Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-07-19 Cont ID  
Sent By jgomez Date 2018-07-19 Time 11:42 Rev Time 0.00
Received By jgomez Date 2018-07-19 Time 09:33 Sent To  
Notes
2018-07-19 09:58:30 
  
  
  
 ***VALUATION ADDD REPAIRS
 -
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 1- REVISE INFILL DETAILS A, B, C AND E:
 A) COORDINATE WOOD STUDS AND CONNECTORS. 2X10 WOOD
 STUDS CAN NOT BE INSTALLED WITH SIMPSON SP6 CONNECTORS.
 B) PROVIDE CLEAR SPECIFICATIONS FOR ATTACHMENT OF TOP
 AND BOTTOM PLATES. TAPCON SIZE IS NOT CLEAR. ARCHITECT
 OF RECORD TO VERIFY THAT ANCHOR SPACING IS ADEQUATE TO
 RESIST THE WIND LOADS.