR IDF RENDERINGS FROM
 DRAWINGS FOLDER OR PUT THEM IN SUPPORTING DOCS FOLDER.
  
 6. [FBC 107.3.5.3]PROVIDE SEDIMENT CONTROL PLAN TO KEEP
 CONSTRUCTION DEBRIS FROM ENTERING ADJACENT PROPERTIES
 AND STORM DRAINS DURING CONSTRUCTION. YOU CAN FIND
 ENGINEERING STANDARD DETAILS FROM WPB WEBSITE-POLLUTION
 CONTROL
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 7. PROVIDE SURVEY TO SHOW NEW STRUCTURE ON THE NEWLY
 DIVIDED LOT.
  
 8. [FBC R401.3]PROVIDE SITE DRAINAGE PLAN.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN
 SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE
 SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE
 FIRST 10 FEET (3048 MM).
 [FBC R403.1.7.3] FOUNDATION ELEVATION.
 ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION
 SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER
 AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED
 DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2
 PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO
 THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN
 BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF
 DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT
 ALL LOCATIONS ON THE SITE.
  
 9. EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING.
  
 10. [FBC R309.1]FLOOR SURFACE.
 GARAGE FLOOR SURFACES SHALL BE OF APPROVED
 NONCOMBUSTIBLE MATERIAL.
 THE AREA OF FLOOR USED FOR PARKING OF AUTOMOBILES OR
 OTHER VEHICLES SHALL BE SLOPED TO FACILITATE THE
 MOVEMENT OF LIQUIDS TO A DRAIN OR TOWARD THE MAIN
 VEHICLE ENTRY DOORWAY.
 SHOW SLOPE OF GARAGE AS APPLICABLE.
  
 11. [FBC R302.5.1] OTHER OPENINGS BETWEEN THE GARAGE
 AND RESIDENCE SHALL BE EQUIPPED WITH SOLID WOOD DOORS
 NOT LESS THAN 1 3/8 INCHES (35 MM) IN THICKNESS, SOLID
 OR HONEYCOMB-CORE STEEL DOORS NOT LESS THAN 1 3/8
 INCHES (35 MM) THICK, OR 20-MINUTE FIRE-RATED DOORS. I
 CAN?T SEE CALL OUT ON THE DWG SHEET, BUT THIS WILL
 APPLY TO RE-SUBMITTAL.
  
 12. [R302.6]GARAGE CEILING TO HAVE TYPE NOT LESS THAT
 5/8? TYPE X OR EQUIVELANT DRYWALL WHEN HABITABLE SPACE
 IS PROVIDED ABOVE. SHOW IN PLANS.
  
 13. [FBC R807]IF ATTIC ACCESS IS PROVIDED, SHOW ON
 PLANS AND PROVIDE DETAIL TO MEET [FBC ENERGY R402.2.4].
  
 14. [FBC ENERGY TABLE R402.2.6]STEEL-FRAME CEILING,
 WALL AND FLOOR INSULATION (R-VALUE)
 USE THIS TABLE TO DETERMINE R-VALUES NEEDED FOR STEEL
 FRAMED CEILINGS, WALLS AND FLOORS.
  
 15. [FBC ENERGY R401.3]PROVIDE ENERGY PERFORMANCE LEVEL
 (ELP)DISPLAY CARD WITH THE ENEGRY CALCULATIONS TO SHOW
 ESTIMATED ENERGY PERFORMANCE LEVEL. THIS CARD IS TO BE
 SIGNED BY BUILDER AND AVAILABLE FOR INSPECTOR TO REVIEW
 FOR BUILDING FINAL.
  
 16. [FBC AMENDED 107.2.1.2]PROVIDE PRODUCT APPROVALS
 FOR ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM
 DEFFERED (RIDGE VENT, SHINGLE AND UNDERLAYMENT)
  
 17. [FBC R803.2.3.1]SHEATHING FASTENING.
 SHOW HOW ROOF SHEATHING IS ATTACHED TO FRAMING IN ROOF
 ZONES 1,2 &3(CONNECTOR AND SPACING). TABLE R804.3 FOR
 COLD-FORMED STEEL ROOF FRAMING
  
 18. [FBC 1014]GUARDS AND HANDRAILS. [FBC 1607.8]LOADS
 ON HANDRAILS AND GUARDRAILS.
 PROVIDE HANDRAIL AND GUARDRAIL ENGINEERING, OR INDICATE
 THAT YOU WOULD LIKE IT DEFERRED.
  
 19. [FBC R318]INDICATE THE MEANS OF TERMITE PROTECTION
 PROPOSED AND REFERENCE SECTION R308 FOR STANDARDS.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-02-06 Cont ID  
Sent By cthroop Date 2019-02-06 Time 16:15 Rev Time 0.00
Received By cthroop Date 2019-02-06 Time 15:16 Sent To  
Notes
2019-02-06 16:16:15PROVIDE PDF OF ELECTRICAL PLANS SIGNED BY DESIGNER.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-12-23 Cont ID  
Sent By jpearson Date 2018-12-23 Time 10:33 Rev Time 0.00
Received By jpearson Date 2018-12-23 Time 10:33 Sent To  
Notes
2018-12-23 10:33:52CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ALL PREVIOUS COMMENTS CORRECTED. PLAN WILL BE
 APPROVED WHEN CORRECT DIGITALLY SIGNED PDF'S WITH 3RD
 PARTY VERIFICATION ARE SUBMITTED. FS 471/481; WPB FBC
 107.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-09-03 Cont ID  
Sent By jpearson Date 2018-09-03 Time 10:56 Rev Time 0.00
Received By jpearson Date 2018-09-03 Time 10:56 Sent To  
Notes
2018-09-03 10:56:10CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3603.3
 2. BE ADVISED THAT GENERATOR AND SWIMMING POOLS ARE NOT
 INCLUDED IN THE SCOPE OF THIS PLAN REVIEW. PROVIDE A
 BLOCK NOTE INDICATING THE REQUIRED SEPARATE PERMITS AND
 PLAN SUBMITTALS FOR THESE SYSTEMS. WPB FBC 105.1,
 107.2.1
 3. PROVIDE ACCURATE RISER DIAGRAM, SHOWING ALL DETAILS
 OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. THERE ARE MANY
 DISCREPANCIES BETWEEN RISER DIAGRAM AND PANEL
 SCHEDULES. A 600 AMP MDP IS SHOWN, A GENERATOR IS
 SPECIFIED AS 22KW IN ONE LOCATION AND 30KW IN ANOTHER,
 ETC. PROVIDE CORRECTIONS. NEC 215.5, 230, 250.50,
 250.94, 408.30; FBC RE E3706.1, E3608.1, E3609.3; WPB
 FBC 107.2.1
 4. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
 5. IS THIS AREA LOCATED TO THE LEFT OF THE REFRIGERATOR
 A COUNTER SPACE? NO COUNTER RECEPTACLE IS SHOWN.
 PROVIDE CLARIFICATION AND/OR CORRECTION. NEC
 210.52(C)(1); FBC RE E3901
 6. LIGHTS OVER MASTER TUB ARE SHOWN AS STANDARD RECESS
 LIGHTS. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE
 SUITABLE FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC
 410.10(D); FBC RE E4003.11
 7. LIGHTS IN CLOSET ARE SHOWN AS STANDARD RECESS
 LIGHTS. LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS
 AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE
 PERMITTED IN CLOTHES CLOSETS. PROVIDE CORRECTION. NEC
 410.16; FBC RE E4003.12
 8. AREA MARKED AS "STUDY" ON PLAN REQUIRES SMOKE ALARM
 AND A CARBON MONOXIDE ALARM WITHIN 10 FEET OF THE ROOM,
 AS IT MEETS THE DEFINITION OF A BEDROOM IN THE FLORIDA
 STATUTES AND COULD BE USED FOR THIS PURPOSE. PROVIDE
 CORRECTION. FS 381.065(2)(B)(1); FBC RE 314, 315
 9. SMOKE ALARMS MUST BE INSTALLED AT LEAST 3 FEET FROM
 BATHROOM DOOR, 3 FEET FROM CEILING FANS, AND 3 FEET
 FROM ANY MECHANICAL DUCT. PROVIDE CORRECTIONS. FBC RE
 R314.3(4), NFPA 72:29.8.3.4
 10. NOTE 32 STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE E4002.14
 11. AFCI PROTECTION SHOWN IN NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902
 12. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2019-02-06 Cont ID  
Sent By cthroop Date 2019-02-06 Time 16:14 Rev Time 0.00
Received By cthroop Date 2019-02-06 Time 15:16 Sent To  
Notes
2019-02-06 16:15:22PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS FOR GAS
 APPLIANCES.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-12-31 Cont ID  
Sent By cthroop Date 2018-12-31 Time 16:59 Rev Time 0.00
Received By cthroop Date 2018-12-31 Time 13:20 Sent To  
Notes
2018-12-31 17:01:39GAS PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS FOR
 ALL GAS APPLIANCES.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-09-20 Cont ID  
Sent By lcrespo Date 2018-09-20 Time 20:29 Rev Time 0.00
Received By lcrespo Date 2018-09-20 Time 19:45 Sent To  
Notes
2018-09-20 20:27:4909/19/2018 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC FUEL GAS RES. SEC.
 G2420.4
  
 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC FUEL GAS RES. SEC. G2407.1 AND G2439.4. (RANGE AND
 OR HEATER)
  
 3. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. INDICATE THE DELIVERY PRESSURE (PSI ON ISOMETRIC) OF
 THE SYSTEM ON THE PLAN PER 2017 FBC FUEL GAS SEC. 402.2
 OR 2017 FBC FUEL GAS RES. SEC. G2413.2.
  
 5. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE,
 TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING
 DETAILS OF THE GAS VENT(S) PER 2017 FBC FUEL GAS RES.
 SECS. G2426 THRU G2429.1.
  
 6. SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS SEC.305.1 OR
 2017 FBC FUEL GAS RES. SEC. G2408.1.
  
 7. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION 2017 FBC FUEL
 GAS RES. SEC. G2413.2 AND G2404.3.
  
 8. INDICATION ON THE PLAN THAT THE GRILL IS LOCATED
 UNDER A ROOF, IT MAY REQUIRE A HOOD PER MANUAL, PLEASE
 SUBMIT MANUFACTURES SPECIFICATIONS FOR THE GRILL. 2017
 FBC FG RES. SEC.G2408.1.
  
 9. SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE
 GENERATOR AND THEY SHALL BE ONSITE FOR FINAL GAS
 INSPECTION. THE GENERATOR SHALL BE LISTED AND APPROVED.
 NFPA 58 SEC. 5.20.1. THE GENERATOR SHALL MEET THE
 REQUIREMENTS OF UL 2200.
  
 10. THE GENERATOR SHALL BE ONE FOOT SIX INCHES (1'-6")
 FROM THE HOUSE, FIVE (5'-0") FROM THE PROPERTY LINE,
 EXHAUST SHALL BE TEN (10'-0") FROM ANY OPENING UNLESS
 OTHERWISE STATED IN THE MANUFACTURES SPECIFICATION
 INSTRUCTIONS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-02-07 Cont ID  
Sent By dbattles Date 2019-02-07 Time 11:21 Rev Time 0.00
Received By cthroop Date 2019-01-23 Time 08:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-01-15 Cont ID  
Sent By dbattles Date 2019-01-15 Time 14:43 Rev Time 0.00
Received By dbattles Date 2018-12-10 Time 15:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-16 Cont ID  
Sent By lmarchan Date 2018-10-16 Time 07:56 Rev Time 0.00
Received By lmarchan Date 2018-08-16 Time 11:00 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2019-06-28 Cont ID  
Sent By lmarchan Date 2019-06-28 Time 14:54 Rev Time 0.00
Received By lmarchan Date 2019-02-08 Time 10:33 Sent To  
Notes
2019-06-28 14:55:08RECEIPT - MU-2019-4471 - $9904.34 - PAID
2019-02-08 10:33:302/8/19 SENT EMAIL TO IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-12-31 Cont ID  
Sent By cthroop Date 2018-12-31 Time 16:56 Rev Time 0.00
Received By cthroop Date 2018-12-31 Time 13:20 Sent To  
Notes
2018-12-31 16:57:44PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-09-24 Cont ID  
Sent By dbattles Date 2018-09-24 Time 12:31 Rev Time 0.00
Received By dbattles Date 2018-09-24 Time 12:31 Sent To  
Notes
2018-09-24 12:33:08[FBC AMENDED 109]PLANS WILL BE REVIEWED BY THE PBC
 IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON
 NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR
 WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE
 WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY
 UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE
 R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU
 ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE
 UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-01-29 Cont ID  
Sent By cmontell Date 2019-01-29 Time 13:42 Rev Time 0.00
Received By cmontell Date 2019-01-29 Time 13:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-12-21 Cont ID  
Sent By cmontell Date 2018-12-21 Time 14:19 Rev Time 0.00
Received By cmontell Date 2018-12-21 Time 14:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-10-15 Cont ID  
Sent By cmontell Date 2018-10-15 Time 14:49 Rev Time 0.00
Received By cmontell Date 2018-10-15 Time 14:45 Sent To  
Notes
2018-10-15 14:49:44MECHANICAL PLAN REVIEW FAIL
  
 1 - NEED ENERGY CALC PER FBC ENERGY CONSERVAITION SEC.
 405
 2 - NEED EQUIPMENT SIZING PER FBC ENERGY CONSERVAITION
 SEC. 403.7.1
  
 CHRIS MONTELLO
 561-805-6733

Review Stop P PLUMBING
Rev No 4 Status P Date 2019-02-07 Cont ID  
Sent By cthroop Date 2019-02-07 Time 11:21 Rev Time 0.00
Received By cthroop Date 2019-02-07 Time 11:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-01-28 Cont ID  
Sent By cmontell Date 2019-01-28 Time 13:02 Rev Time 0.00
Received By cmontell Date 2019-01-28 Time 12:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-12-31 Cont ID  
Sent By cthroop Date 2018-12-31 Time 16:59 Rev Time 0.00
Received By cthroop Date 2018-12-31 Time 13:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-09-20 Cont ID  
Sent By lcrespo Date 2018-09-20 Time 19:42 Rev Time 0.00
Received By lcrespo Date 2018-09-20 Time 06:15 Sent To  
Notes
2018-09-20 19:44:5209/19/2018 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A BACKFLOW PERMIT REQUIRED BY A LICENSED CONTRACTOR
 AND MUST BE CERTIFIED BY UTILITIES PRIOR TO FINAL
 INSPECTION. PLEASE CONTACT CITY OF WPB UTILITIES AT
 561-822-2240 FOR FURTHER DIRECTIONS.
  
 2. THE BACKFLOW IS NOT A LEAD-FREE DEVICE WHICH IS
 REQUIRED BY THE CITY OF WEST PALM BEACH UTILITY
 DEPARTMENT. YOU CAN REFER TO THEIR CROSS CONNECTION
 MANUAL IN THE CITY WEB SITE HTTP://WPB.ORG/DEPARTMENTS/
 PUBLIC-UTILITIES/FORMS-PUBLICATIONS/BACKFLOW-CROSS-CON
 NECTION-CONTROL-MANUAL FOR MORE INFORMATION.
  
 3. ON DOWNSTAIRS AND UPSTAIRS CLEAN OUTS NOT REQUIRED
 ON THE STACK. THE TOILETS MAY RUN FLAT AND ONLY ON VENT
 REQUIRED TO REDUCE VENTING. IN MASTER, A VENT IS
 REQUIRED BETWEEN THE TUB AND SHOWER, 2017 FBC R3101.2
 TRAP SEAL PROTECTION.
  
 4. ROMAN TUB STANDALONE REQUIRED A CONTROL VALVE BY A
 WATER TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3, EXCEPT WHERE SUCH PROTECTION IS
 OTHERWISE PROVIDED BY A COMBINATION TUB/SHOWER VALVE IN
 ACCORDANCE WITH SECTION P2708.4. FBC R 2713.3 BATHTUB
 AND WHIRLPOOL BATHTUB VALVES.
  
 5. IF THE SHOWER PAN IS NOT RECEDED IT WILL REQUIRE
 LINING. THE ADJOINING WALLS AND FLOOR FRAMING ENCLOSING
 ON-SITE BUILT-UP SHOWER RECEPTORS SHALL BE LINED.
 SHOWER PAN MUST HAVE A SLOPED MORTAR BED THAT IS
 PRE-PITCHED BENEATH PRIOR TO LINER INSTALLATION OF 1/4"
 IN PER FOOT TOWARD THE DRAIN, MUST HAVE DAM CORNER,
 BACKING AROUND THE PERIMETER AND BEFORE FINAL MORTAR
 APPLICATION PLACE SOME PEA GRAVEL OVER WEEP HOLES SO
 THE MORTAR DOESN'T COVER THEM PER MANUFACTURES
 SPECIFICATIONS. 2017 FBC R2709.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2019-01-11 Cont ID  
Sent By dbattles Date 2019-01-11 Time 15:34 Rev Time 0.00
Received By dbattles Date 2019-01-11 Time 15:34 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2019-02-11 Cont ID  
Sent By dbattles Date 2019-02-11 Time 15:19 Rev Time 0.00
Received By dbattles Date 2019-02-08 Time 09:36 Sent To  
Notes
2019-02-11 15:20:36ARCHITECTURAL, MEP AND SURVEY ARE MULTI PAGE DOCUMENTS
 IN SIGNATURE FOLDER AND DIGITALLY SIGNED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2019-02-07 Cont ID  
Sent By dbattles Date 2019-02-07 Time 09:45 Rev Time 0.00
Received By dbattles Date 2019-01-25 Time 10:18 Sent To  
Notes
2019-01-31 16:54:07CUSTOMER IS UPLOADING MULTI FILE DOCUMENT AFTER REVIEWS
 ARE COMPLETE. DB

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-12-23 Cont ID  
Sent By jpearson Date 2018-12-23 Time 09:48 Rev Time 0.00
Received By jpearson Date 2018-12-23 Time 09:48 Sent To  
Notes
2018-12-23 09:48:53MECHANICAL PAGES ARE NOT DIGITALLY SIGNED AND SEALED.
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET)
 IS REQUIRED TO BEAR THE NAME AND BE SIGNED AND SEALED
 BY THE PERSON RESPONSIBLE FOR THE DESIGN. PROVIDE
 CORRECTION. ADDITIONALLY, SOME OF THE FILES PROVIDED
 ARE DWG FILES, PROVIDE PDF FOR EACH PAGE. WPB FBC
 107.1, 107.2; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-09-03 Cont ID  
Sent By jpearson Date 2018-09-03 Time 10:12 Rev Time 0.00
Received By jpearson Date 2018-09-03 Time 10:11 Sent To  
Notes
2018-09-25 12:57:22MECHANICAL PAGES ARE NOT DIGITALLY SIGNED AND SEALED.
2018-09-03 10:11:29CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET)
 IS REQUIRED TO BEAR THE NAME AND BE SIGNED AND SEALED
 BY THE PERSON RESPONSIBLE FOR THE DESIGN. PROVIDE
 CORRECTION. ADDITIONALLY, SOME OF THE FILES PROVIDED
 ARE DWG FILES, PROVIDE PDF FOR EACH PAGE. WPB FBC
 107.1, 107.2; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2019-06-26 Cont ID  
Sent By dbattles Date 2019-06-26 Time 16:00 Rev Time 0.00
Received By dbattles Date 2019-06-26 Time 16:00 Sent To  
Notes
2019-06-26 16:01:17IN PROGRESS FOR RESIDENT INSPECTOR FOR SPECIAL
 CONSTRUCTION TYPE.
 WORKING WITH SPENCER BLANK TO GET THE ENGINEER
 APPROVED.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2019-01-25 Cont ID  
Sent By dbattles Date 2019-01-25 Time 12:07 Rev Time 0.00
Received By dbattles Date 2019-01-25 Time 12:07 Sent To  
Notes
2019-01-25 12:07:12DB IS WORKING WITH THE CONTRACTOR TO GET THE DOCUMENTS
 FOR RESIDENT INSPECTOR.
 THIS WILL BECOME A PROVISO IF NOT COMPLETED PRIOR TO
 IMPACT FEE BEING APPROVED.
 HOWEVER, THE RESIDENT INSPECTORS AGREEMENT NEEDS TO BE
 APPROVED PRIOR TO ANY INSPECTIONS OCCURING.

Review Stop Z ZONING
Rev No 3 Status P Date 2019-01-30 Cont ID  
Sent By awooten Date 2019-01-30 Time   Rev Time 0.00
Received By awooten Date 2019-01-30 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2019-01-14 Cont ID  
Sent By awooten Date 2019-01-14 Time   Rev Time 0.00
Received By awooten Date 2019-01-14 Time   Sent To  
Notes
2019-01-14 15:02:45******************************************ZONING REVIEW
 FAILED (REPEAT COMMENTS)*******************************
 ******************************
  
 PLEASE PROVIDE A SURVEY OF THE PROPERTY.
  
 THE REQUIRED CORNER SETBACK ON GEORGIA IS 12.5 FEET.
  
 THE REAR SETBACK IS 10% OF THE LOT DEPTH OR 15 FEET,
 WHICHEVER IS THE LESSER NUMBER.
  
 POOLS, FENCES AND MECHANICAL EQUIPMENT REQUIRE A
 SEPARATE PERMIT.
  
 STRUCTURAL INTRUSIONS. STRUCTURAL OVERHANGS, INCLUDING
 BUT NOT LIMITED TO BALCONIES, CORNICES, GUTTERS, EAVES,
 AND ROOF OVERHANG PROJECTIONS SHALL NOT EXTEND FARTHER
 THAN THREE FEET INTO ANY SETBACK. PLEASE SHOW
 STRUCTURAL OVERHANG PROJECTIONS FOR BALCONIES.
  
 PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT.
  
 SHOWING THE FOLLOWING:
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 GROSS LOT SQUARE FOOTAGE MINUS
 BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE OR
 PORTION THEREOF
 ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE OR
 PORTION THEREOF
  
 MORE COMMENTS MAY FOLLOW FURTHER REVIEW.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 ZONING DIVISION
 561-822-1449
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-09-05 Cont ID  
Sent By awooten Date 2018-09-05 Time   Rev Time  
Received By awooten Date 2018-09-05 Time   Sent To  
Notes
2018-09-05 15:54:12******************************************ZONING REVIEW
 FAILED************************************************
 *************************************************
  
 PLEASE PROVIDE A SURVEY OF THE PROPERTY.
  
 THE REQUIRED CORNER SETBACK ON GEORGIA IS 12.5 FEET.
  
 THE REAR SETBACK IS 10% OF THE LOT DEPTH OR 15 FEET,
 WHICHEVER IS THE LESSER NUMBER.
  
 POOLS, FENCES AND MECHANICAL EQUIPMENT REQUIRE A
 SEPARATE PERMIT.
  
 STRUCTURAL INTRUSIONS. STRUCTURAL OVERHANGS, INCLUDING
 BUT NOT LIMITED TO BALCONIES, CORNICES, GUTTERS, EAVES,
 AND ROOF OVERHANG PROJECTIONS SHALL NOT EXTEND FARTHER
 THAN THREE FEET INTO ANY SETBACK. PLEASE SHOW
 STRUCTURAL OVERHANG PROJECTIONS FOR BALCONIES.
  
 PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT.
  
 SHOWING THE FOLLOWING:
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 GROSS LOT SQUARE FOOTAGE MINUS
 BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE OR
 PORTION THEREOF
 ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE OR
 PORTION THEREOF
  
 MORE COMMENTS MAY FOLLOW FURTHER REVIEW.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 ZONING DIVISION
 561-822-1449
  