| 2018-08-10 13:08:19 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (BOTH |
| | COPIES) IS REQUIRED TO BEAR THE NAME AND BE SIGNED AND |
| | SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. SINCE |
| | THIS IS LSITED AS MULTI-FAMILY ON THE PROPERTY |
| | APPRAISERS WEBSITE, THE ELECTRICAL PAGES WILL NEED TO |
| | BE DESIGNED AND SIGNED/SEALED BY A DESIGN PROFESSIONAL |
| | OR ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. |
| | WPB FBC 107.1, 107.2; FS 471, 481 |
| | 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| | LOADS. LOAD CALCULATION IS DIFFICULT TO READ. IT |
| | APPEARS THE SERVICE CALCULATION SHOWS THE TOTAL SQUARE |
| | FOOTAGE, BUT DOES NOT SHOW BOTH RANGES, OR BOTH DRYERS. |
| | ALL LOADS NEED TO BE INCLUDED. NEC 220; FBC RE E3602.2 |
| | 3. RISER DIAGRAM SHOWS 2/0 WIRE FOR FEED, BUT THE LOAD |
| | CALCULATION IS NOT CORRECT. IT IS POSSIBLY CORRECT, BUT |
| | PROVIDE CORRECT SIZE OF WIRE IN MAST FOR TOTAL LOAD |
| | WHEN COMPUTED IF DIFFERENT. NEC 310.15 |
| | 4. RISER DIAGRAM SHOWS # 2 WIRE FEEDING SUB-PANELS THAT |
| | HAVE A 150 AMP MAIN BREAKER. THIS WIRE SIZE IS NOT |
| | RATED FOR 150 AMPS. PROVIDE CORRECTION. NEC |
| | 310.15(B)(7) AND (B)(16); FBC RE E3603.1, E3705.1 |
| | 5. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10; FBC RE E3603.3 |
| | 6. PROVIDE AIC RATING OF SERVICE PANELS. NEC 110.3, |
| | 110.9; FBC RE E3603.3 |
| | 7. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 |
| | 8. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| | 210.8(D); FBC RE E3902.10 |
| | 9. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| | SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| | KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| | PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, |
| | RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND |
| | SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS |
| | INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES. |
| | SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION. |
| | PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD |
| | SHEETS?. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |