Plan Review Details - Permit 18070501
Plan Review Stops For Permit 18070501
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-08-20 Cont ID  
Sent By rmcdouga Date 2018-08-20 Time 18:17 Rev Time 0.00
Received By rmcdouga Date 2018-08-20 Time 15:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-08-08 Cont ID  
Sent By jleahy Date 2018-08-08 Time 12:16 Rev Time 0.00
Received By jleahy Date 2018-08-08 Time 12:02 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2018-08-08 Cont ID  
Sent By jleahy Date 2018-08-08 Time 12:17 Rev Time 0.00
Received By jleahy Date 2018-08-08 Time 12:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-07-17 Cont ID  
Sent By pleduc Date 2018-07-17 Time   Rev Time 0.00
Received By pleduc Date 2018-07-16 Time 16:29 Sent To  
Notes
2018-07-17 10:58:39THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) SHEET A 3 - THERE IS AN INDICATION OF A LOCK SET
 WITH A CYLINDER BOLT. THIS IS THE MAIN EXIT DOOR FROM
 THE PHARMACY AREA AND MUST COMPLY WITH NFPA 101,
 CHAPTER 7, MEANS OF EGRESS.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES
  
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
  
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE
 PERMITTED TO HAVE
 KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT
 ALL OF THE
 FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR
 THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN.
 (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS
 FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF:
 THIS
 DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE
 AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE
 BUILDING WHEN IT IS LOCKED.
  
 THOUGH THIS DOOR IS NOT A TRUE EXTERIOR DOOR, IT IS THE
 EXTERIOR DOOR OF THE PHARMACY AND SIMILAR NEED EXIST
 FOR EXITING THIS SPACE.
  
 PLEASE ENSURE THAT EGRESS FROM THE PHARMACY COMPLIES
 WITH THE OF NOTED AREAS ON FIRE INSPECTIONS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-20 Cont ID  
Sent By rmcdouga Date 2018-08-20 Time 18:18 Rev Time 0.00
Received By rmcdouga Date 2018-07-12 Time 16:13 Sent To  
Notes
2018-07-13 16:13:31B21

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-08-20 Cont ID  
Sent By rmcdouga Date 2018-08-20 Time 16:50 Rev Time 0.00
Received By rmcdouga Date 2018-08-20 Time 16:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-08-15 Cont ID  
Sent By gjohnson Date 2018-08-15 Time 17:19 Rev Time 0.00
Received By gjohnson Date 2018-08-15 Time 14:13 Sent To  
Notes
***NONE***