Plan Review Details - Permit 18070704
| Plan Review Stops For Permit 18070704 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-08-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-08-25 |
Time |
15:21 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-08-25 |
Time |
15:21 |
Sent To |
|
|
| Notes |
| 2018-08-25 15:25:23 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. PLANS LACK A SUBSTANTIAL AMOUNT OF INFORMATION, SO A | | | COMPLETE PLAN REVIEW CANNOT BE DONE. INFORMATION NOT | | | PROVIDED: | | | | | | OCCUPANT LOAD | | | EXIT CAPACITIES | | | PANIC BARS ON DOORS | | | PREVIOUS OCCUPANCY, PROPOSED OCCUPANCY (FBC B CHAPTER | | | 3) | | | COMPLIANCE WITH ALL REQUIREMENTS OF FBC EXISTING | | | BUILDING CHAPTER 10 | | | LEVEL OF ALTERATION | | | | | | 2. PROVIDE A DETAIL FOR THE STAGE, FBC 107. WILL THIS | | | BE ACCESSIBLE (RAMP)? | | | | | | 3. PLANS ARE TO BE ARCHITECTURAL QUALITY, DRAWN TO | | | SCALE, FBC 107. | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-08-10 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-08-10 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-08-10 |
Time |
14:34 |
Sent To |
|
|
| Notes |
| 2018-08-10 14:34:43 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH | | | SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE | | | MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH | | | DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND | | | SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS | | | RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH | | | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR | | | OTHER ITEMS RELATED TO RECORDS MANAGEMENT. ELECTRONIC | | | MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS | | | OF FLORIDA STATUTES. PROVIDE CORRECTION. WPB FBC | | | 107.2.1.3 | | | 2. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND | | | SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE | | | ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H); | | | 471.025; WPB FBC 107.2.1, 107.3.5 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD | | | SHEETS?. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2018-07-20 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-07-20 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-07-19 |
Time |
15:22 |
Sent To |
|
|
| Notes |
| 2018-07-20 09:29:30 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE IS INSUFFICIENT INFORMATION PROVIDE TO DO A | | | COMPLETE AND DETAILED REVIEW OF THIS CHANGE OF | | | OCCUPANCY. | | | | | | | | | | | | 2) THERE ARE NO INDICATIONS OF REVIEW OR DESIGN OF ANY | | | FIRE CODE. | | | | | | THIS PROJECT SHALL COMPLY WITH THE 6TH EDITION OF THE | | | FLORIDA FIRE PREVENTION CODE. | | | | | | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF | | | ACKNOWLEDGEMENT AND COMPLIANCE. | | | | | | | | | | | | 3) WHAT WAS THE PREVIOUS OCCUPANCY AND WHAT IS THE | | | PROPOSED OCCUPNACY PER THE NOTED FFPC ABOVE. | | | | | | IT MAY HAVE BEEN BUSINESS AND NOW ASSEMBLY, BUT PLEASE | | | ENSURE IT IS ACCURATE. | | | | | | | | | | | | 4) A LIFE SAFETY PLAN IS REQUIRED FOR THIS PROJECT THAT | | | INCLUDES THE OCCUPANCY TYPE, OCCUPANCY LOAD, TRAVEL | | | PATHS, EXITS WIDTHS, EMERGENCY LIGHTS, DOOR SCHEDULE, | | | EXIT HARDWARE, DOOR LOCK TYPES, SEATING PLAN, ETC. | | | | | | PLEASE PROVIDE A DETAILED PLAN SHEET. | | | | | | | | | | | | 5) A STAGE IS INDICATED WITH NO DETAIL. | | | | | | PLEASE PROVIDE DETAILS INCLUDING, BUILDING MATERIAL, | | | HEIGHT, STEPS, HANDRAILS, SPRINKLER PROTECTION, AND | | | EXACT LOCATION WITH SPECIFIC DIMENSIONS FROM ALL WALLS. | | | | | | | | | | | | 6) CHAIRS ARE INDICATED WITH NO DETAIL. | | | | | | A SEATING PLAN SHALL BE PROVIDED AS PART OF THE LIFE | | | SAFETY PLAN, INCLUDING CHAIR TYPE, NUMBER OF CHAIRS, | | | AND AISLE(S) WIDTH. | | | | | | ALL DIMENSION SHALL COMPLY WITH NFPA 101, CHAPTER 7, | | | MEANS OF EGRESS AND CHAPTER 12, NEW ASSEMBLY | | | OCCUPNACIES. | | | | | | | | | | | | 7) A FIRE ALARM IS NOT INDICATED. | | | | | | BASED ON THE OCCUPANY AND OCCUPANCY LOAD A FIRE ALARM | | | IS LIKELY REQUIRED. | | | | | | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF | | | ACKNOWLEDGEMENT AND COMPLIANCE TO PROVIDE A FIRE ALARM | | | UNDER SEPARATE SHOP DRAWING BY A LICENSED FIRE ALARM | | | CONTRACTOR. | | | | | | | | | | | | 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-08-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-08-25 |
Time |
15:26 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-07-17 |
Time |
09:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2018-08-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-08-25 |
Time |
15:25 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-08-25 |
Time |
15:25 |
Sent To |
|
|
| Notes |
| 2018-08-25 15:26:19 | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | | (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE | | | PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE | | | RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS | | | APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE | | | FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD | | | MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-08-07 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-08-07 |
Time |
16:46 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-08-07 |
Time |
16:46 |
Sent To |
|
|
| Notes |
| 2018-08-07 16:58:50 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #18070704 | | | 8/7/18 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE PROPOSED CHANGE OF OCCUPANCY TO A PLACE OF | | | WORSHIP MAY REQUIRE INCREASED MECHANICAL VENTILATION AS | | | NOTED IN SECTION 1009.1 FBC EX. IN ORDER TO VERIFY THE | | | EXISTING AC SYSTEMS WILL ACCOMODATE THE CHANGE, PLEASE | | | PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS | | | AND SPACES PER TABLE 403.3.1.1 FBC-17 MECHANICAL. | | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED CFMS OF | | | FRESH OUTDOOR AIR, AND THE AMOUNT OF AIR THAT THE | | | EXISTING SYSTEMS ARE PROVIDING. IN ACCORDANCE WITH | | | TABLE 403.3.1.1 THE MINIMUM VENTILATION IS BASED ON AN | | | OCCUPANT DENSITY OF 120 PERSONS PER 1000 SQ. FT. AT A | | | RATE OF 5 CFMS PER PERSON + 0.06 CFMS PER SQ. FT. | | | | | | 2) DESIGN CRITERIA: PLEASE PROVIDE A LIST OF CURRENT | | | CODES AND STANDARDS USED IN THE DESIGN OF THE PROPOSED | | | NEW OCCUPANCY. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-08-20 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-08-20 |
Time |
16:55 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-08-20 |
Time |
16:55 |
Sent To |
|
|
| Notes |
| 2018-08-20 18:01:07 | 1ST REVIEW: | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. THIS IS A CHANGE OF OCCUPANCY PLEASE SHOW ON THE | | | PLAN THE PREVIOUS OCCUPANCY ALONG WITH THE NEW ONE. PER | | | FBC EX CH. 407 | | | | | | 2. PLEASE SHOW THE OCCUPANT LOAD ON THE PLAN. PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | 3. WITH THE CHANGE OF OCCUPANCY FROM BUSINESS TO | | | ASSEMBLY YOUR OCCUPANT LOAD WILL INCREASE WHICH WILL | | | YOU TO INSTALL A WATER FOUNTAIN AND SERVICE SINK. | | | PER FBC EX 1010.1 AND FBC PL TABLE 403.1, 410.3 | | | | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2018-07-27 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2018-07-27 |
Time |
08:52 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2018-07-27 |
Time |
08:52 |
Sent To |
|
|
| Notes |
|
|
|