Plan Review Details - Permit 18070566
Plan Review Stops For Permit 18070566
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-09-02 Cont ID  
Sent By shill Date 2018-09-02 Time 09:32 Rev Time 0.00
Received By shill Date 2018-09-02 Time 09:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-07-31 Cont ID  
Sent By sathomas Date 2018-07-31 Time 14:42 Rev Time 0.00
Received By shill Date 2018-07-31 Time 14:42 Sent To E
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-27 Cont ID  
Sent By fgiaquin Date 2018-08-27 Time 10:10 Rev Time 0.00
Received By fgiaquin Date 2018-08-27 Time 09:06 Sent To B
Notes
2018-08-27 10:09:38THIS PLAN HAS BEEN PASSED PROVISIONALLY:
  
 PROVIDE ACCURATE PANEL SCHEDULE BEFORE FINAL
 INSPECTION. PANEL SCHEDULE IS LABELED "LA", NO "LA"
 PANEL ON THE EXISTING RISER DIAGRAM DRAWING.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-24 Cont ID  
Sent By shill Date 2018-07-31 Time 14:42 Rev Time 0.00
Received By fgiaquin Date 2018-07-24 Time 06:51 Sent To  
Notes
2018-07-24 07:08:52ROUTED BACK TO BIN B14
  
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
 2. SHOW LIGHTS TO BE REPLACED IN ROOMS
 106,107,108,109,110,112. FBC 107.2.1
  
 3. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
  
 4. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
  
 5. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT
 SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2
 (OFFICES 106,107,108,109,110,112. WHERE LIGHTING WILL
 BE REPLACED)
  
 6. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE
 AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL
 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE
 OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR
 PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS,
 CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE
 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR
 FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC
 EC C405.6.1 (OPEN OFFICE AREA WITH RELOCATED AND NEW
 RECEPTACLES AND BREAK ROOM)
  
 7. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. NEC 220; FBC RE E3602.2 WE DO NOT ACCEPT
 "ASSUMED LOADS".
  
 8. PROVIDE ACCURATE PANEL SCHEDULE INDICATING ANY NEW
 OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR
 THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE
 APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12,
 215.5, 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
  
 9. PROVIDE RISER DIAGRAM OF EXISTING SERVICE FEEDING
 UNIT. NEC 215.5; WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-08-24 Cont ID  
Sent By scaldero Date 2018-08-24 Time 09:44 Rev Time 0.00
Received By scaldero Date 2018-08-24 Time 09:44 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-07-31 Cont ID  
Sent By scaldero Date 2018-07-31 Time 15:19 Rev Time 0.00
Received By scaldero Date 2018-07-16 Time 16:29 Sent To  
Notes
2018-07-31 15:20:08REVIEWED AND APPROVED BY S. THOMAS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-02 Cont ID  
Sent By shill Date 2018-09-02 Time 09:32 Rev Time 0.00
Received By shill Date 2018-08-09 Time 13:41 Sent To  
Notes
2018-08-10 13:41:55ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-01 Cont ID  
Sent By cpuell Date 2018-08-01 Time 07:19 Rev Time 0.00
Received By cpuell Date 2018-07-12 Time 16:07 Sent To  
Notes
2018-07-13 16:08:03B14

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-07-30 Cont ID  
Sent By ccole Date 2018-07-30 Time 14:10 Rev Time 0.00
Received By ccole Date 2018-07-30 Time 14:10 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved