Plan Review Details - Permit 18070686
Plan Review Stops For Permit 18070686
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2018-10-19 Cont ID  
Sent By skennedy Date 2018-10-19 Time 11:19 Rev Time 0.00
Received By skennedy Date 2018-10-19 Time 11:19 Sent To  
Notes
2018-10-19 11:20:07ADVISED APPLICANT TO CORIDINATE ADDRESSES UPON
 APPLICATION TO COMPLETE IMPROVEMENTS.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2018-07-23 Cont ID  
Sent By skennedy Date 2018-07-23 Time 10:56 Rev Time 0.00
Received By skennedy Date 2018-07-23 Time 10:56 Sent To  
Notes
2018-07-23 11:04:471ST REVIEW: FBC 2017 6TH ED. RESIDENTIAL
 1ST REVIEW FBC 2017 EXISTING BUILDING
  
 THIS PROJECT PROPOSES TO MOVE TWO SEPARATE STRUCTURES
 ONTO A SINGLE PARCEL. IT IS UNCLEAR IF EACH STRUCTURE
 CONSTITUTES INDIVIDUALLY A SEPARTE DWELLING UNIT.
 PLEASE CLARIFY AND NOTE THAT EACH SHOULD BE UNDER
 SEPARATE PERMIT IF SEPARATE DWELLING UNITS WITH A
 UNIQUE ADDRESS. IN THE EVENT THIS IS TWO SEPARATE
 DWELLING UNITS WITH OR WITHOUT SEPARATE ELECTRICAL
 SERVICES, PLEASE COORDINATE WITH MICHAEL ORIO AT 561
 494-1040 OR [email protected] TO DETEMINE THE APPROPRIATE
 ADDRESS FOR THE ACCESSORY STRUCTURE. IN SUCH CASE,
 PLEASE PROVIDE AN ADDITIONAL PERMIT APPLICATION FOR THE
 ACCESSORY STRUCTURE WITH THE DETERMINED ADDRESS UPON
 IT.
  
 THIS PROJECT IS SUBJECT TO APPROVAL OF A MINOR
 SUBDIVISION PLAT. ACCORDINGLY, THE PROPERTY CONTROL
 NUMBER IS SUBJECT TO CHANGE,
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-10-24 Cont ID  
Sent By skennedy Date 2018-10-24 Time 11:49 Rev Time 0.00
Received By skennedy Date 2018-10-24 Time 11:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-07-23 Cont ID  
Sent By skennedy Date 2018-07-23 Time 11:04 Rev Time 0.00
Received By skennedy Date 2018-07-23 Time 11:04 Sent To  
Notes
2018-07-23 11:30:431ST REVIEW: FBC 2017 6TH ED. RESIDENTIAL
 1ST REVIEW FBC 2017 EXISTING BUILDING
  
 1 - FBC 107.2.1 - CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 PLEASE DECLARE UPON THE PLAN THE APPLICABLE CODE
 CRITERIA GOVERNING THE PROPOSED WORK. PURSUANT TO
 DISCUSSIONS WITH THE CONTRACTOR AND DESIGNER OF RECORD,
 IT IS APPARENT THAT THE APPLICABLE CODE IS THE FBC 2017
 EXISTING BUILDING , MORE PARTICULARLY CHAPTER 13
 RELOCATED OR MOVED BUILDINGS. PLEASE PROVIDE A CLEAR
 SCOPE OF WORK. THE SCOPE SHOULD IDENTIFY THAT AN
 EXISTING STRUCTURE(S) IS BEING MOVED AND INCLUDE A
 DESCRIPTION OF THE MEANS AND METHODS INTENDED TO
 CONNECT A MOVED STRUCTURE TO THE FOUNDATION AND
 STEMWALL. PROVIDE ADDITIONAL DETAILS OR NOTES RELATIVE
 TO PROPOSED IMPROVEMENTS SUCH AS PLUMBING, ELECTRICAL,
 HVAC, LANDSCAPING, DRIVEWAY, SEPARATE STRUCTURES,
 INCLUDING A FUTURE POOL. THE ENTIRE SCOPE OF WORK TO
 RESULT IN THE COMPLETE PROJECT SHOULD BE INCLUDED. YOU
 MAY ELECT TO DEFER INFORMATION UNDER DESIGN WHICH IS
 FORTHCOMING. PLEASE NOTE THAT EACH SEPARATE STRUCTURE
 REQUIRES A SEPARATE PERMIT APPLICATION. ADDITIONALLY,
 DRIVEWAYS, LANDSCAPING, POOLS, AND POOL BARRIERS
 REQUIRES SEPARATE PERMIT SUBMITTALS. PLEASE NOTE OR
 ACKNOWLEGE THIS ON THE PLAN. ADDITIONALLY THERE APPEARS
 TO BE STREET IMPROVEMENTS PROPOSED. PLEASE ACKNOWLEGE
 SUCH IMPROVEMENTS TO THE RIGHT OF WAY ARE TO BE
 APPROVED BY THE CITY OF WEST PALM BEACH ENGINEERING
 DEPARTMENT UNDER SEPARATE REVIEW. THE DRIVEWAY DEPICTED
 ON THE PRELIMINARY SITE PLAN IS SHOWN TO CONNECT TO A
 FUTURE ROAD EXTENTION.
  
 2 - CHAPTER 481, FLORIDA STATUTES& 61G1 FLORIDA
 ADMINISTRATIVE CODE.
  
 THE PLANS ARE DESIGNED BY MARK S MCCREE, REGISTERED
 ARCITECT, BUT DO NOT BEAR A PHYSICAL SIGNATURE AND SEAL
 AS REQUIRED. PLEASE PHYSICALLY SIGN AND SEAL THE
 PHYSICAL SETS OF PLANS.
  
 3A - FBC 107.2.5 SITE PLAN
  
 THE SITE PLAN MUST INCLUDE PROPOSED LOT DRAINAGE, AND
 DESIGN FLOOD ELEVATIONS.
  
 4 - FBC 107.3.5.3 PROVIDE THE FOLLOWING MINIMUM
 SUBMITTAL DOCUMENTS:
 A) CURRENT SURVEY. PLEASE NOTE THE SURVEY PROVIDED
 APPEARS PENDING PLAT CONCEPT THAT IS NOT YET APPROVED.
 B) DESIGN FLOOD ELEVATION, LOWEST FLOOR ELEVATION,
 FLOOD DAMAGE RESISTANT MATERIALS.
 C) PROPOSED ELEVATION CERTIFICATE FOR STRUCTURES AND
 EQUIPMENT IN SPECIAL FLOOD HAZARD AREA.
  
 5 - FBCE1302.6 FLOOD HAZARD AREAS.
  
 IF RELOCATED OR MOVED INTO A FLOOD HAZARD AREA,
 STRUCTURES SHALL COMPLY WITH SECTION 1612 OF THE
 FLORIDA BUILDING CODE, BUILDING, OR SECTION R322 OF THE
 FLORIDA BUILDING CODE, RESIDENTIAL, AS APPLICABLE.
 IT APPEARS FROM THE SUBMITTED SURVEY THAT THE STRUCTURE
 IS PROPOSED TO BE LOCATED IN A FLOOD HAZARD AREA. SEE
 ABOVE COMMENTS IN 4.
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2018-10-19 Cont ID  
Sent By skennedy Date 2018-10-19 Time 09:52 Rev Time 0.00
Received By skennedy Date 2018-10-19 Time 09:52 Sent To  
Notes
2018-10-19 09:52:37ELECTRICAL BY SEPARATE PERMIT

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-09-30 Cont ID  
Sent By jpearson Date 2018-09-30 Time 12:58 Rev Time 0.00
Received By jpearson Date 2018-09-30 Time 12:58 Sent To  
Notes
2018-09-30 12:57:59NO RESPONSE PROVIDED FOR PREVIOUS COMMENTS. SEE
 PREVIOUS COMMENTS BELOW:
  
 1ST REVIEW: FBC 2017 6TH ED. RESIDENTIAL
 1ST REVIEW FBC 2017 EXISTING BUILDING
  
 FBC 107. PROVIDE ELECTRICAL DETAILS OR NOTES TO
 DEMONSTRATE HOW THE ELECTRICAL SERVICE IS TO BE
 PROVIDED.
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-23 Cont ID  
Sent By skennedy Date 2018-07-23 Time 10:45 Rev Time 0.00
Received By skennedy Date 2018-07-23 Time 10:45 Sent To  
Notes
2018-07-23 10:56:371ST REVIEW: FBC 2017 6TH ED. RESIDENTIAL
 1ST REVIEW FBC 2017 EXISTING BUILDING
  
 FBC 107. PROVIDE ELECTRICAL DETAILS OR NOTES TO
 DEMONSTRATE HOW THE ELECTRICAL SERVICE IS TO BE
 PROVIDED.
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2018-07-23 Cont ID  
Sent By skennedy Date 2018-07-23 Time 13:13 Rev Time 0.00
Received By skennedy Date 2018-07-23 Time 13:10 Sent To  
Notes
2018-07-23 13:18:39SPOKE TO VINCE NOEL. HE HAD NO CONCERN BUT RECOMENDED
 THE C/C NOT BE ISSUED PRIOR TO COMPLETION OF MINOR
 SUBDIVISION AND RIGHT-OF-WAY IMPROVEMENTS. I HAVE
 PLACED A HOLD ON C/C ISSUANCE.
2018-07-23 10:44:32PLEASE REVIEW FOR SUBDIVISION REQUIREMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2018-07-18 Cont ID  
Sent By pleduc Date 2018-07-18 Time   Rev Time 0.00
Received By pleduc Date 2018-07-18 Time 11:09 Sent To  
Notes
2018-07-18 11:16:25SINGLE FAMILY WITH SEPARATE GUEST HOUSE, LIFE SAFETY
 FIRE REVIEW NOT REQUIRED.PML

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-24 Cont ID  
Sent By skennedy Date 2018-10-24 Time 11:49 Rev Time 0.00
Received By skennedy Date 2018-09-21 Time 11:40 Sent To  
Notes
2018-09-25 11:40:57R14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-24 Cont ID  
Sent By cpuell Date 2018-07-24 Time 11:28 Rev Time 0.00
Received By cpuell Date 2018-07-16 Time 13:22 Sent To  
Notes
2018-07-17 13:22:34C13

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-10-24 Cont ID  
Sent By skennedy Date 2018-10-24 Time 11:24 Rev Time 0.00
Received By skennedy Date 2018-10-19 Time 11:18 Sent To  
Notes
2018-10-24 11:24:53MU-2018-026607-0000
2018-10-19 11:19:10AWAITING RECEIPT.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-07-23 Cont ID  
Sent By skennedy Date 2018-07-23 Time 10:43 Rev Time 0.00
Received By skennedy Date 2018-07-23 Time 10:43 Sent To  
Notes
2018-07-23 10:43:48PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status N Date 2018-10-24 Cont ID  
Sent By skennedy Date 2018-10-24 Time 11:29 Rev Time 0.00
Received By skennedy Date 2018-10-24 Time 11:29 Sent To  
Notes
2018-10-24 11:32:18STRUCTURES ARE LOCATED IN AN X500 ZONE. SURVEY TO BE
 UPDATED UPON TIE IN SURVEY SUBMITTAL TO INSPECTOR.

Review Stop P PLUMBING
Rev No 3 Status N Date 2018-10-19 Cont ID  
Sent By skennedy Date 2018-10-19 Time 09:52 Rev Time 0.00
Received By skennedy Date 2018-10-19 Time 09:52 Sent To  
Notes
2018-10-19 09:54:36PLUMBING WILL BE BY SEPARATE PERMIT.

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-10-11 Cont ID  
Sent By jesmith Date 2018-10-11 Time 11:27 Rev Time 0.00
Received By jesmith Date 2018-10-11 Time 12:26 Sent To  
Notes
2018-10-11 11:27:16CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW: DENIED
 COMMENTS
  
 1. RE: PLAN SHEET SP-1; THE PLANS ARE DESIGNED BY MARK
 S MCCREE, REGISTERED ARCHITECT, BUT THIS PAGE DOES NOT
 BEAR A PHYSICAL SIGNATURE AND SEAL AS REQUIRED. PLEASE
 PHYSICALLY SIGN AND SEAL THE PAGE. FS 471 & FAC 61G15
 2. BASED ON THE REQUIREMENTS OF THE 1ST REVIEW, IT IS
 NOTED ON THE REVISED PLAN SHEET S-1 THAT THE PLUMBING
 WILL BE ADDRESSED ON A FUTURE REVISION. A SEPARATE
 PLUMBING PERMIT SHALL BE APPLIED FOR WITH REVISED
 DRAWINGS PROVIDING THE REQUIRED DETAILS FOR SEWER AND
 WATER CONNECTIONS. WPB FBC 105.1 & 107.2.1
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-07-23 Cont ID  
Sent By skennedy Date 2018-07-23 Time 09:55 Rev Time 0.00
Received By skennedy Date 2018-07-23 Time 09:55 Sent To  
Notes
2018-07-23 10:42:571ST REVIEW FBC 2017 EXISTING BUILDING
 FBC 2017 PLUMBING
  
 PROVIDE DETAILS FOR WATER & SEWER CONNECTIONS OR ELECT
 TO DEFER SUCH DETAILS.
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2018-10-19 Cont ID  
Sent By awooten Date 2018-10-19 Time   Rev Time 0.00
Received By awooten Date 2018-10-19 Time   Sent To  
Notes
2018-10-19 16:09:59******ZONING PROVISO******
  
 PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY,
 THE FOLLOWING CONDITIONS SHALL BE ADDRESSED:
  
 1. A LANDSCAPE PERMIT, WHICH INCLUDES A LANDSCAPE PLAN,
 SHALL BE SUBMITTED TO THE BUILDING DIVISION FOR REVIEW.
  
 2. THE LANDSCAPE MATERIAL SHOWN ON THE APPROVED
 LANDSCAPE PERMIT SHALL BE INSTALLED AND PASS A FINAL
 LANDSCAPE INSPECTION.
  
 ALANA WOOTEN
 PLANNING DIVISION
 ASSOCIATE PLANNER
 561-822-1449
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2018-10-10 Cont ID  
Sent By awooten Date 2018-10-10 Time   Rev Time 0.00
Received By awooten Date 2018-10-10 Time   Sent To  
Notes
2018-10-10 12:09:39*************************ZONING REVIEW
 FAILED**************************
  
 PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT. SHOWING THE FOLLOWING:
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A.
  
 GROSS LOT SQUARE FOOTAGE MINUS
 BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE OR
 PORTION THEREOF
 ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE OR
 PORTION THEREOF
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-07-23 Cont ID  
Sent By AW Date 2018-07-23 Time   Rev Time  
Received By awooten Date 2018-07-23 Time   Sent To  
Notes
2018-07-23 16:59:50************************************ZONING REVIEW FAILE
 D**************************************************
  
 ENGINEERING COMMENTS ON EXPANSION OF PURITAN ROAD MUST
 BE SATISFIED PRIOR TO APPROVAL OF THIS BUILDING PERMIT.
  
 APPROVAL OF SUBDIVISION APPLICATION MUST BE OBTAINED
 PRIOR TO APPROVAL FOR THIS BUILDING PERMIT.
  
 THE FRONT SETBACK IN THE SF-14 DISTRICT IS A MINIMUM OF
 25 FEET.
  
 A 3 FOOT SETBACK FOR THE DRIVEWAY IS REQUIRED FROM SIDE
 PROPERTYLINES.
  
 INDICATE THE HEIGHT OF THE PROPOSED STRUCTURES ON THE
 ELEVATION DRAWINGS.
  
 DIMENSION SETBACKS. MECHANICAL EQUIPMENT. MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN FOUR FEET INTO A
 SETBACK. WINDOW AIR-CONDITIONING UNITS MAY NOT PROJECT
 MORE THAN 18 INCHES INTO A REQUIRED SIDE SETBACK.
  
 DIMENSION OVERHANGS. STRUCTURAL INTRUSIONS. STRUCTURAL
 OVERHANGS, INCLUDING BUT NOT LIMITED TO BALCONIES,
 CORNICES, GUTTERS, EAVES, AND ROOF OVERHANG PROJECTIONS
 SHALL NOT EXTEND FARTHER THAN THREE FEET INTO ANY
 SETBACK.
  
 SEPARATE PERMITS ARE REQUIRED FOR FENCES/WALSL,
 GENERATORS, POOLS, DRIVEWAYS, LANDSCAPING, IRRIGATION,
 AND MECHANICAL/AC/POOL EQUIPMENT,
  
 PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT. SHOWING THE FOLLOWING:
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A.
  
 GROSS LOT SQUARE FOOTAGE MINUS
 BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE OR
 PORTION THEREOF
 ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE OR
 PORTION THEREOF
  
 ADDITIONAL COMMENTS MAY FOLLOW FURTHER REVIEW.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  
  
  