Plan Review Details - Permit 18070641
Plan Review Stops For Permit 18070641
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-10-03 Cont ID  
Sent By rmcdouga Date 2018-10-03 Time 15:06 Rev Time 0.00
Received By rmcdouga Date 2018-10-03 Time 10:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-17 Cont ID  
Sent By rmcdouga Date 2018-08-17 Time 13:49 Rev Time 0.00
Received By rmcdouga Date 2018-08-16 Time 07:36 Sent To  
Notes
2018-08-16 18:01:41PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHEET LS.1.0 SPECIFIES THIS BUILDING AS CONSTRUCTION
 TYPE III-B WITH 2 HOUR FIRE RATED EXTERIOR BEARING
 WALLS. PROVIDE DETAILS OF EACH OF THE 2 HOUR FIRE RATED
 EXTERIOR WALL TYPES AND THEIR LISTED ASSEMBLIES. FBC
 107.2.1 & FBC 704
  
 2) THE EXTERIOR STEEL COLUMNS LOCATED IN THE EXTERIOR
 WALLS ARE REQUIRED TO BE 2 HOUR FIRE PROTECTED. PROVIDE
 A DETAIL SHOWING HOW THIS PROTECTION WILL BE PROVIDED.
 FBC 704.2
  
 3) SHEET LS.1.0 SPECIFIES THIS BUILDING AS A TWO STORY
 STRUCTURE. IT APPEARS THAT THE VESTIBLE AND BATHROOMS
 SHOWN ON THE ROOF/TERRACE LEVEL SHOULD BE CONSIDERED A
 THIRD FLOOR. PLEASE REVISE THE PLANS ACCORDINGLY. FBC
 202
  
  
2018-08-14 13:16:25NOTE FOR BUILDING REVIEW: ELECTRICAL ROOM HAS CHANGED
 LAYOUT AND IS NOW SHOWN AS EXITING INTO STAIRWELL. THIS
 IS NOT REFLECTED ON LIFE SAFETY PLAN AS A REVISION, BUT
 IS SHOWN ON ELECTRICAL SHEET AS A CHANGE. FYI

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-09-20 Cont ID  
Sent By jpearson Date 2018-09-20 Time 12:37 Rev Time 0.00
Received By jpearson Date 2018-09-20 Time 12:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-14 Cont ID  
Sent By jpearson Date 2018-08-14 Time 15:16 Rev Time 0.00
Received By jpearson Date 2018-08-14 Time 15:16 Sent To  
Notes
2018-08-14 15:16:17CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHEET E1.1.1 SHOWS AN EXHAUST FAN INSTALLED ABOVE
 THE 1200 AMP DISCONNECT. PROVIDE CORRECTION. NEC
 110.26(E)(1)
 2. FYI ONLY, THIS IS NOT A CODE VIOLATION. I NOTICED
 THE FEEDERS FOR THE 1200 AMP SERVICE ARE INSTALLED IN
 FOUR 3.5 INCH CONDUITS. HOWEVER, THERE ARE ONLY THREE 4
 INCH CONDUITS THAT LEAVE THE 1200 AMP DISCONNECT TO THE
 RESTAURANT. THIS WOULD POSSIBLY REQUIRE COPER WIRE TO
 MEET AMPACITY REQUIREMENT. POSSIBLE OVERSIGHT. WPB FBC
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-08-09 Cont ID  
Sent By scaldero Date 2018-07-24 Time 12:45 Rev Time 0.00
Received By scaldero Date 2018-07-24 Time 11:35 Sent To  
Notes
2018-07-24 12:45:23PERMIT # 18070641
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED WITH PROVISIONS:
  
 LIFE SAFETY SHEETS AND FIRE PROTECTION SHEETS ARE ALL
 MARKED AS "ENTIRE SHEET REVISED". UNABLE TO ACCESS
 ORIGINAL SUBMISSION TO DETERMINE WHAT SPECIFIC DETAILS
 HAVE CHANGED.
 ALSO, CIVIL DRAWINGS NOT INCLUDED TO CONFIRM COMPLIANCE
 WITH ORIGINAL PROVISO COMMENTS PER W. JOLIN.
 THAT SAID, THIS SUBMISSION IS APPROVED WITH THE SAME
 PROVISIONAL COMMENTS, AS ORIGNALLY MADE.
  
 1) PER NFPA 24 SECTION 6.2.1, ALL CONNECTIONS TO
 PRIVATE FIRE SERVICE MAINS FOR FIRE PROTECTION SYSTEMS
 SHALL BE ARRANGED IN ACCORDANCE WITH ONE OF THE
 FOLLOWING SO THAT THEY CAN BE ISOLATED:
 (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40
 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST
 INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED
 CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE
 BUILDING AS THE HEIGHT OF THE WALL FACING THE POST
 INDICATOR VALVE.
 (2) A WALL POST INDICATOR VALVE
 (3) AN INDICATING VALVE IN A PIT, INSTALLED IN
 ACCORDANCE WITH SECTION 6.4
 (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT LESS THAN 40 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A
 BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE
 SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET
 BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF
 THE WALL FACING THE BACKFLOW PREVENTER.
 (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM
 ACCESSIBLE FROM THE EXTERIOR
 (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE
 ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE
 AUTHORITY HAVING JURISDICTION
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-03 Cont ID  
Sent By rmcdouga Date 2018-10-03 Time 15:28 Rev Time 0.00
Received By rmcdouga Date 2018-08-31 Time 12:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-27 Cont ID  
Sent By lmarchan Date 2018-08-27 Time 10:39 Rev Time 0.00
Received By lmarchan Date 2018-07-19 Time 09:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-09-20 Cont ID  
Sent By ccole Date 2018-09-20 Time 16:00 Rev Time 0.00
Received By ccole Date 2018-09-20 Time 16:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-08-14 Cont ID  
Sent By ccole Date 2018-08-14 Time 14:10 Rev Time 0.00
Received By ccole Date 2018-08-14 Time 14:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-09-28 Cont ID  
Sent By gjohnson Date 2018-09-28 Time 14:24 Rev Time 0.00
Received By gjohnson Date 2018-09-28 Time 14:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-08-23 Cont ID  
Sent By gjohnson Date 2018-08-23 Time 11:20 Rev Time 0.00
Received By gjohnson Date 2018-08-23 Time 11:20 Sent To  
Notes
2018-08-23 12:03:271ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. P3.3.1 THE 6" OVERFLOW DRAIN DISCHARGING ON THE
 WEST SIDE OF THE BUILDING WITH 5718 SQFT ON IT IS
 UNDERSIZED IT SHALL BE 8". PER FBC PL TABLE 1106.3
  
 2. SHT. P3.3.1 THERE ARE SEVERAL SECTION OF THE STORM
 DRAIN THAT ARE MISSING THE SQFT I CAN NOT CHECK THE
 SIZING CALCULATIONS WITH OUT THESE NUMBERS PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 3. P3.2.1 A TWO WAY CLEAN OUT IS REQUIRED BETWEEN EACH
 GREASE INTERCEPTOR PLEASE SHOW ON ISOMETRIC . PER
 MANUFACTURE SPECIFICATIONS AND WPB UTIL. DEPT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status P Date 2018-09-28 Cont ID  
Sent By gjohnson Date 2018-09-28 Time 14:25 Rev Time 0.00
Received By gjohnson Date 2018-09-28 Time 14:25 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2018-10-03 Cont ID  
Sent By rmcdouga Date 2018-10-03 Time 15:26 Rev Time 0.00
Received By rmcdouga Date 2018-10-03 Time 10:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2018-08-17 Cont ID  
Sent By rmcdouga Date 2018-08-17 Time 13:50 Rev Time 0.00
Received By rmcdouga Date 2018-08-17 Time 13:50 Sent To  
Notes
2018-08-14 14:11:30MECH DIG/SIGS GOOD.

Review Stop Z ZONING
Rev No 1 Status P Date 2018-08-24 Cont ID  
Sent By aaponte Date 2018-08-24 Time 13:39 Rev Time 0.00
Received By aaponte Date 2018-08-24 Time 13:39 Sent To  
Notes
2018-08-24 13:52:24PROVISO:
 1.FINAL DESIGN FOR OUTDOOR RESTAURANT PATIO DECK SHALL
 BE APPROVED WITH FUTURE RESTAURANT IT. THE PATIO DECK
 SHALL BE DESIGNED TO ENSURE AN ENHANCED RELATIONSHIP
 BETWEEN THE BUILDING AND THE PARK.
  