Plan Review Details - Permit 18070478
Plan Review Stops For Permit 18070478
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-08-01 Cont ID  
Sent By cthroop Date 2018-08-01 Time 14:23 Rev Time 0.00
Received By cthroop Date 2018-08-01 Time 14:16 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-07-19 Cont ID  
Sent By cthroop Date 2018-07-19 Time 11:19 Rev Time 0.00
Received By cthroop Date 2018-07-19 Time 11:03 Sent To E
Notes
2018-07-19 11:24:48BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 THIS IS A SUBSTANTIAL DEMOLITION OF ONE THIRD OF THE
 STRUCTURE. PLEASE SEE ATTACHED DEMOLITION CHECKLIST.
 COMPLY WITH THE APPROPRIATE ITEMS ON THE CHECKLIST. A
 PLUMBING AND ELECTRICAL REVIEW ARE ALSO REQUIRED.
  
 DEMO PERMIT APPLICATION CHECKLIST
  
 PRIOR TO ISSUANCE OF PERMIT, THE FOLLOWING ITEMS ARE
 REQUIRED TO BE SUBMITTED OR COMPLETED.
  
 1)CONFIRMATION OF RELEASE OF POWER FROM F.P.L.
  
 2) CONFIRMATION OF RELEASE OF GAS FROM F.P.U.
  
 3) CONFIRMATION OF WATER METER PULL, OR COPY OF
 APPLICATION TO INSTALL A BACKFLOW PREVENTER, OR
 CONFIRMATION OF A HYDRANT METER BEING ORDERED TO KEEP
 THE DEMO WET.
  
 4) A PLUMBING PERMIT PULLED TO CAP THE SEWER LATERAL,
 AND A FINAL PLUMBING #703 REQUESTED TO CONFIRM THE
 COMPLETED CAPPING.
  
 5) A COPY OF RODENT LETTER. A LICENSED PEST CONTROL
 COMPANY WILL CONFIRM THEIR INSPECTION AND OR TREATMENT.
  
 6) A DEBRIS DISPOSAL FORM FILLED OUT. THIS CAN BE DONE
 AT PERMIT PICKUP.
  
 7) A NOTICE OF COMMENCEMENT, OR N.O.C.
  
 8) ENGINEERING AND HISTORIC DEPARTMENT SIGN OFF.
  
 ANY QUESTION, FEEL FREE TO CALL TOM AT 561-805-6669
  
 ??FIRST INSPECTION TO BE MADE AFTER ALL UTILITY
 CONNECTIONS HAVE BEEN
 DISCONNECTED AND SECURED IN SUCH MANNER THAT NO UNSAFE
 OR UNSANITARY CONDITIONS SHALL EXIST DURING OR AFTER
 DEMOLITION OPERATIONS.
  
 ??FINAL INSPECTION TO BE MADE AFTER ALL DEMOLITION WORK
 IS COMPLETED
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-07-31 Cont ID  
Sent By fgiaquin Date 2018-07-31 Time 06:16 Rev Time 0.00
Received By fgiaquin Date 2018-07-31 Time 06:12 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-07-24 Cont ID  
Sent By fgiaquin Date 2018-07-24 Time 06:05 Rev Time 0.00
Received By fgiaquin Date 2018-07-24 Time 05:55 Sent To P
Notes
2018-07-24 06:05:23ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE SUBMITTED FLOOR PLAN IS UNACCEPTABLE. PLEASE
 REVIEW THE FOLLOWING SECTIONS FROM THE WEST PALM BEACH
 AMENDMENTS TO THE FBC:
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 2. DEMOLITION NOTES 8, 9, AND 11 SAY (REFER TO
 ELECTRICAL DRAWINGS). PROVIDE ELECTRICAL DEMO PLAN FOR
 REVIEW, SIGNED AND SEALED BY A LICENSED DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS
 471.003(2)(H); 471.025; WPB FBC 107.2.1, 107.3.5
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2018-07-20 Cont ID  
Sent By cthroop Date 2018-07-20 Time 08:12 Rev Time 0.00
Received By hhall Date 2018-07-20 Time 08:12 Sent To HIST
Notes
2018-07-20 08:13:42PASSED - NO UTILITY CONFLICTS
 ADDRESS BUILDING COMMENTS

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-07-23 Cont ID  
Sent By cthroop Date 2018-07-23 Time 11:55 Rev Time 0.00
Received By fmittner Date 2018-07-23 Time 11:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-01 Cont ID  
Sent By cthroop Date 2018-08-01 Time 14:24 Rev Time 0.00
Received By cthroop Date 2018-07-27 Time 11:00 Sent To  
Notes
2018-07-30 11:00:54RESUB ROUTED TO FGIAQUINTO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-25 Cont ID  
Sent By tklarge Date 2018-07-25 Time 13:41 Rev Time 0.00
Received By tklarge Date 2018-07-11 Time 11:38 Sent To  
Notes
2018-07-13 11:23:55SHILL

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-07-25 Cont ID  
Sent By tklarge Date 2018-07-25 Time 13:41 Rev Time 0.00
Received By tklarge Date 2018-07-25 Time 13:36 Sent To I
Notes
***NONE***