Plan Review Details - Permit 18070731
Plan Review Stops For Permit 18070731
Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-07-28 Cont ID  
Sent By tklarge Date 2018-07-28 Time 04:28 Rev Time 0.00
Received By tklarge Date 2018-07-28 Time 04:06 Sent To I
Notes
2018-07-28 04:27:401) THE SUBMITTED MANUAL FOR THE GAS RANGE DOES NOT SHOW
 THAT THE RANGE IS LISTED OR LABELED AS REQUIRED BY 2017
 FBCR SEC.G2404.3.
 2) CITY RECORDS DO NOT SHOW ANY PREVIOUS PERMITS FOR
 GAS AT THIS ADDRESS. SUBMIT A PLAN SHOWING ALL GAS
 APPLIANCES IN THE STRUCTURE. THOSE APPLIANCES SHALL BE
 INCLUDED IN THIS PERMIT IF IT IS DETERMINED THAT THEY
 HAVE BEEN INSTALLED WITHOUT PERMITS.WPB AMEND. TO FBC
 SEC. 105.1.
 3) SUBMIT TWO COPIES OF AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE
 PER 2017 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017
 FBC-RES SEC. G2413.4.1, G2413.4.2.
 4) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED & ALL
 PIPE SIZES. WPB AMENDMENTS TO FBC SEC.107.2.1.
 5) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21).
 6.) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES.
 SEC. G 2413.4.1, G2413.4.2.
 7) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
 8) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-28 Cont ID  
Sent By tklarge Date 2018-07-28 Time 04:29 Rev Time 0.00
Received By tklarge Date 2018-07-17 Time 14:09 Sent To  
Notes
2018-07-18 14:09:43PLUMB<5K