| Plan Review Stops For Permit 18070686 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2018-10-19 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-10-19 |
Time |
11:19 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-10-19 |
Time |
11:19 |
Sent To |
|
|
| Notes |
| 2018-10-19 11:20:07 | ADVISED APPLICANT TO CORIDINATE ADDRESSES UPON | | | APPLICATION TO COMPLETE IMPROVEMENTS. |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2018-07-23 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-07-23 |
Time |
10:56 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-07-23 |
Time |
10:56 |
Sent To |
|
|
| Notes |
| 2018-07-23 11:04:47 | 1ST REVIEW: FBC 2017 6TH ED. RESIDENTIAL | | | 1ST REVIEW FBC 2017 EXISTING BUILDING | | | | | | THIS PROJECT PROPOSES TO MOVE TWO SEPARATE STRUCTURES | | | ONTO A SINGLE PARCEL. IT IS UNCLEAR IF EACH STRUCTURE | | | CONSTITUTES INDIVIDUALLY A SEPARTE DWELLING UNIT. | | | PLEASE CLARIFY AND NOTE THAT EACH SHOULD BE UNDER | | | SEPARATE PERMIT IF SEPARATE DWELLING UNITS WITH A | | | UNIQUE ADDRESS. IN THE EVENT THIS IS TWO SEPARATE | | | DWELLING UNITS WITH OR WITHOUT SEPARATE ELECTRICAL | | | SERVICES, PLEASE COORDINATE WITH MICHAEL ORIO AT 561 | | | 494-1040 OR [email protected] TO DETEMINE THE APPROPRIATE | | | ADDRESS FOR THE ACCESSORY STRUCTURE. IN SUCH CASE, | | | PLEASE PROVIDE AN ADDITIONAL PERMIT APPLICATION FOR THE | | | ACCESSORY STRUCTURE WITH THE DETERMINED ADDRESS UPON | | | IT. | | | | | | THIS PROJECT IS SUBJECT TO APPROVAL OF A MINOR | | | SUBDIVISION PLAT. ACCORDINGLY, THE PROPERTY CONTROL | | | NUMBER IS SUBJECT TO CHANGE, | | | | | | STEVEN KENNEDY, CBO | | | ASSISTANT BUILDING OFFICIAL | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2018-10-24 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-10-24 |
Time |
11:49 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-10-24 |
Time |
11:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-07-23 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-07-23 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-07-23 |
Time |
11:04 |
Sent To |
|
|
| Notes |
| 2018-07-23 11:30:43 | 1ST REVIEW: FBC 2017 6TH ED. RESIDENTIAL | | | 1ST REVIEW FBC 2017 EXISTING BUILDING | | | | | | 1 - FBC 107.2.1 - CONSTRUCTION DOCUMENTS SHALL BE OF | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL. | | | | | | PLEASE DECLARE UPON THE PLAN THE APPLICABLE CODE | | | CRITERIA GOVERNING THE PROPOSED WORK. PURSUANT TO | | | DISCUSSIONS WITH THE CONTRACTOR AND DESIGNER OF RECORD, | | | IT IS APPARENT THAT THE APPLICABLE CODE IS THE FBC 2017 | | | EXISTING BUILDING , MORE PARTICULARLY CHAPTER 13 | | | RELOCATED OR MOVED BUILDINGS. PLEASE PROVIDE A CLEAR | | | SCOPE OF WORK. THE SCOPE SHOULD IDENTIFY THAT AN | | | EXISTING STRUCTURE(S) IS BEING MOVED AND INCLUDE A | | | DESCRIPTION OF THE MEANS AND METHODS INTENDED TO | | | CONNECT A MOVED STRUCTURE TO THE FOUNDATION AND | | | STEMWALL. PROVIDE ADDITIONAL DETAILS OR NOTES RELATIVE | | | TO PROPOSED IMPROVEMENTS SUCH AS PLUMBING, ELECTRICAL, | | | HVAC, LANDSCAPING, DRIVEWAY, SEPARATE STRUCTURES, | | | INCLUDING A FUTURE POOL. THE ENTIRE SCOPE OF WORK TO | | | RESULT IN THE COMPLETE PROJECT SHOULD BE INCLUDED. YOU | | | MAY ELECT TO DEFER INFORMATION UNDER DESIGN WHICH IS | | | FORTHCOMING. PLEASE NOTE THAT EACH SEPARATE STRUCTURE | | | REQUIRES A SEPARATE PERMIT APPLICATION. ADDITIONALLY, | | | DRIVEWAYS, LANDSCAPING, POOLS, AND POOL BARRIERS | | | REQUIRES SEPARATE PERMIT SUBMITTALS. PLEASE NOTE OR | | | ACKNOWLEGE THIS ON THE PLAN. ADDITIONALLY THERE APPEARS | | | TO BE STREET IMPROVEMENTS PROPOSED. PLEASE ACKNOWLEGE | | | SUCH IMPROVEMENTS TO THE RIGHT OF WAY ARE TO BE | | | APPROVED BY THE CITY OF WEST PALM BEACH ENGINEERING | | | DEPARTMENT UNDER SEPARATE REVIEW. THE DRIVEWAY DEPICTED | | | ON THE PRELIMINARY SITE PLAN IS SHOWN TO CONNECT TO A | | | FUTURE ROAD EXTENTION. | | | | | | 2 - CHAPTER 481, FLORIDA STATUTES& 61G1 FLORIDA | | | ADMINISTRATIVE CODE. | | | | | | THE PLANS ARE DESIGNED BY MARK S MCCREE, REGISTERED | | | ARCITECT, BUT DO NOT BEAR A PHYSICAL SIGNATURE AND SEAL | | | AS REQUIRED. PLEASE PHYSICALLY SIGN AND SEAL THE | | | PHYSICAL SETS OF PLANS. | | | | | | 3A - FBC 107.2.5 SITE PLAN | | | | | | THE SITE PLAN MUST INCLUDE PROPOSED LOT DRAINAGE, AND | | | DESIGN FLOOD ELEVATIONS. | | | | | | 4 - FBC 107.3.5.3 PROVIDE THE FOLLOWING MINIMUM | | | SUBMITTAL DOCUMENTS: | | | A) CURRENT SURVEY. PLEASE NOTE THE SURVEY PROVIDED | | | APPEARS PENDING PLAT CONCEPT THAT IS NOT YET APPROVED. | | | B) DESIGN FLOOD ELEVATION, LOWEST FLOOR ELEVATION, | | | FLOOD DAMAGE RESISTANT MATERIALS. | | | C) PROPOSED ELEVATION CERTIFICATE FOR STRUCTURES AND | | | EQUIPMENT IN SPECIAL FLOOD HAZARD AREA. | | | | | | 5 - FBCE1302.6 FLOOD HAZARD AREAS. | | | | | | IF RELOCATED OR MOVED INTO A FLOOD HAZARD AREA, | | | STRUCTURES SHALL COMPLY WITH SECTION 1612 OF THE | | | FLORIDA BUILDING CODE, BUILDING, OR SECTION R322 OF THE | | | FLORIDA BUILDING CODE, RESIDENTIAL, AS APPLICABLE. | | | IT APPEARS FROM THE SUBMITTED SURVEY THAT THE STRUCTURE | | | IS PROPOSED TO BE LOCATED IN A FLOOD HAZARD AREA. SEE | | | ABOVE COMMENTS IN 4. | | | | | | STEVEN KENNEDY, CBO | | | ASSISTANT BUILDING OFFICIAL | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
N |
Date |
2018-10-19 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-10-19 |
Time |
09:52 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-10-19 |
Time |
09:52 |
Sent To |
|
|
| Notes |
| 2018-10-19 09:52:37 | ELECTRICAL BY SEPARATE PERMIT |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2018-09-30 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-09-30 |
Time |
12:58 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-09-30 |
Time |
12:58 |
Sent To |
|
|
| Notes |
| 2018-09-30 12:57:59 | NO RESPONSE PROVIDED FOR PREVIOUS COMMENTS. SEE | | | PREVIOUS COMMENTS BELOW: | | | | | | 1ST REVIEW: FBC 2017 6TH ED. RESIDENTIAL | | | 1ST REVIEW FBC 2017 EXISTING BUILDING | | | | | | FBC 107. PROVIDE ELECTRICAL DETAILS OR NOTES TO | | | DEMONSTRATE HOW THE ELECTRICAL SERVICE IS TO BE | | | PROVIDED. | | | | | | STEVEN KENNEDY, CBO | | | ASSISTANT BUILDING OFFICIAL | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-07-23 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-07-23 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-07-23 |
Time |
10:45 |
Sent To |
|
|
| Notes |
| 2018-07-23 10:56:37 | 1ST REVIEW: FBC 2017 6TH ED. RESIDENTIAL | | | 1ST REVIEW FBC 2017 EXISTING BUILDING | | | | | | FBC 107. PROVIDE ELECTRICAL DETAILS OR NOTES TO | | | DEMONSTRATE HOW THE ELECTRICAL SERVICE IS TO BE | | | PROVIDED. | | | | | | STEVEN KENNEDY, CBO | | | ASSISTANT BUILDING OFFICIAL | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2018-07-23 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-07-23 |
Time |
13:13 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-07-23 |
Time |
13:10 |
Sent To |
|
|
| Notes |
| 2018-07-23 13:18:39 | SPOKE TO VINCE NOEL. HE HAD NO CONCERN BUT RECOMENDED | | | THE C/C NOT BE ISSUED PRIOR TO COMPLETION OF MINOR | | | SUBDIVISION AND RIGHT-OF-WAY IMPROVEMENTS. I HAVE | | | PLACED A HOLD ON C/C ISSUANCE. | | 2018-07-23 10:44:32 | PLEASE REVIEW FOR SUBDIVISION REQUIREMENTS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
N |
Date |
2018-07-18 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-07-18 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-07-18 |
Time |
11:09 |
Sent To |
|
|
| Notes |
| 2018-07-18 11:16:25 | SINGLE FAMILY WITH SEPARATE GUEST HOUSE, LIFE SAFETY | | | FIRE REVIEW NOT REQUIRED.PML |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-10-24 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-10-24 |
Time |
11:49 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-09-21 |
Time |
11:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-07-24 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2018-07-24 |
Time |
11:28 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2018-07-16 |
Time |
13:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2018-10-24 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-10-24 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-10-19 |
Time |
11:18 |
Sent To |
|
|
| Notes |
| 2018-10-24 11:24:53 | MU-2018-026607-0000 | | 2018-10-19 11:19:10 | AWAITING RECEIPT. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2018-07-23 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-07-23 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-07-23 |
Time |
10:43 |
Sent To |
|
|
| Notes |
| 2018-07-23 10:43:48 | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | | 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND | | | TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED | | | WITH A COPY OF RECEIPT AS APPLICABLE. |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
N |
Date |
2018-10-24 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-10-24 |
Time |
11:29 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-10-24 |
Time |
11:29 |
Sent To |
|
|
| Notes |
| 2018-10-24 11:32:18 | STRUCTURES ARE LOCATED IN AN X500 ZONE. SURVEY TO BE | | | UPDATED UPON TIE IN SURVEY SUBMITTAL TO INSPECTOR. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
N |
Date |
2018-10-19 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-10-19 |
Time |
09:52 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-10-19 |
Time |
09:52 |
Sent To |
|
|
| Notes |
| 2018-10-19 09:54:36 | PLUMBING WILL BE BY SEPARATE PERMIT. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2018-10-11 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2018-10-11 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2018-10-11 |
Time |
12:26 |
Sent To |
|
|
| Notes |
| 2018-10-11 11:27:16 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH | | | EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | | | | 2ND REVIEW: DENIED | | | COMMENTS | | | | | | 1. RE: PLAN SHEET SP-1; THE PLANS ARE DESIGNED BY MARK | | | S MCCREE, REGISTERED ARCHITECT, BUT THIS PAGE DOES NOT | | | BEAR A PHYSICAL SIGNATURE AND SEAL AS REQUIRED. PLEASE | | | PHYSICALLY SIGN AND SEAL THE PAGE. FS 471 & FAC 61G15 | | | 2. BASED ON THE REQUIREMENTS OF THE 1ST REVIEW, IT IS | | | NOTED ON THE REVISED PLAN SHEET S-1 THAT THE PLUMBING | | | WILL BE ADDRESSED ON A FUTURE REVISION. A SEPARATE | | | PLUMBING PERMIT SHALL BE APPLIED FOR WITH REVISED | | | DRAWINGS PROVIDING THE REQUIRED DETAILS FOR SEWER AND | | | WATER CONNECTIONS. WPB FBC 105.1 & 107.2.1 | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-805-6715 | | | | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-07-23 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-07-23 |
Time |
09:55 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-07-23 |
Time |
09:55 |
Sent To |
|
|
| Notes |
| 2018-07-23 10:42:57 | 1ST REVIEW FBC 2017 EXISTING BUILDING | | | FBC 2017 PLUMBING | | | | | | PROVIDE DETAILS FOR WATER & SEWER CONNECTIONS OR ELECT | | | TO DEFER SUCH DETAILS. | | | | | | STEVEN KENNEDY, CBO | | | ASSISTANT BUILDING OFFICIAL | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2018-10-19 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2018-10-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2018-10-19 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-10-19 16:09:59 | ******ZONING PROVISO****** | | | | | | PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY, | | | THE FOLLOWING CONDITIONS SHALL BE ADDRESSED: | | | | | | 1. A LANDSCAPE PERMIT, WHICH INCLUDES A LANDSCAPE PLAN, | | | SHALL BE SUBMITTED TO THE BUILDING DIVISION FOR REVIEW. | | | | | | 2. THE LANDSCAPE MATERIAL SHOWN ON THE APPROVED | | | LANDSCAPE PERMIT SHALL BE INSTALLED AND PASS A FINAL | | | LANDSCAPE INSPECTION. | | | | | | ALANA WOOTEN | | | PLANNING DIVISION | | | ASSOCIATE PLANNER | | | 561-822-1449 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2018-10-10 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2018-10-10 |
Time |
|
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2018-10-10 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-10-10 12:09:39 | *************************ZONING REVIEW | | | FAILED************************** | | | | | | PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION | | | PERMIT. SHOWING THE FOLLOWING: | | | RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM | | | BEACH | | | SECTION 94-442(C)(2)A. | | | | | | GROSS LOT SQUARE FOOTAGE MINUS | | | BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS | | | OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA) | | | ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE OR | | | PORTION THEREOF | | | ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE OR | | | PORTION THEREOF | | | | | | ALANA WOOTEN | | | ASSOCIATE PLANNER | | | PLANNING DIVISION | | | 561-822-1449 | | | [email protected] | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2018-07-23 |
|
|
Cont ID |
|
| Sent By |
AW |
Date |
2018-07-23 |
Time |
|
Rev Time |
|
| Received By |
awooten |
Date |
2018-07-23 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-07-23 16:59:50 | ************************************ZONING REVIEW FAILE | | | D************************************************** | | | | | | ENGINEERING COMMENTS ON EXPANSION OF PURITAN ROAD MUST | | | BE SATISFIED PRIOR TO APPROVAL OF THIS BUILDING PERMIT. | | | | | | APPROVAL OF SUBDIVISION APPLICATION MUST BE OBTAINED | | | PRIOR TO APPROVAL FOR THIS BUILDING PERMIT. | | | | | | THE FRONT SETBACK IN THE SF-14 DISTRICT IS A MINIMUM OF | | | 25 FEET. | | | | | | A 3 FOOT SETBACK FOR THE DRIVEWAY IS REQUIRED FROM SIDE | | | PROPERTYLINES. | | | | | | INDICATE THE HEIGHT OF THE PROPOSED STRUCTURES ON THE | | | ELEVATION DRAWINGS. | | | | | | DIMENSION SETBACKS. MECHANICAL EQUIPMENT. MECHANICAL | | | EQUIPMENT MAY NOT PROJECT MORE THAN FOUR FEET INTO A | | | SETBACK. WINDOW AIR-CONDITIONING UNITS MAY NOT PROJECT | | | MORE THAN 18 INCHES INTO A REQUIRED SIDE SETBACK. | | | | | | DIMENSION OVERHANGS. STRUCTURAL INTRUSIONS. STRUCTURAL | | | OVERHANGS, INCLUDING BUT NOT LIMITED TO BALCONIES, | | | CORNICES, GUTTERS, EAVES, AND ROOF OVERHANG PROJECTIONS | | | SHALL NOT EXTEND FARTHER THAN THREE FEET INTO ANY | | | SETBACK. | | | | | | SEPARATE PERMITS ARE REQUIRED FOR FENCES/WALSL, | | | GENERATORS, POOLS, DRIVEWAYS, LANDSCAPING, IRRIGATION, | | | AND MECHANICAL/AC/POOL EQUIPMENT, | | | | | | PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION | | | PERMIT. SHOWING THE FOLLOWING: | | | RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM | | | BEACH | | | SECTION 94-442(C)(2)A. | | | | | | GROSS LOT SQUARE FOOTAGE MINUS | | | BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS | | | OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA) | | | ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE OR | | | PORTION THEREOF | | | ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE OR | | | PORTION THEREOF | | | | | | ADDITIONAL COMMENTS MAY FOLLOW FURTHER REVIEW. | | | | | | ALANA WOOTEN | | | ASSOCIATE PLANNER | | | PLANNING DIVISION | | | 561-822-1449 | | | [email protected] | | | | | | | | | |
|
|