Plan Review Details - Permit 18070454
Plan Review Stops For Permit 18070454
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-01-30 Cont ID  
Sent By pvalenti Date 2019-01-30 Time 08:47 Rev Time 0.00
Received By pvalenti Date 2019-01-30 Time 08:47 Sent To  
Notes
2019-01-30 09:41:14PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 THE OWNER SUBMITTED THE COUNTY RECEIPT FOR IMPACT FEES
 (# MU-2018-038733-0000).
  
 APPROVED WITH PROVISOS:
  
 1. FBC B 2403.2 THE MANUFACTURER'S DOCUMENTATION FOR
 THE NEW SHOWER FRAMELESS ENCLOSURE IS TO BE PROVIDED AT
 TIME OF INSPECTION AND SHALL BE IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE (BUILDING) SECTION 2403.2.
 2. FBC R 703.7.3 AT EXTERIOR WOOD FRAMED WALLS, (2)
 VAPOR PERMEABLE BARRIERS ARE TO BE INSPECTED PRIOR TO
 APPLICATION OF STUCCO AS PER THE FLORIDA BUILDING CODE
 (RESIDENTIAL) SECTION 703.7.3

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-12-26 Cont ID  
Sent By pvalenti Date 2018-12-26 Time 12:15 Rev Time 0.00
Received By pvalenti Date 2018-12-26 Time 12:15 Sent To  
Notes
2018-12-26 13:42:06****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 3RD REVIEW:
  
 PLEASE ADDRESS COMMENTS BELOW:
  
 1) COMPLIED LAST REVIEW.
  
 2) COMPLIED LAST REVIEW.
  
 3) COMPLIED LAST REVIEW.
  
 4) NOT COMPLIED. WE STILL NEED THE REGISTERED DESIGN
 PROFESSIONAL'S SIGNATURE, SEAL, AND TITLE BLOCK ON EACH
 PAGE/DOCUMENT AS PER LAST REVIEW:
 THE STRUCTURAL PLANS ARE REQUIRED TO HAVE THE
 ENGINEER?S ORIGINAL HANDWRITTEN SIGNATURE IN THE TITLE
 BLOCK ON EACH SHEET. FAC 61G15?23.003 PROCEDURES FOR
 PHYSICALLY SIGNING AND SEALING PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN
 ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025,
 F.S., AND RULE 61G15?23.001, F.A.C. MUST BE PHYSICALLY
 SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE
 USED.
 (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY
 CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY
 OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL
 NOT RENDER THE SIGNATURE ILLEGIBLE.
  
 5) COMPLIED (NOT APPLICABLE).
  
 6) NOT COMPLIED. THE SUBMITTED DOCUMENTATION (FLORIDA
 BUILDING CODE, ENERGY CONSERVATION AND ENERGY
 PERFORMANCE LEVEL DISPLAY CARD) ARE MISSING THE
 REQUIRED SIGNATURES AND DATES.
 COMMENTS FROM LAST REVIEW:
 PROVIDE ACCURATE AREA TABULATIONS FOR THE EXISTING
 CONDITIONED AND UNCONDITIONED SPACE, AS WELL AS, THE
 PROPOSED SPACES. FBC 107.2.1
  
 7) NOT COMPLIED. A MUNICIPAL IMPACT FEE RECEIPT
 (#MU-2018-038733-0000) FROM PALM BEACH COUNTY WAS
 SUBMITTED BUT WE ARE STILL MISSING THE RECEIPTS STAMPED
 ON THE PLAN COMPLETE WITH TRACKING NUMBER.
 COMMENTS FROM LAST REVIEW:
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL,
 ONE SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO
 PALM BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS
 WITH THE IMPACT FEE STAMP AND A COPY OF THE PAID
 RECEIPT MUST BE RETURNED TO THE CITY BUILDING
 DEPARTMENT BEFORE THE BUILDING PERMIT CAN BE ISSUED.
 FOR INFORMATION CALL PALM BEACH COUNTY IMPACT FEES AT
 (561) 233-5025.
  
 8) NOT COMPLIED. A FLORIDA BUILDING CODE, ENERGY
 CONSERVATION FORM #R 402 AND (EPL) DISPLAY CARD WERE
 SUBMITTED BUT NOT SIGNED AND DATED AS REQUIRED.
 COMMENTS FROM LAST REVIEW:
 MISSING PAGES FROM FORM THAT WAS SUBMITTED. SUBMIT
 ENERGY COMPLIANCE DOCUMENTS AS REQUIRED BY THE 2017 FBC
 ENERGY CONSERVATION SECTION R101.5.
  
 9) COMPLIED; THE INFORMATION FOR DOOR SHOULD BE
 SUBMITTED UNDER SEPERATE PERMIT # 18081459.
  
 10) COMPLIED; THE INFORMATION FOR WINDOW AND DOOR TYPES
 SHOULD BE SUBMITTED UNDER SEPERATE PERMIT # 18081459.
 PRODUCT APPROVALS FOR AN EXTERIOR DOOR #FL14320-R5 AND
 A FIXED WINDOW # FL15553-R3 WERE SUBMITTED.
  
 11) COMPLIED; THE INFORMATION FOR CASEMENT WINDOW
 SHOULD BE SUBMITTED UNDER SEPERATE PERMIT # 18081459.
  
 12) NOT COMPLIED. THE INFORMATION FOR THE BATHROOM
 WINDOWS SHOULD BE SUBMITTED UNDER SEPERATE PERMIT #
 18081459 BUT THE PRODUCT APPROVALS ARE STILL REQUIRED
 FOR THE GLAZING OF THE SHOWER ENCLOSURE.
 COMMENTS FROM LAST REVIEW:
 SPECIFY SAFETY GLAZING FOR THE SHOWER ENCLOSURE,
 THE MASTER BATH WINDOW AT THE TUB AND THE WINDOWS IN
 THE SHOWERS IF THEY ARE WITHIN 60" OF THE SHOWER FLOOR.
 FBC?R308.4
  
 13) COMPLIED LAST REVIEW.
  
 14) COMPLIED LAST REVIEW.
  
 15) COMPLIED; THE MEANING OF KSD AND TSD WAS CLARIFIED.
 KSD=KING STUD AND TSD=TRIMMER STUD.
 COMMENTS FROM LAST REVIEW:
 CLARIFY THE MEANING OF (2) KSD AND (2) TSD ON SHEET
 S4.0 OF THE PLANS. FBC 107.2.1
  
 16) COMPLIED LAST REVIEW.
  
 17) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE?SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 18) NOT COMPLIED. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED
 AND DRAWN UPON SUITABLE MATERIAL. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-10-26 Cont ID  
Sent By rmcdouga Date 2018-10-26 Time 13:52 Rev Time 0.00
Received By rmcdouga Date 2018-10-26 Time 07:54 Sent To  
Notes
2018-10-26 11:36:24PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMPLIED. THE ARCHITECTURAL PLANS HAVE SEVERAL
 REFERENCES TO THE FBC FIFTH EDITION (2014). THE FBC
 SIXTH EDITION (2017) WENT INTO EFFECT ON JANUARY 1,
 2018. ALL NEW PERMITS APPLIED FOR ON OR AFTER THAT DATE
 ARE REQUIRED TO COMPLY WITH AND REFERENCE THE FBC SIXTH
 EDITION (2017). UPDATE THE CODE REFERENCES ON THE
 PLANS. FS CHAPTER 553
  
 2) COMPLIED. SCOPE OF WORK WAS REDUCED.THE VALUATION OF
 $75,000.00 FOR THIS PROJECT APPEARS TO BE LOW. SUBMIT A
 DETAILED LINE ITEM COST ESTIMATE FOR THE ENTIRE SCOPE
 OF WORK, INCLUDING DESIGN FEES, OVERHEAD AND PROFIT.
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 3) COMPLIED. SCOPE OF WORK WAS REDUCED. THE CITY OF
 WEST PALM BEACH'S FLOOD ORDINANCE REQUIRES ALL PROJECTS
 THAT ARE CONSIDERED SUBSTANTIAL IMPROVEMENTS MEET THE
 CURRENT RULES FOR CONSTRUCTION IN A SPECIAL FLOOD
 HAZARD AREA. SUBSTANTIAL IMPROVEMENT MEANS ANY
 COMBINATION OF REPAIR, RECONSTRUCTION, REHABILITATION,
 ALTERATION, ADDITION, OR OTHER IMPROVEMENT OF A
 BUILDING OR STRUCTURE, FOR WHICH THE CUMULATIVE COST IN
 ANY FIVE YEAR PERIOD EQUALS OR EXCEEDS 50 PERCENT OF
 THE MARKET VALUE OF THE BUILDING OR STRUCTURE AT THE
 END OF THE FIVE YEAR PERIOD AND BEFORE THE IMPROVEMENT
 OR REPAIR IS STARTED. IF THE STRUCTURE HAS INCURRED
 "SUBSTANTIAL DAMAGE," ANY REPAIRS ARE CONSIDERED
 SUBSTANTIAL IMPROVEMENT REGARDLESS OF THE ACTUAL REPAIR
 WORK PERFORMED.
 ACCORDING TO THE FLOOD INSURANCE RATE MAP WHICH WAS
 ADOPTED ON OCTOBER 5, 2017 BY THE CITY OF WEST PALM
 BEACH AND IS APPLICABLE TO THIS PROJECT, THE STRUCTURE
 IS LOCATED IN AN AE FLOOD ZONE WHICH IS A SPECIAL FLOOD
 HAZARD AREA. THE BASE FLOOD ELEVATION FOR THE PROPERTY
 IS 7' NAVD 88. THE CITY OF WEST PALM BEACH HAS ADOPTED
 A FLOOD ORDINANCE THAT REQUIRES A TWO (2) FOOT FREE
 BOARD. THIS MEANS THAT THE LOWEST FLOOR AND ALL
 EQUIPMENT SERVICING THE RESIDENCE IS REQUIRED TO BE AT
 OR ABOVE 9' NAVD 88. THE GARAGE AND STORAGE CAN BE
 BELOW BFE, IF FLOOD VENTS ARE INSTALLED AND NO
 MATERIALS OR EQUIPMENT THAT CAN BE DAMAGED BY FLOOD
 WATERS ARE BELOW BFE. SHOW COMPLIANCE WITH THESE
 REQUIREMENTS ON THE PLANS. SPECIFY ALL ELEVATIONS IN
 NAVD 88 ON ALL CONSTRUCTION DOCUMENTS, SUCH AS,
 SURVEYS, SITE PLANS, ARCHITECTURAL PLANS AND ELEVATION
 CERTIFICATES.
  
 4) THE STRUCTURAL PLANS ARE REQUIRED TO HAVE THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE IN THE TITLE
 BLOCK ON EACH SHEET. FAC 61G15-23.003 PROCEDURES FOR
 PHYSICALLY SIGNING AND SEALING PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN
 ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025,
 F.S., AND RULE 61G15-23.001, F.A.C. MUST BE PHYSICALLY
 SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE
 USED.
 (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY
 CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY
 OVERLAPPING THE LICENSEE'S SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL
 NOT RENDER THE SIGNATURE ILLEGIBLE.
  
 5) SPECIFY THE TERMITE PROTECTION THAT WILL BE PROVIDED
 ON THE PLANS. R318.1 TERMITE PROTECTION SHALL BE
 PROVIDED BY REGISTERED TERMITICIDES, INCLUDING SOIL
 APPLIED PESTICIDES, BAITING SYSTEMS, AND PESTICIDES
 APPLIED TO WOOD, OR OTHER APPROVED METHODS OF TERMITE
 PROTECTION LABELED FOR USE AS A PREVENTATIVE TREATMENT
 TO NEW CONSTRUCTION. SEE SECTION 202, ?REGISTERED
 TERMITICIDE.? UPON COMPLETION OF THE APPLICATION OF THE
 TERMITE PROTECTIVE TREATMENT, A CERTIFICATE OF
 COMPLIANCE SHALL BE ISSUED TO THE BUILDING DEPARTMENT
 BY THE LICENSED PEST CONTROL COMPANY THAT CONTAINS THE
 FOLLOWING STATEMENT: "THE BUILDING HAS RECEIVED A
 COMPLETE TREATMENT FOR THE PREVENTION OF SUBTERRANEAN
 TERMITES. TREATMENT IS IN ACCORDANCE WITH RULES AND
 LAWS ESTABLISHED BY THE FLORIDA DEPARTMENT OF
 AGRICULTURE AND CONSUMER SERVICES."
  
 6) PROVIDE ACCURATE AREA TABULATIONS FOR THE EXISTING
 CONDITIONED AND UNCONDITIONED SPACE, AS WELL AS, THE
 PROPOSED SPACES. FBC 107.2.1
  
 7) BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL,
 ONE SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO
 PALM BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS
 WITH THE IMPACT FEE STAMP AND A COPY OF THE PAID
 RECEIPT MUST BE RETURNED TO THE CITY BUILDING
 DEPARTMENT BEFORE THE BUILDING PERMIT CAN BE ISSUED.
 FOR INFORMATION CALL PALM BEACH COUNTY IMPACT FEES AT
 (561) 233-5025.
  
 8) MISSING PAGES FROM FORM THAT WAS SUBMITTED. SUBMIT
 ENERGY COMPLIANCE DOCUMENTS AS REQUIRED BY THE 2017 FBC
 ENERGY CONSERVATION SECTION R101.5.
  
 9) SHOW THAT THE DOOR FROM THE GARAGE TO THE DEN
 COMPLIES WITH FBC-R302.5.1
  
 10) IDENTIFY THE WINDOW AND DOOR TYPES ON THE PLANS.
 FBC 107.2.1
  
 11) PROVIDE THE CLEAR OPENING SIZE OF THE ACW 2828
 CASEMENT WINDOW IN BEDROOM #2 TO SHOW THAT IT COMPLIES
 WITH FBC-R310.1 FOR EMERGENCY ESCAPE AND RESCUE
 OPENINGS.
  
 12) SPECIFY SAFETY GLAZING FOR THE SHOWER ENCLOSURE,
 THE MASTER BATH WINDOW AT THE TUB AND THE WINDOWS IN
 THE SHOWERS IF THEY ARE WITHIN 60" OF THE SHOWER FLOOR.
 FBC-R308.4
  
 13) COMPLIED. EXISTING ROOF SYSTEM TO REMAIN. SHOW
 COMPLIANCE WITH FBC-R806.1 FOR ATTIC VENTILATION.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN OR SNOW. VENTILATION OPENINGS SHALL
 HAVE A LEAST DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM
 AND 1/4 INCH (6.4 MM) MAXIMUM. VENTILATION OPENINGS
 HAVING A LEAST DIMENSION LARGER THAN 1/4 INCH (6.4 MM)
 SHALL BE PROVIDED WITH CORROSION-RESISTANT WIRE CLOTH
 SCREENING, HARDWARE CLOTH OR SIMILAR MATERIAL WITH
 OPENINGS HAVING A LEAST DIMENSION OF 1/16 INCH (1.6 MM)
 MINIMUM AND 1/4 INCH (6.4 MM) MAXIMUM. OPENINGS IN ROOF
 FRAMING MEMBERS SHALL CONFORM TO THE REQUIREMENTS OF
 SECTION R802.7. REQUIRED VENTILATION OPENINGS SHALL
 OPEN DIRECTLY TO THE OUTSIDE AIR. R806.2 THE MINIMUM
 NET FREE VENTILATING AREA SHALL BE 1/150 OF THE AREA OF
 THE VENTED SPACE.
  
 14) COMPLIED. EXISTING ATTIC ACCESS. SHOW COMPLIANCE
 WITH R807.1 ATTIC ACCESS. BUILDINGS WITH COMBUSTIBLE
 CEILING OR ROOF CONSTRUCTION SHALL HAVE AN ATTIC ACCESS
 OPENING TO ATTIC AREAS THAT HAVE A VERTICAL HEIGHT OF
 30 INCHES OR GREATER OVER AN AREA OF NOT LESS THAN 30
 SQUARE FEET. THE VERTICAL HEIGHT SHALL BE MEASURED FROM
 THE TOP OF THE CEILING FRAMING MEMBERS TO THE UNDERSIDE
 OF THE ROOF FRAMING MEMBERS. THE ROUGH-FRAMED OPENING
 SHALL BE NOT LESS THAN 22 INCHES BY 30 INCHES (559 MM
 BY 762 MM) AND SHALL BE LOCATED IN A HALLWAY OR OTHER
 READILY ACCESSIBLE LOCATION. WHERE LOCATED IN A WALL,
 THE OPENING SHALL BE NOT LESS THAN 22 INCHES WIDE BY 30
 INCHES HIGH. WHERE THE ACCESS IS LOCATED IN A CEILING,
 MINIMUM UNOBSTRUCTED HEADROOM IN THE ATTIC SPACE SHALL
 BE 30 INCHES AT SOME POINT ABOVE THE ACCESS MEASURED
 VERTICALLY FROM THE BOTTOM OF CEILING FRAMING MEMBERS.
 SEE SECTION M1305.1.3 FOR ACCESS REQUIREMENTS WHERE
 MECHANICAL EQUIPMENT IS LOCATED IN ATTICS.
  
 15) CLARIFY THE MEANING OF (2) KSD AND (2) TSD ON SHEET
 S4.0 OF THE PLANS. FBC 107.2.1
  
 16) COMPLIED. PRODUCT APPROVALS FOR FIXED WINDOWS,
 IN-SWING FRENCH DOORS AND BALCONY DECKING WERE
 SUBMITTED. FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT
 APPROVALS FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, WINDOW (GLASS TYPES), STRUCTURAL
 MULLIONS AND EXTERIOR DOOR TYPES.
  
 17) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 18) NEW COMMENT. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED
 AND DRAWN UPON SUITABLE MATERIAL. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
 19) NEW COMMENT. PROVIDE TWO COMPLETE SETS OF PLANS AND
 OTHER CONSTRUCTION DOCUMENTS.
 RE-SUBMITTAL PROCEDURE
 YOU ARE REQUIRED TO FILL OUT A RE-SUBMITTAL FORM TO BE
 SUBMITTED WITH THE CORRECTED PLANS AND/OR OTHER
 DOCUMENTS. THE PERMIT CLERK WILL RETRIEVE THE DENIED
 APPLICATION, PLANS AND OTHER DOCUMENTS FOR YOU. YOU ARE
 REQUIRED TO REMOVE THE OLD PLAN SHEETS THAT HAVE BEEN
 CORRECTED AND REPLACE THEM WITH THE NEW ONES. THE CLERK
 WILL PROVIDE YOU WITH A STAPLE REMOVER AND A STAPLER.
 ONE SET OF THE OLD PLAN SHEETS THAT HAVE BEEN REMOVED
 SHALL BE MARKED AS VOIDED AND RESUBMITTED ALONG WITH
 THE TWO (OR MORE) SETS THAT CONTAIN THE CORRECTED
 SHEETS. IF THERE ARE ANY SHEETS THAT HAVE BEEN STAMPED
 FOR COUNTY IMPACT FEES, HOA APPROVAL STAMPS OR OTHERS,
 RESUBMIT THOSE SHEETS.
 IF ALL OF THE PLAN SHEETS HAVE BEEN CORRECTED, THEN TWO
 (OR MORE) SETS OF THE NEW PLANS AND ANY OTHER DOCUMENTS
 SHALL BE SUBMITTED.
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-27 Cont ID  
Sent By rmcdouga Date 2018-08-27 Time 16:55 Rev Time 0.00
Received By rmcdouga Date 2018-08-21 Time 19:10 Sent To  
Notes
2018-08-27 08:37:46PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ARCHITECTURAL PLANS HAVE SEVERAL REFERENCES TO
 THE FBC FIFTH EDITION (2014). THE FBC SIXTH EDITION
 (2017) WENT INTO EFFECT ON JANUARY 1, 2018. ALL NEW
 PERMITS APPLIED FOR ON OR AFTER THAT DATE ARE REQUIRED
 TO COMPLY WITH AND REFERENCE THE FBC SIXTH EDITION
 (2017). UPDATE THE CODE REFERENCES ON THE PLANS. FS
 CHAPTER 553
  
 2) THE VALUATION OF $75,000.00 FOR THIS PROJECT APPEARS
 TO BE LOW. SUBMIT A DETAILED LINE ITEM COST ESTIMATE
 FOR THE ENTIRE SCOPE OF WORK, INCLUDING DESIGN FEES,
 OVERHEAD AND PROFIT. FBC 109.3 BUILDING PERMIT
 VALUATION. FOR PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE
 TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND
 DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT;
 EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL CODE
 CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET
 BY THE BUILDING OFFICIAL.
  
 3) THE CITY OF WEST PALM BEACH'S FLOOD ORDINANCE
 REQUIRES ALL PROJECTS THAT ARE CONSIDERED SUBSTANTIAL
 IMPROVEMENTS MEET THE CURRENT RULES FOR CONSTRUCTION IN
 A SPECIAL FLOOD HAZARD AREA. SUBSTANTIAL IMPROVEMENT
 MEANS ANY COMBINATION OF REPAIR, RECONSTRUCTION,
 REHABILITATION, ALTERATION, ADDITION, OR OTHER
 IMPROVEMENT OF A BUILDING OR STRUCTURE, FOR WHICH THE
 CUMULATIVE COST IN ANY FIVE YEAR PERIOD EQUALS OR
 EXCEEDS 50 PERCENT OF THE MARKET VALUE OF THE BUILDING
 OR STRUCTURE AT THE END OF THE FIVE YEAR PERIOD AND
 BEFORE THE IMPROVEMENT OR REPAIR IS STARTED. IF THE
 STRUCTURE HAS INCURRED "SUBSTANTIAL DAMAGE," ANY
 REPAIRS ARE CONSIDERED SUBSTANTIAL IMPROVEMENT
 REGARDLESS OF THE ACTUAL REPAIR WORK PERFORMED.
 ACCORDING TO THE FLOOD INSURANCE RATE MAP WHICH WAS
 ADOPTED ON OCTOBER 5, 2017 BY THE CITY OF WEST PALM
 BEACH AND IS APPLICABLE TO THIS PROJECT, THE STRUCTURE
 IS LOCATED IN AN AE FLOOD ZONE WHICH IS A SPECIAL FLOOD
 HAZARD AREA. THE BASE FLOOD ELEVATION FOR THE PROPERTY
 IS 7' NAVD 88. THE CITY OF WEST PALM BEACH HAS ADOPTED
 A FLOOD ORDINANCE THAT REQUIRES A TWO (2) FOOT FREE
 BOARD. THIS MEANS THAT THE LOWEST FLOOR AND ALL
 EQUIPMENT SERVICING THE RESIDENCE IS REQUIRED TO BE AT
 OR ABOVE 9' NAVD 88. THE GARAGE AND STORAGE CAN BE
 BELOW BFE, IF FLOOD VENTS ARE INSTALLED AND NO
 MATERIALS OR EQUIPMENT THAT CAN BE DAMAGED BY FLOOD
 WATERS ARE BELOW BFE. SHOW COMPLIANCE WITH THESE
 REQUIREMENTS ON THE PLANS. SPECIFY ALL ELEVATIONS IN
 NAVD 88 ON ALL CONSTRUCTION DOCUMENTS, SUCH AS,
 SURVEYS, SITE PLANS, ARCHITECTURAL PLANS AND ELEVATION
 CERTIFICATES.
  
 4) THE STRUCTURAL PLANS ARE REQUIRED TO HAVE THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE IN THE TITLE
 BLOCK ON EACH SHEET. FAC 61G15-23.003 PROCEDURES FOR
 PHYSICALLY SIGNING AND SEALING PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN
 ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025,
 F.S., AND RULE 61G15-23.001, F.A.C. MUST BE PHYSICALLY
 SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE
 USED.
 (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY
 CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY
 OVERLAPPING THE LICENSEE'S SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL
 NOT RENDER THE SIGNATURE ILLEGIBLE.
  
 5) SPECIFY THE TERMITE PROTECTION THAT WILL BE PROVIDED
 ON THE PLANS. R318.1 TERMITE PROTECTION SHALL BE
 PROVIDED BY REGISTERED TERMITICIDES, INCLUDING SOIL
 APPLIED PESTICIDES, BAITING SYSTEMS, AND PESTICIDES
 APPLIED TO WOOD, OR OTHER APPROVED METHODS OF TERMITE
 PROTECTION LABELED FOR USE AS A PREVENTATIVE TREATMENT
 TO NEW CONSTRUCTION. SEE SECTION 202, ?REGISTERED
 TERMITICIDE.? UPON COMPLETION OF THE APPLICATION OF THE
 TERMITE PROTECTIVE TREATMENT, A CERTIFICATE OF
 COMPLIANCE SHALL BE ISSUED TO THE BUILDING DEPARTMENT
 BY THE LICENSED PEST CONTROL COMPANY THAT CONTAINS THE
 FOLLOWING STATEMENT: ?THE BUILDING HAS RECEIVED A
 COMPLETE TREATMENT FOR THE PREVENTION OF SUBTERRANEAN
 TERMITES. TREATMENT IS IN ACCORDANCE WITH RULES AND
 LAWS ESTABLISHED BY THE FLORIDA DEPARTMENT OF
 AGRICULTURE AND CONSUMER SERVICES.?
  
 6) PROVIDE ACCURATE AREA TABULATIONS FOR THE EXISTING
 CONDITIONED AND UNCONDITIONED SPACE, AS WELL AS, THE
 PROPOSED SPACES. FBC 107.2.1
  
 7) BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL,
 ONE SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO
 PALM BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS
 WITH THE IMPACT FEE STAMP AND A COPY OF THE PAID
 RECEIPT MUST BE RETURNED TO THE CITY BUILDING
 DEPARTMENT BEFORE THE BUILDING PERMIT CAN BE ISSUED.
 FOR INFORMATION CALL PALM BEACH COUNTY IMPACT FEES AT
 (561) 233-5025.
  
 8) SUBMIT ENERGY COMPLIANCE DOCUMENTS AS REQUIRED BY
 THE 2017 FBC ENERGY CONSERVATION SECTION R101.5.
  
 9) SHOW THAT THE DOOR FROM THE GARAGE TO THE DEN
 COMPLIES WITH FBC-R302.5.1
  
 10) IDENTIFY THE WINDOW AND DOOR TYPES ON THE PLANS.
 FBC 107.2.1
  
 11) PROVIDE THE CLEAR OPENING SIZE OF THE ACW 2828
 CASEMENT WINDOW IN BEDROOM #2 TO SHOW THAT IT COMPLIES
 WITH FBC-R310.1 FOR EMERGENCY ESCAPE AND RESCUE
 OPENINGS.
  
 12) SPECIFY SAFETY GLAZING FOR THE SHOWER ENCLOSURE,
 THE MASTER BATH WINDOW AT THE TUB AND THE WINDOWS IN
 THE SHOWERS IF THEY ARE WITHIN 60" OF THE SHOWER FLOOR.
 FBC-R308.4
  
 13) SHOW COMPLIANCE WITH FBC-R806.1 FOR ATTIC
 VENTILATION. ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES
 FORMED WHERE CEILINGS ARE APPLIED DIRECTLY TO THE
 UNDERSIDE OF ROOF RAFTERS SHALL HAVE CROSS VENTILATION
 FOR EACH SEPARATE SPACE BY VENTILATING OPENINGS
 PROTECTED AGAINST THE ENTRANCE OF RAIN OR SNOW.
 VENTILATION OPENINGS SHALL HAVE A LEAST DIMENSION OF
 1/16 INCH (1.6 MM) MINIMUM AND 1/4 INCH (6.4 MM)
 MAXIMUM. VENTILATION OPENINGS HAVING A LEAST DIMENSION
 LARGER THAN 1/4 INCH (6.4 MM) SHALL BE PROVIDED WITH
 CORROSION-RESISTANT WIRE CLOTH SCREENING, HARDWARE
 CLOTH OR SIMILAR MATERIAL WITH OPENINGS HAVING A LEAST
 DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM AND 1/4 INCH
 (6.4 MM) MAXIMUM. OPENINGS IN ROOF FRAMING MEMBERS
 SHALL CONFORM TO THE REQUIREMENTS OF SECTION R802.7.
 REQUIRED VENTILATION OPENINGS SHALL OPEN DIRECTLY TO
 THE OUTSIDE AIR. R806.2 THE MINIMUM NET FREE
 VENTILATING AREA SHALL BE 1/150 OF THE AREA OF THE
 VENTED SPACE.
  
 14) SHOW COMPLIANCE WITH R807.1 ATTIC ACCESS. BUILDINGS
 WITH COMBUSTIBLE CEILING OR ROOF CONSTRUCTION SHALL
 HAVE AN ATTIC ACCESS OPENING TO ATTIC AREAS THAT HAVE A
 VERTICAL HEIGHT OF 30 INCHES OR GREATER OVER AN AREA OF
 NOT LESS THAN 30 SQUARE FEET. THE VERTICAL HEIGHT SHALL
 BE MEASURED FROM THE TOP OF THE CEILING FRAMING MEMBERS
 TO THE UNDERSIDE OF THE ROOF FRAMING MEMBERS. THE
 ROUGH-FRAMED OPENING SHALL BE NOT LESS THAN 22 INCHES
 BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE LOCATED IN
 A HALLWAY OR OTHER READILY ACCESSIBLE LOCATION. WHERE
 LOCATED IN A WALL, THE OPENING SHALL BE NOT LESS THAN
 22 INCHES WIDE BY 30 INCHES HIGH. WHERE THE ACCESS IS
 LOCATED IN A CEILING, MINIMUM UNOBSTRUCTED HEADROOM IN
 THE ATTIC SPACE SHALL BE 30 INCHES AT SOME POINT ABOVE
 THE ACCESS MEASURED VERTICALLY FROM THE BOTTOM OF
 CEILING FRAMING MEMBERS. SEE SECTION M1305.1.3 FOR
 ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS
 LOCATED IN ATTICS.
  
 15) CLARIFY THE MEANING OF (2) KSD AND (2) TSD ON SHEET
 S4.0 OF THE PLANS. FBC 107.2.1
  
 16) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, WINDOW (GLASS TYPES), STRUCTURAL
 MULLIONS AND EXTERIOR DOOR TYPES.
  
 17) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2019-01-21 Cont ID  
Sent By jpearson Date 2019-01-21 Time 10:16 Rev Time 0.00
Received By jpearson Date 2019-01-21 Time 10:16 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2018-12-27 Cont ID  
Sent By cthroop Date 2018-12-27 Time 10:48 Rev Time 0.00
Received By cthroop Date 2018-12-27 Time 09:40 Sent To  
Notes
2018-12-27 11:34:31ELECTRICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 4TH REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. TANKLESS WATER HEATER REMOVED FROM PLAN - COMPLIED.
 LOCATION OF NEW INTERIOR PANEL NOT SHOWN ON PLAN. FBC
 107.2.1 - NOT ADDRESSED.
  
 2. MINIMUM OF 2 GROUND RODS - COMPLIED.
  
 3. RISER DIAGRAM AND SERVICE TYPE - COMPLIED.
  
 4. A/C COMPRESSOR AND AIR HANDLER NOT LISTED IN LOAD
 CALC. - NOT ADDRESSED.
 PROVIDE ACCURATE LOAD CALCULATIONS INCLUDING ALL LOADS.
 - NOT ADDRESSED.
  
 5. SMOKE DETECTOR/CO DETECTOR COMBO. LOCATED OUTSIDE
 M-BED. - COMPLIED.
 NOTE: COMBO WILL BE REQUIRED ON 1ST FLOOR ALSO.
 INSPECTOR WILL VERIFY.
  
 6. PROVIDE PANEL SCHEDULE. LIST ALL NEW CIRCUTS.
 IDENTIFY ALL CIRCUTS REQUIRING AFCI AND GFCI
 PROTECTION. - NOT ADDRESSED.
  
 7. SUBMITTAL INCLUDES TWO COMPLETE SETS. - COMPLIED.
  
 NEW COMMENT:
  
 8. FEEDER CONDUCTOR SIZE ON RISER INDICATES 3 - 1/0
 CONDUCTORS. FEEDER CONDUCTOR SIZE AT PANEL SCHEDULE
 INDICATES 3 - #2 CONDUCTORS. PLEASE CLARIFY.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2018-09-30 Cont ID  
Sent By jpearson Date 2018-09-30 Time 15:30 Rev Time 0.00
Received By jpearson Date 2018-09-30 Time 15:30 Sent To  
Notes
2018-09-30 15:25:10CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. TANKLESS WATER HEATER AND LOCATION OF NEW INTERIOR
 PANEL NOT ON PLAN, PROVIDE LOCATION. FBC 107.2.1 (NOT
 ADDRESSED)
  
 2. MINIMUM OF 2 GROUND RODS REQUIRED 250.53A2 NEC (NOT
 ADDRESSED)
  
 3. PROVIDE RISER DIAGRAM OF EXISTING RESIDENTIAL
 SERVICE. OVERHEAD SERVICE? UNDERGROUND SERVICE? WIRE
 SIZE? NEC 220.16A1&2, 220.12, 220.14
 FBC RE 3602.1, FBC RE 3602.2, FBC 107.2.1 (NOT
 ADDRESSED)
  
 4. A/C COMPRESSORS AND AHU'S FED FROM METE/MAIN COMBO
 NOT IN LOAD CALC, ALSO TANKLESS WATER HEATER NOT IN
 LOAD CALC. PROVIDE ACCURATE LOAD CALCULATION INCLUDING
 ALL LOADS. NEC 220; FBC RE E3602.2 (NOT ADDRESSED)
  
 5. HOUSE HAS ATTACHED GARAGE. SMOKE ALARMS OF OUTSIDE
 OF BEDROOMS MUST BE SMOKE/CARBON MONOXIDE COMBINATION
 ALARMS WITHIN 10'. FBC R 315.1 FBC R 315.13 (NOT
 ADDRESSED)
  
 6. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS FOR ALL PANELS (METER/MAIN COMBO HAS NO PANEL
 SCHEDULE), THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. NEC 210.8, 210.12, 215.5, 408.4;
 WPB FBC 107.3.5; FBC RE E3706.2, E3902 (NOT ADDRESSED)
  
 INFORMATIONAL NOTE: TO MY KNOWLEDGE A 300AMP METER/MAIN
 COMBO IS NOT SOLD PLEASE VERIFY AND PROVIDE MORE
 INFORMATION. FBC 107.2.1 (NOT ADDRESSED)
  
 NEW COMMENT:
  
 7. PLAN SHOULD BE SUBMITTED AS 2 COMPLETE SETS.
 CURRENTLY, IT APPEARS THERE IS ONLY ONE SET IN PACKAGE
 AND A LOT OF ADDITIONAL SHEETS, MANY WHICH APPEAR TO BE
 OLD SHEETS FROM FIRST REVIEW. THIS REVIEWER IS NOT ABLE
 TO DETERMINE WHAT IS THE NEW SUBMISSION. A RESPONSE
 LETTER ADDRESSING THE ELECTRICAL COMMENTS COULD NOT BE
 FOUND. FURTHER COMMENT MAY BE NECESSARY AS MUSH OF THE
 INFORMATION REQUESTED IS MISSING FROM THIS SUBMISSION.
 WPB FBC 107.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-08-08 Cont ID  
Sent By fgiaquin Date 2018-08-08 Time 06:13 Rev Time 0.00
Received By fgiaquin Date 2018-08-08 Time 05:28 Sent To  
Notes
2018-08-08 06:13:55ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. TANKLESS WATER HEATER AND LOCATION OF NEW INTERIOR
 PANEL NOT ON PLAN, PROVIDE LOCATION. FBC 107.2.1
  
 2. MINIMUM OF 2 GROUND RODS REQUIRED 250.53A2 NEC
  
 3. PROVIDE RISER DIAGRAM OF EXISTING RESIDENTIAL
 SERVICE. OVERHEAD SERVICE? UNDERGROUND SERVICE? WIRE
 SIZE? NEC 220.16A1&2, 220.12, 220.14
 FBC RE 3602.1, FBC RE 3602.2, FBC 107.2.1
  
 4. A/C COMPRESSORS AND AHU'S FED FROM METE/MAIN COMBO
 NOT IN LOAD CALC, ALSO TANKLESS WATER HEATER NOT IN
 LOAD CALC. PROVIDE ACCURATE LOAD CALCULATION INCLUDING
 ALL LOADS. NEC 220; FBC RE E3602.2
  
 5. HOUSE HAS ATTACHED GARAGE. SMOKE ALARMS OF OUTSIDE
 OF BEDROOMS MUST BE SMOKE/CARBON MONOXIDE COMBINATION
 ALARMS WITHIN 10'. FBC R 315.1 FBC R 315.13
  
 6. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS FOR ALL PANELS (METER/MAIN COMBO HAS NO PANEL
 SCHEDULE), THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. NEC 210.8, 210.12, 215.5, 408.4;
 WPB FBC 107.3.5; FBC RE E3706.2, E3902
  
 INFORMATIONAL NOTE: TO MY KNOWLEDGE A 300AMP METER/MAIN
 COMBO IS NOT SOLD PLEASE VERIFY AND PROVIDE MORE
 INFORMATION. FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-12-27 Cont ID  
Sent By cthroop Date 2018-12-27 Time 09:40 Rev Time 0.00
Received By cthroop Date 2018-12-21 Time 10:38 Sent To  
Notes
2018-12-27 09:40:42SEE COMMENTS FROM 2ND AND 3RD ELECTRICAL REVIEW. CT

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2019-02-19 Cont ID  
Sent By cthroop Date 2019-02-19 Time 09:06 Rev Time 0.00
Received By cthroop Date 2019-02-19 Time 08:16 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2018-10-16 Cont ID  
Sent By gjohnson Date 2018-10-16 Time 14:41 Rev Time 0.00
Received By gjohnson Date 2018-10-16 Time 14:41 Sent To  
Notes
2018-10-16 15:14:21GAS PLAN REVIEW: IT APPEARS THAT THE GAS WORK WAS
 REMOVED FROM THE APPLICATION SEE PLUMBING COMMENTS.
  
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-08-30 Cont ID  
Sent By shill Date 2018-08-30 Time 13:59 Rev Time 0.00
Received By jesmith Date 2018-08-30 Time 13:59 Sent To  
Notes
2018-08-30 14:00:441ST REVIEW: FBC 2017 6TH EDITION
 DENIED
  
 GENERAL COMMENT:PLAN SHEET T-0 INDICATES APPLICABLE
 CODES ARE FBC 5TH ADDITION; APPLICABLE CODES ADOPTED BY
 WPB ARE 6TH ADDITION. PLEASE COMPLY
  
 GAS REVIEW
  
 1. SUBMIT MANUFACTURERS SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2; INCLUDE
 TANKLESS WATER HEATER, RANGE AND DRYER
  
 2. DRYER AND TANKLESS WATER HEATER ARE SHOWN ON RISER
 DIAGRAM AND IN THE CALCULATIONS. PLEASE SHOW LOCATIONS
 ON PLAN.
 THE TANKLESS HEATER IF MOUNTED ON BUILDING EXTERIOR
 SHALL BE MOUNTED A MIN OF 4' FROM ANY OPENING IN
 BUILDING OR IF INSIDE REQUIRES COMBUSTION AIR FROM
 OUTSIDE AND EXHAUST VENT TO OUTSIDE IN ACCORDANCE WITH
 FBC G2407 AND MANUFACTURERS SPECS.SHOW VENT AND EXHAUST
 ROUTING ON PLAN.
  
 3. PLEASE SHOW METER ON THE FLOOR PLAN. PER WPB AMEND
 TO FBC 107.2.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-02-19 Cont ID  
Sent By cthroop Date 2019-02-19 Time 09:06 Rev Time 0.00
Received By cthroop Date 2019-01-16 Time 14:18 Sent To  
Notes
2019-02-16 10:08:492/16 REMOVED FROM R32 AND ROUTED TO CT DESK / S.HILL
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-12-27 Cont ID  
Sent By cthroop Date 2018-12-27 Time 09:39 Rev Time 0.00
Received By cthroop Date 2018-11-28 Time 15:12 Sent To  
Notes
2018-12-27 09:39:33 
  
2018-11-29 15:12:19R32

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-29 Cont ID  
Sent By shill Date 2018-10-29 Time 08:02 Rev Time 0.00
Received By shill Date 2018-09-25 Time 13:05 Sent To  
Notes
2018-10-29 07:52:58TO JP DESK
  
2018-10-01 10:59:59R39
2018-09-27 13:05:34LIBRARY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-30 Cont ID  
Sent By shill Date 2018-08-30 Time 14:21 Rev Time 0.00
Received By shill Date 2018-07-11 Time 12:51 Sent To  
Notes
2018-07-13 12:51:55R01

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2019-02-19 Cont ID  
Sent By cthroop Date 2019-02-19 Time 08:30 Rev Time 0.00
Received By cthroop Date 2019-02-19 Time 08:19 Sent To  
Notes
2019-02-19 08:30:46MU-2018-038733-0000. CT

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2019-02-11 Cont ID  
Sent By hmoser Date 2019-02-11 Time 14:52 Rev Time 0.00
Received By hmoser Date 2019-02-11 Time 14:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-12-27 Cont ID  
Sent By cthroop Date 2018-12-27 Time 08:28 Rev Time 0.00
Received By cthroop Date 2018-12-21 Time 10:38 Sent To  
Notes
2018-12-27 09:21:42MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE MECHANICAL PLAN FOR PROPOSED WORK. SUBMITTAL
 INCLUDES TWO PAGES MARKED EXISTING MECHANICAL.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 2. PROVIDE ENERGY SUBMITTAL.
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 _ OR _
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
 (MANDATORY).
 THE BUILDING OFFICIAL SHALL REQUIRE THAT AN ENERGY
 PERFORMANCE LEVEL (EPL) DISPLAY CARD BE COMPLETED AND
 CERTIFIED BY THE BUILDER TO BE ACCURATE AND CORRECT
 BEFORE FINAL APPROVAL OF THE BUILDING FOR OCCUPANCY.
 FLORIDA LAW [SECTION 553.9085, FLORIDA STATUTES)]
 REQUIRES THE EPL DISPLAY CARD TO BE INCLUDED AS AN
 ADDENDUM TO EACH SALES CONTRACT FOR BOTH PRESOLD AND
 NON-PRESOLD RESIDENTIAL BUILDINGS. THE EPL DISPLAY CARD
 CONTAINS INFORMATION INDICATING THE ENERGY PERFORMANCE
 LEVEL AND EFFICIENCIES OF COMPONENTS INSTALLED IN A
 DWELLING UNIT. THE BUILDING OFFICIAL SHALL VERIFY THAT
 THE EPL DISPLAY CARD COMPLETED AND SIGNED BY THE
 BUILDER ACCURATELY REFLECTS THE PLANS AND
 SPECIFICATIONS SUBMITTED TO DEMONSTRATE CODE COMPLIANCE
 FOR THE BUILDING. A COPY OF THE EPL DISPLAY CARD CAN BE
 FOUND IN APPENDIX C.
  
 3. PROPERTY IS LOCATED IN FLOOD ZONE AE WITH A BASE
 FLOOD ELEVATION (BFE) OF 7.0 FEET NAVD. IF A NEW
 CONDENSING UNIT IS INSTALLED IT MUST SET AT OR ABOVE
 THE DESIGN FLOOD ELEVATION (DFE) OF 9.0 FEET NAVD.
  
 4. PROVIDE EXHAST FOR PROPOSED BATHROOM PER TABLE
 M1507.4.
  
 5. PROVIDE BALANCED AIR RETURNS FOR NEW MECHANICAL
 SYSTEM PER SECTION M1602.
  
 6. NEW DUCT WORK SHALL BE DESIGNED TO COMPLY WITH
 SECTION M1601.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-10-17 Cont ID  
Sent By cmontell Date 2018-10-17 Time 14:42 Rev Time 0.00
Received By cmontell Date 2018-10-17 Time 14:39 Sent To  
Notes
2018-10-17 14:40:48MECHANICAL PLAN FAIL
  
 1 - 107.2.1.3 QUALITY OF BUILDING PLANS.
  
 BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8
 INCH SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER
 ACCEPTABLE MEDIUM. THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY,
 OTHER STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY
 MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE,
 CONTRAST, CLARITY, OR OTHER ITEMS
 RELATED TO RECORDS MANAGEMENT. ELECTRONIC MEDIA MUST BE
 COMPATIBLE WITH THE ARCHIVE
 REQUIREMENTS OF FLORIDA STATUTES.
  
  
 CHRIS MONTELLO
 561-805-6733

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-08-04 Cont ID  
Sent By hmoser Date 2018-08-04 Time 11:19 Rev Time 0.00
Received By hmoser Date 2018-08-04 Time 11:02 Sent To  
Notes
2018-08-04 11:19:30DENIED NO AIR CONDITIONING PLAN SUBMITTED. HM.

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-12-27 Cont ID  
Sent By cthroop Date 2018-12-27 Time 14:02 Rev Time 0.00
Received By cthroop Date 2018-12-21 Time 10:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-10-16 Cont ID  
Sent By gjohnson Date 2018-10-16 Time 12:46 Rev Time 0.00
Received By gjohnson Date 2018-10-16 Time 07:25 Sent To  
Notes
2018-10-16 14:37:152ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS: IN ORDER TO CLARIFY APPLICATION IT
 WOULD BE GOOD TO SCHEDULE A MEETING WITH THE REVIEWERS
 TO GO OVER COMMENTS AND THE SUBMITTAL PACKAGE.
  
 1. THE DRAIN CANNOT DISCHARGE INTO THE TRAP FOR THE TUB
 THIS IS DOUBLE TRAPPING A FIXTURE IT SHALL CONNECT DOWN
 STREAM OF THE TUB TRAP. PER FBC RES P3201.6
  
 2. YOUR PERMIT SUBMITTAL PACKAGE IS A LITTLE CONFUSING
 THERE SEAMS TO BE OLD PLANS AND DOCUMENTS FROM PREVIOUS
 REVIEW WHEN YOU RESUBMIT PLEASE MARK ALL OLD SHEETS AS
 VOID SO ANYBODY THAT LOOKS AT SUBMITTAL KNOWS WHICH IS
 NEW AND WHICH IS OLD ALSO SUBMIT A DETAILED SCOPE OF
 PLUMBING AND GAS WORK BEING DONE THE LETTER THAT WAS
 SUBMITTED SAID THE RENOVATION WORK ON THE FIRST FLOOR
 WAS ELIMINATED WITH ALL THE DIFFERENT PLAN SHEETS I
 JUST WANT TO BE SURE WHAT IS BEING PERMITTED. PER WPB
 AMEND TO FBC 107.1.2
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-08-30 Cont ID  
Sent By shill Date 2018-08-30 Time 13:53 Rev Time 0.00
Received By jesmith Date 2018-08-30 Time 13:53 Sent To  
Notes
2018-08-30 13:58:451ST REVIEW: FBC 2017 6TH EDITION
 DENIED
  
 GENERAL COMMENT:PLAN SHEET T-0 INDICATES APPLICABLE
 CODES ARE FBC 5TH ADDITION; APPLICABLE CODES ADOPTED BY
 WPB ARE 6TH ADDITION. PLEASE COMPLY
  
 PLUMBING REVIEW
  
 1. PLAN SHEET T-0 AND T-2 INCLUDE RERFERENCES TO
 PLUMBING. PLAN SHEET A-2 SEEM TO INDICATE SOME PLUMBING
 CHANGES. ARE THERE RELOCATED OR ADDED PLUMBING
 FIXTURES? PLEASE CLARIFY.
 PROVIDE PLUMBING RISER DIAGRAM IN ACCORDANCE WITH 2017
 FBC 107.3.5.3 (12) WPB AMEND IF CHANGES OR ADDITIONS
 ARE BEING MADE.
 NOTE ON PLAN WHICH IF ANY PLUMBING FIXTURES ARE BEING
 REPLACED, ADDED OR RELOCATED.
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711

Review Stop Z ZONING
Rev No 3 Status P Date 2019-01-18 Cont ID  
Sent By mcruz Date 2019-01-18 Time 14:01 Rev Time 0.00
Received By mcruz Date 2019-01-18 Time 13:59 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2018-10-04 Cont ID  
Sent By mcruz Date 2018-10-04 Time 11:45 Rev Time 0.00
Received By mcruz Date 2018-10-04 Time 11:35 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-07-26 Cont ID  
Sent By MC Date 2018-07-26 Time 11:50 Rev Time 0.00
Received By mcruz Date 2018-07-26 Time 11:50 Sent To PC
Notes
***NONE***