Plan Review Details - Permit 18070480
Plan Review Stops For Permit 18070480
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-07-23 Cont ID  
Sent By jleahy Date 2018-07-23 Time 11:59 Rev Time 0.00
Received By jleahy Date 2018-07-23 Time 11:59 Sent To  
Notes
2018-07-23 12:03:05FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 THE FOLLOWING ARE CONDITION TO THE ISSUANCE OF THE
 PERMIT.
  
 1) INSPECTOR WILL VERIFY THAT THERE IS OCP AHEAD OF THE
 CONDUCTORS ( NOT FPL)
  
 2) VALUE OF CONTRACTSHALL BE VERIFIED BEFORE FINAL
 INSPECTION.
  
 3) JOB IS FOR DUCT BANK ONLY NO CONDUCTORS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-13 Cont ID  
Sent By jleahy Date 2018-07-13 Time 08:30 Rev Time 0.00
Received By jleahy Date 2018-07-13 Time 08:30 Sent To  
Notes
2018-07-13 08:46:37FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED TO LAYOUT THE SCOPE OF THIS PROJECT. WHAT IS THE
 ACTUAL WORK INVOLVED.
  
 PLANS NEED TO SIGNED AND SEALED BY AND ENGINEER
  
 CONDUCTOR SIZES NOT SHOWN ON PLANS, PLEASE INDICATE
 SIZE AND TYPE OF CONDUCTORS TO BE USED (CUT SHEETS)
  
 PLANS SHOWS CONDUITS COMING FROM A MV MANHOLE TO
 BUILDING AND THEN INTO THE SWITCHGEAR WITH NO
 DISCONNECT OR OVER CURRENT PROTECTION..
  
 230.205 DISCONNECTING MEANS
 (A) LOCATION. THE SERVICE DISCONNECTING MEANS SHALL BE
 LOCATED IN ACCORDANCE WITH 230.70.
  
 230.70 GENERAL
 MEANS SHALL BE PROVIDED TO DISCONNECT ALL CONDUCTORS IN
 A BUILDING OR OTHER STRUCTURE FROM THE SERVICE-ENTRANCE
 C ONDUCTORS.
  
 (1) READILY ACCESSIBLE LOCATION. THE SERVICE
 DISCONNECTING MEANS SHALL BE INSTALLED AT A READILY
 ACCESSIBLE LOCATION EITHER
 OUTSIDE OF A BUILDING OR STRUCTURE OR INSIDE NEAR EST
 THE POINT OF ENTRANCE OF THE SERVICE CONDUCTORS.
  
 300.50 UNDERGROUND INSTALLATIONS
 (A) GENERAL. UNDERGROUND CONDUCTORS SHALL BE IDENTIFIED
 FOR THE VOLTAGE AND CONDITIONS UNDER WHICH THEY ARE
 INSTALLED. DI RECTBURIAL
 CABLES SHALL COMPLY WITH THE PROVISIONS OF 310.10(F).
 UNDERGROUND CABLES SHALL BE INSTALLED IN ACCORDANCE
 WITH
 300.50(A)(1), (A)(2), OR (A)(3), AND THE INSTALLATION
 SHALL MEET THE DEPTH REQUIREMENTS OF TABLE 300.50
  
 BASED ON PLAN THE VALUE OF THE WORK SHOWN SEEMS LOW
 PLEASE SUBMIT A SIGNED CONTRACT FROM CITY OF WPB.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA
 OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-23 Cont ID  
Sent By jleahy Date 2018-07-23 Time 12:03 Rev Time 0.00
Received By jleahy Date 2018-07-18 Time 14:48 Sent To  
Notes
2018-07-19 14:48:18RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2018-07-13 Cont ID  
Sent By jleahy Date 2018-07-13 Time 08:46 Rev Time 0.00
Received By jleahy Date 2018-07-11 Time 15:23 Sent To  
Notes
2018-07-11 15:23:45ROUTED TO ELECTRICAL INBOX