Plan Review Details - Permit 18070665
Plan Review Stops For Permit 18070665
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-08-20 Cont ID  
Sent By rmcdouga Date 2018-08-20 Time 09:26 Rev Time 0.00
Received By rmcdouga Date 2018-08-20 Time 09:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-07-24 Cont ID  
Sent By rmcdouga Date 2018-07-24 Time 09:27 Rev Time 0.00
Received By rmcdouga Date 2018-07-24 Time 09:19 Sent To  
Notes
2018-07-24 09:24:29PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD ENGINEERING THAT WAS SUBMITTED
 REQUIRES THE 16KW GENERATOR TO HAVE A MINIMUM WEIGHT OF
 448 POUNDS. THE GENERATOR THAT IS PROPOSED HAS A UNIT
 WEIGHT OF 409 POUNDS WHICH DOES NOT MEET THE MINIMUM
 REQUIRED. FBCR-G2404.6

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-07-27 Cont ID  
Sent By jleahy Date 2018-07-27 Time 13:21 Rev Time 0.00
Received By jleahy Date 2018-07-27 Time 13:21 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2018-07-27 Cont ID  
Sent By lcrespo Date 2018-07-27 Time 15:45 Rev Time 0.00
Received By lcrespo Date 2018-07-27 Time 15:45 Sent To  
Notes
2018-07-27 15:46:1407/27/18 REVIEWED FOR CODE COMPLIANCE (PLUMBING/GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-20 Cont ID  
Sent By rmcdouga Date 2018-08-20 Time 09:26 Rev Time 0.00
Received By rmcdouga Date 2018-08-16 Time 13:29 Sent To  
Notes
2018-08-17 13:29:59RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-27 Cont ID  
Sent By lcrespo Date 2018-07-27 Time 15:45 Rev Time 0.00
Received By lcrespo Date 2018-07-16 Time 13:39 Sent To  
Notes
2018-07-17 13:40:02ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2018-07-19 Cont ID  
Sent By mcruz Date 2018-07-19 Time 14:14 Rev Time 0.00
Received By mcruz Date 2018-07-19 Time 14:12 Sent To B
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved