Plan Review Details - Permit 18070612
Plan Review Stops For Permit 18070612
Review Stop AD ADDRESSING
Rev No 2 Status N Date 2018-08-25 Cont ID  
Sent By shill Date 2018-08-25 Time 12:30 Rev Time 0.00
Received By shill Date 2018-08-25 Time 12:30 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2018-08-12 Cont ID  
Sent By shill Date 2018-08-12 Time 15:55 Rev Time 0.00
Received By shill Date 2018-08-12 Time 15:55 Sent To  
Notes
2018-08-12 15:55:46THIS NEW STRUCTURE REQUIRES ADDRESSING
  
 FOR ADDRESSING, PLEASE CONTACT (PREFERABLY VIA EMAIL):
  
 MICHAEL ORIO
 GIS SUPPORT SPECIALIST
 [email protected]
 CITY OF WEST PALM BEACH
 INFORMATION TECHNOLOGY DEPARTMENT
 401 CLEMATIS STREET, WEST PALM BEACH, FLORIDA 33401
 P: 561.494.1080
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-08-25 Cont ID  
Sent By shill Date 2018-08-25 Time 12:30 Rev Time 0.00
Received By shill Date 2018-08-25 Time 12:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-12 Cont ID  
Sent By shill Date 2018-08-12 Time 15:50 Rev Time 0.00
Received By shill Date 2018-08-12 Time 15:50 Sent To  
Notes
2018-08-12 15:54:44****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. A FOUNDATION PERMIT CANNOT BE ISSUED WITHOUT
 SUBMISSION OF THE BUILDING PERMIT.
  
 2. CONFIRM PARCEL THAT THE PROPOSED IMPROVEMENT IS
 LOCATED ON. THE PARCEL ID PROVIDED ON THE APPLICATION
 IS NOT THE ONE THAT THE PUTTING GREEN IS LOCATED ON.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-22 Cont ID  
Sent By jpearson Date 2018-08-22 Time 08:03 Rev Time 0.00
Received By jpearson Date 2018-08-22 Time 08:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-09 Cont ID  
Sent By jpearson Date 2018-08-09 Time 17:22 Rev Time 0.00
Received By jpearson Date 2018-08-09 Time 17:22 Sent To  
Notes
2018-08-09 17:22:52CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30
 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. NEC 220
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2018-08-23 Cont ID  
Sent By mgonzale Date 2018-08-23 Time   Rev Time 1.00
Received By mgonzale Date 2018-08-23 Time   Sent To I
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2018-08-02 Cont ID  
Sent By shill Date 2018-08-02 Time 13:12 Rev Time 0.00
Received By mgonzale Date 2018-08-02 Time 13:12 Sent To  
Notes
2018-08-02 15:28:47PLEASE ADDRESS PLANNING COMMENTS AND RESUBMIT.
  
 NO CONFLICTS WITH CITY OF WPB PUBLIC UTILITIES.
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
  
  
  
2018-08-02 13:12:29CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-07-17 Cont ID  
Sent By scaldero Date 2018-07-17 Time 11:30 Rev Time 0.00
Received By scaldero Date 2018-07-17 Time 11:13 Sent To  
Notes
2018-07-17 11:30:32PERMIT # 18070612
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) PERMIT AND APPROVAL IS FOR PRESSBOX FOUNDATION ONLY.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-09-01 Cont ID  
Sent By shill Date 2018-09-01 Time 17:21 Rev Time 0.00
Received By shill Date 2018-08-29 Time 15:14 Sent To  
Notes
2018-08-30 15:14:43IMPACT FEES ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-25 Cont ID  
Sent By shill Date 2018-08-25 Time 12:31 Rev Time 0.00
Received By shill Date 2018-08-14 Time 16:22 Sent To  
Notes
2018-08-15 16:22:54C10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-12 Cont ID  
Sent By shill Date 2018-08-12 Time 15:56 Rev Time 0.00
Received By shill Date 2018-07-13 Time 14:55 Sent To  
Notes
2018-07-16 14:56:03C09

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2018-09-04 Cont ID  
Sent By shill Date 2018-09-04 Time 08:52 Rev Time 0.00
Received By shill Date 2018-09-04 Time 08:52 Sent To  
Notes
2018-09-04 08:53:29MU 2018 030247
 RECEIPT $37.68

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-09-01 Cont ID  
Sent By shill Date 2018-09-01 Time 17:20 Rev Time 0.00
Received By shill Date 2018-09-01 Time 17:20 Sent To  
Notes
2018-09-01 17:21:24****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 THE PLAN WAS STAMPED BUT THE RECEIPT SHOWING THAT FEES
 DUE WERE PAID WAS NOT PROVIDED.
  
 THIS MAY BE PROVIDED TO ME VIA EMAIL.
  
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-08-12 Cont ID  
Sent By shill Date 2018-08-12 Time 15:55 Rev Time 0.00
Received By shill Date 2018-08-12 Time 15:55 Sent To  
Notes
2018-08-12 15:56:14PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-08-23 Cont ID  
Sent By eschneid Date 2018-08-23 Time 11:29 Rev Time 0.50
Received By eschneid Date 2018-08-23 Time 08:21 Sent To  
Notes
2018-08-23 11:29:08PASSED W/PROVISOS
  
 1) THE SLAB IS REQUIRED TO BE SET BACK AT LEAST 100
 FEET FROM THE WESTERN PROPERTY LINE.
  
 2) THE ARRANGEMENT OF THE PRESS BOX, STAIRS AND
 BLEACHERS IS DIFFERENT THAN THE ORIGINAL APPROVAL.
 PRIOR TO C.O., A MINOR PLANNED DEVELOPMENT AMENDMENT
 INCLUDING THE SITE PLAN SHOWING THE NEW CONFIGURATION
 IS REQUIRED, EVEN IF THIS IS AN INTERIM CONDITION.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2018-07-25 Cont ID  
Sent By ES Date 2018-07-25 Time 16:41 Rev Time 0.50
Received By eschneid Date 2018-07-24 Time 16:19 Sent To  
Notes
2018-07-25 16:55:10FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSE.
  
 1) THE FOUNDATION PLAN AND SECTION A-A DO NOT SHOW THE
 SAME DIMENSIONS FOR THE POSTS, TO INCLUDE THE CENTER
 LINE SPACING AND THE LOCATIONS ON THE PAD. ALL DRAWINGS
 MUST SHOW THE SAME CONDITIONS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]