Plan Review Details - Permit 18070442
Plan Review Stops For Permit 18070442
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2018-10-29 Cont ID  
Sent By shill Date 2018-10-29 Time 08:48 Rev Time 0.00
Received By shill Date 2018-10-29 Time 08:48 Sent To  
Notes
2018-10-29 08:48:501201 S FLAGLER
  

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2018-08-27 Cont ID  
Sent By shill Date 2018-08-27 Time 10:26 Rev Time 0.00
Received By shill Date 2018-08-27 Time 10:26 Sent To  
Notes
2018-08-27 10:31:41FOR ADDRESSING, PLEASE CONTACT (PREFERABLY VIA EMAIL):
  
 MICHAEL ORIO
 GIS SUPPORT SPECIALIST
 [email protected]
 CITY OF WEST PALM BEACH
 INFORMATION TECHNOLOGY DEPARTMENT
 401 CLEMATIS STREET, WEST PALM BEACH, FLORIDA 33401
 P: 561.494.1080
  
  

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status N Date 2018-09-01 Cont ID  
Sent By shill Date 2018-09-01 Time 18:45 Rev Time 0.00
Received By shill Date 2018-09-01 Time 18:45 Sent To  
Notes
2018-09-01 18:46:19PER EMAIL FROM SYBILLE WELTER, AIPP IS NOT REQUIREC
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-10-29 Cont ID  
Sent By rgathrig Date 2018-10-29 Time 11:25 Rev Time 0.00
Received By rgathrig Date 2018-10-29 Time 11:25 Sent To  
Notes
2018-10-29 11:49:322ND REVIEW PASSED WITH PROVISOS
  
 RICHARD GATHRIGHT
 [email protected]
 561-805-6679
  
 1ST REVIEW BY SAMANTHA HILL
 9/4/2018 THAT GENERATED THE FOLLOWING COMMENTS
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SEE PLUMBING COMMENTS REGARDING ACCESSIBILITY;
 APPLICABLE FOR BUILDING REVIEW. (PLUMBING APPROVED
 COMMENT CLOSED REG)
  
 2. SEE FIRE COMMENTS REGARDING FIRE SPRINKLERS;
 APPLICABLE FOR BUILDING REVIEW. (FIRE APPROVED COMMENT
 CLOSED REG)
  
 3. SINCE THE PRODUCT APPROVALS ARE SPECIFIED ON THE
 PLAN, PLEASE PROVIDE:
 NOA 17?110602
 YKK 35H, FL 16554.1 & 16554.2
 YKK YES 50 FS, FL 14218.7
 (PRODUCT APPROVALS WERE PROVIDED COVER SHEETS PROVIDED
 BY REVIEWER COMMENT CLOSED OK REG)
  
 4. REVISE PLAN TO STATE TOTAL NUMBER OF PARKING SPACES,
 TOTAL NUMBER OF ACCESSIBLE SPACES, FBC A 208.2, 502.
 (THIS COMMENT NOT PROPERLY ADDRESSED, SPACES SHOWN ON
 ALS1.1 MUST BE RELOCATED FOR THE OFFICE USE TO MEET THE
 FLORIDA ACCESSIBILITY REQUIREMENT,
 FAIR HOUSING REQUIREMENTS MUST ALSO BE MET. PROVIDE
 TOTAL NUMBER OF PARKING SPACES PROVIDED FOR THE COVERED
 UNITS IN THE BRISTOL AND PROVIDED LOCATIONS FOR THE
 REQUIRED PARKING REG)
  
 5. CONDENSING UNIT STAND SHOWN ON S4.0; EITHER PROVIDE
 PRODUCT APPROVAL OR INDICATE THAT YOU WOULD LIKE THIS
 ITEM DEFERRED, FBC 107.
 (NOTE ADDED TO SUBMIT NOA FOR APPROVAL, ITEM WILL BE A
 PROVISO REG)
  
 6. S0.0, S6.1, THIS APPEARS TO BE LOCATED IN EXPOSURE
 D, FBC B 1609. PLEASE NOTE THE FETCH OF OVER A MILE TO
 THE SOUTH. IF SEOR DISAGREES, PLEASE SEND JUSTIFICATION
 VIA EMAIL PRIOR TO RESUBMITTING. (ITEM HAS BEEN ADDED
 COMMENT CLOSED REG)
  
 7. S0.0 HAS TEXT WHICH IS NOT LEGIBLE (REINFORCED
 MASONRY), PLEASE CORRECT. (COMMENT ON PLANS DELETED
 (RESOLVED) COMMENTCLOSED REG)
  
 8. OK (COMMENT MODIFIED IN FIRST REVIEW CLOSED REG)
  
 9. S0.1, S6.1, PAGES INCLUDE REFERENCES TO FBC 2014.
 PLEASE CHECK ALL PAGES AND UPDATE. (REFERENCES HAVE
 BEEN UPDATED COMMENT CLOSED REG)
  
 10. S0.1, ROOF PRESSURES APPEAR TOO LOW FOR A FLAT ROOF
 (?38.5, ?67.1, ?67.1). PRESSURES ARE FOR 20SF. AT THIS
 TIME I DO NOT KNOW THE FASTENING PROPOSED FOR THE
 PITCHED AND FLAT ROOFS, BUT IT APPEARS THAT PRESSURES
 FOR 10 SF ARE REQUIRED.
 (ROOF PRESSURES HAVE BEEN REVISED COMMENT CLOSED REG)
  
 11. CLARIFY PARAPET HEIGHT RELATIVE TO ROOF SURFACE.
 PARAPET IS TO BE 3? OR GREATER TO UTILIZE ZONE 2
 PRESSURES IN ZONE 3, FBC B 1609, ASCE7?10. (ROOF
 PRESSURES HAVE BEEN REVISED COMMENT CLOSED REG)
  
 12. 6?S3.2 SHOWS WOOD TRUSSES, CDX PLYWOOD. SEE FBC B
 603 (COMBUSTIBLES IN TYPE I & II BUILDINGS), REVISE
 PLAN TO SHOW COMPLIANCE (FRT OR STATE APPLICABLE
 EXCEPTION); CHECK ALL DETAILS FOR COMBUSTIBLES.
 (DETAILS 3 & 4 PG S3.2 STILL SAY CDX. THE REFERENCE ON
 THE ARCHITECTURAL SUCH AS DETAIL 4 ON A4.0.1 DOES NOT
 SAY FIRE RETARDANT LUMBER AS REQUIRED FOR A TYPE IIB AS
 STATED ON ALS1.1. THESE CORRECTIONS CAN BE A PROVISO
 REG)
  
 13. PROVIDE A SITE PLAN WHICH SHOWS COMPLIANCE WITH FBC
 B TABLES 602, 705.8 (IN PARTICULAR, THE DISTANCE FROM
 PROPOSED STRUCTURE TO THE SOUTH PROPERTY LINE).(SITE
 PLAN PROVIDE GC-001 AND SURVEY PROVIDE IN SUBMITTAL
 18100459 COMMENT CLOSED REG)
  
 14. FBC B 107.2.5, PROVIDE A PLAN WHICH SHOWS LOCATION
 OF STRUCTURE RELATIVE TO THE FLOOD ZONE LINES. THIS
 PARCEL IS AFFECTED BY BOTH THE 6? AND 7? NAVD88 FLOOD
 ZONES. ALTERNATIVELY, P
 PLEASE ACKNOWLEDGE ON THE PLANS THAT THIS IS LOCATED IN
 SFHA 7? NAVD88. (SURVEY PROVIDE IN SUBMITTAL 18100459
 THAT DEPICTS LOCATION OF BUILDING IN BOTH THE 6?AND 7?
 NAVD88 FLOOD ZONES COMMENT CLOSED REG)
  
 15. IF LOCATED IN A SFHA, FBC B 107.3.5.1.1(1), PROVIDE
 A "CONSTRUCTION DOCUMENTS" ELEVATION CERTIFICATE. (AN
 EC WAS PROVIDED WITH SURVEY PROVIDE IN SUBMITTAL
 18100459 THAT DEPICTS LOCATION OF BUILDING IN BOTH THE
 6?AND 7? NAVD88 FLOOD ZONES.
 EC SUBMITTED WAS NOT CORRECT, EC WAS UNDER CONSTRUCTION
 AND ONLY LOCATED TOP OF FOOTERS IT DID NOT KNOWLEDGE
 PROPOSED FLOOR ELEVATION.EC ALSO HAD NOTATION OF FLOOD
 VENTS. RICHARD DEAN OF DEAN SURVEYING WAS CONTACTED
 CONCERNING THE FLOOD VENTS AND NOT HAVING A PROPOSED
 EC.
 HE STATED HE USED THE GARAGE DOOR OPENINGS AS FLOOD
 OPENINGS. MR. DEAN SAID HE WOULD PROVIDE A PROPER
 PROPOSED EC AND PROVIDE AN UNDER CONSTRUCTION EC
 SHOWING FLOOR ELEVATION. THE EC DATED 10/01/18 HE SAID
 IS NOT CORRECT AND HE WILL VOID THAT DOCUMENT. R DEAN
 SAID HE WOULD HAVE THE CORRECTED EC BY 11/02/18.
 COMMENT NOT CLOSED HOWEVER IT WILL BE A PROVISO REG)
  
 16. FBC B 107.2.5, REVISE ARCHITECTURAL AND/OR
 STRUCTURAL PLANS TO INCLUDE PROPOSED ELEVATION. C5.00
 APPEARS TO PROPOSE 10.52 NGVD29. THIS APPEARS TO COMPLY
 WITH THE REQUIREMENT OF 9? NAVD88. ON A AND/OR SSHEETS,
 PLEASE SPECIFY IN NAVD88 TO BE CONSISTENT WITH THE
 FLOOD INSURANCE RATE MAPS OR SPECIFY CONVERSION. (FLOOR
 ELEVATIONS WERE ADDED AND SURVEYOR WILL PROVIDE SURVEY
 TO SUPPORT SUCH COMMENT CLOSED REG)
  
 17. FBC B 1612, IF ANY PORTION OF THE PROPOSED
 STRUCTURE IS LOCATED IN THE SPECIAL FLOOD HAZARD
 AREA,DESIGN FLOOD ELEVATION IS BFE + 2? FREEBOARD.(THE
 ENTIRE BUILDING IS AT ELEVATION 9.00 NAVD88 COMMENT
 CLOSED REG)
  
 18. ENERGY CALCS REQURIED, FBC EC C401. (ENERGY CALCS
 SUBMITTED COMMENT CLOSED REG)
  
 19. THIS PERMIT WILL BE ISSUED WITH PROVISO:
 A. PRIOR TO CONCRETE POUR, A "BUILDING UNDER
 CONSTRUCTION" ELEVATION CERTIFICATE IS REQUIRED. EC
 THAT HAS BEEN SUBMITTED NEEDS CORRECTION. CORRECT EC
 MAY BE SENT VIA EMAIL FOR PRELIMINARY REVIEW.
 AN UNDER CONSTRUCTION EC IS REQUIRED TO ESTABLISH FLOOR
 HEIGHT. PRIOR TO FINAL INSPECTION BUT AFTER ALL
 MECHANICAL EQUIPMENT HAS BEEN INSTALLED AND FINAL
 GRADES COMPLETED,
 A "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE WILL BE
 REQUIRED. THIS MAY BE SENT VIA EMAIL FOR PRELIMINARY
 REVIEW.
 B. DEFERRED SUBMITTALS REQUESTED BY ARCHITECT ?
 COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF
 RECORD ARE TO BE SUBMITTED TO THE BUILDING DIVISION,
 REVIEWED AND ISSUED PRIOR TO
 INSTALLATION. CONFIRM COMPLIANCE WITH PRESSURES
 SPECIFIED BY SEOR PRIOR TO SUBMITTAL.
 IF PRODUCT APPROVAL OFFERS OPTIONS, INDICATE OPTION
 PROPOSED, ESPECIALLY IF NOT ALL
 OPTIONS COMPLY WITH MINIMUM DESIGN PRESSURES.
 C. SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR
 THE FOLLOWING ITEMS AS APPLICABLE:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS CONTROL
 LANDSCAPING
 IRRIGATION
 ALL OTHER ITEMS OTHER THAN BMEP
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-27 Cont ID  
Sent By shill Date 2018-08-27 Time 12:22 Rev Time 0.00
Received By shill Date 2018-08-25 Time 19:33 Sent To  
Notes
2018-08-27 12:22:47****CORRECTIONS****
 REVISED 9/4/18 (REMOVED COMMENT #8)
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SEE PLUMBING COMMENTS REGARDING ACCESSIBILITY;
 APPLICABLE FOR BUILDING REVIEW.
  
 2. SEE FIRE COMMENTS REGARDING FIRE SPRINKLERS;
 APPLICABLE FOR BUILDING REVIEW.
  
 3. SINCE THE PRODUCT APPROVALS ARE SPECIFIED ON THE
 PLAN, PLEASE PROVIDE:
  
 NOA 17-8080.06
 YKK 35H, FL 16554.1 & 16554.2
 YKK YES 50 FS, FL 14218.7
  
 4. REVISE PLAN TO STATE TOTAL NUMBER OF PARKING SPACES,
 TOTAL NUMBER OF ACCESSIBLE SPACES, FBC A 208.2, 502.
  
 5. CONDENSING UNIT STAND SHOWN ON S4.0; EITHER PROVIDE
 PRODUCT APPROVAL OR INDICATE THAT YOU WOULD LIKE THIS
 ITEM DEFERRED, FBC 107.
  
 6. S0.0, S6.1, THIS APPEARS TO BE LOCATED IN EXPOSURE
 D, FBC B 1609. PLEASE NOTE THE FETCH OF OVER A MILE TO
 THE SOUTH. IF SEOR DISAGREES, PLEASE SEND JUSTIFICATION
 VIA EMAIL PRIOR TO RESUBMITTING.
  
 7. S0.0 HAS TEXT WHICH IS NOT LEGIBLE (REINFORCED
 MASONRY), PLEASE CORRECT.
  
 8. OK
  
 9. S0.1, S6.1, PAGES INCLUDE REFERENCES TO FBC 2014.
 PLEASE CHECK ALL PAGES AND UPDATE.
  
 10. S0.1, ROOF PRESSURES APPEAR TOO LOW FOR A FLAT ROOF
 (-38.5, -67.1, -67.1). PRESSURES ARE FOR 20SF. AT THIS
 TIME I DO NOT KNOW THE FASTENING PROPOSED FOR THE
 PITCHED AND FLAT ROOFS, BUT IT APPEARS THAT PRESSURES
 FOR 10 SF ARE REQUIRED.
  
 11. CLARIFY PARAPET HEIGHT RELATIVE TO ROOF SURFACE.
 PARAPET IS TO BE 3' OR GREATER TO UTILIZE ZONE 2
 PRESSURES IN ZONE 3, FBC B 1609, ASCE7-10.
  
 12. 6-S3.2 SHOWS WOOD TRUSSES, CDX PLYWOOD. SEE FBC B
 603 (COMBUSTIBLES IN TYPE I & II BUILDINGS), REVISE
 PLAN TO SHOW COMPLIANCE (FRT OR STATE APPLICABLE
 EXCEPTION); CHECK ALL DETAILS FOR COMBUSTIBLES.
  
 13. PROVIDE A SITE PLAN WHICH SHOWS COMPLIANCE WITH FBC
 B TABLES 602, 705.8 (IN PARTICULAR, THE DISTANCE FROM
 PROPOSED STRUCTURE TO THE SOUTH PROPERTY LINE).
  
 14. FBC B 107.2.5, PROVIDE A PLAN WHICH SHOWS LOCATION
 OF STRUCTURE RELATIVE TO THE FLOOD ZONE LINES. THIS
 PARCEL IS AFFECTED BY BOTH THE 6' AND 7' NAVD88 FLOOD
 ZONES. ALTERNATIVELY, PLEASE ACKNOWLEDGE ON THE PLANS
 THAT THIS IS LOCATED IN SFHA 7' NAVD88.
  
 15. IF LOCATED IN A SFHA, FBC B 107.3.5.1.1(1), PROVIDE
 A "CONSTRUCTION DOCUMENTS" ELEVATION CERTIFICATE.
  
 16. FBC B 107.2.5, REVISE ARCHITECTURAL AND/OR
 STRUCTURAL PLANS TO INCLUDE PROPOSED ELEVATION. C5.00
 APPEARS TO PROPOSE 10.52 NGVD29. THIS APPEARS TO COMPLY
 WITH THE REQUIREMENT OF 9' NAVD88. ON A AND/OR S
 SHEETS, PLEASE SPECIFY IN NAVD88 TO BE CONSISTENT WITH
 THE FLOOD INSURANCE RATE MAPS OR SPECIFY CONVERSION.
  
 17. FBC B 1612, IF ANY PORTION OF THE PROPOSED
 STRUCTURE IS LOCATED IN THE SPECIAL FLOOD HAZARD AREA,
 DESIGN FLOOD ELEVATION IS BFE + 2' FREEBOARD.
  
 18. ENERGY CALCS REQURIED, FBC EC C401.
  
 19. THIS PERMIT WILL BE ISSUED WITH PROVISO:
  
 A. PRIOR TO CONCRETE POUR, A "BUILDING UNDER
 CONSTRUCTION" ELEVATION CERTIFICATE WILL BE REQUIRED.
 THIS MAY BE SENT VIA EMAIL FOR PRELIMINARY REVIEW.
 PRIOR TO FINAL INSPECTION BUT AFTER ALL MECHANICAL
 EQUIPMENT HAS BEEN INSTALLED AND FINAL GRADES
 COMPLETED, A "FINISHED CONSTRUCTION" ELEVATION
 CERTIFICATE WILL BE REQUIRED. THIS MAY BE SENT VIA
 EMAIL FOR PRELIMINARY REVIEW.
  
 B. DEFERRED SUBMITTALS REQUESTED BY ARCHITECT -
 COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING
 DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION.
 CONFIRM COMPLIANCE WITH PRESSURES SPECIFIED BY SEOR
 PRIOR TO SUBMITTAL. IF PRODUCT APPROVAL OFFERS OPTIONS,
 INDICATE OPTION PROPOSED, ESPECIALLY IF NOT ALL OPTIONS
 COMPLY WITH MINIMUM DESIGN PRESSURES.
  
 C. SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR THE FOLLOWING ITEMS AS APPLICABLE:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 ALL OTHER ITEMS OTHER THAN BMEP
  
 D. AIPP COMPLIANCE MAY BE REQUIRED; VERIFICATION
 REQUIRED PRIOR TO C.O.
  
 *******************************
 INTERNAL USE ONLY:
 USC-404 321 - NEW: PARKING GARAGE
 SQUARE FEET - 19,924
  
 CONSTRUCTION TYPE: IIB
  
 FLOORS: 1
 BEDROOMS:
 ROOMS:
 SQ FT LIVABLE: 19924
 SQ FT FOOTPRINT: 19924
 SQ FT ROOF: 19924
  
 SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF
 KNOWN):
 SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN):
 XX.XX
 SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN:
 XX.XX
 OCC LOAD:
 PROP USE: APARTMENT
 SPRINKLER SYS? Y
 SPRK REQ'D? Y
 BATHRMS:
  
 BLDG CODE: FL 2017
 OCC CLASS: 6TH ED S-1
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-10-10 Cont ID  
Sent By jleahy Date 2018-10-10 Time 12:54 Rev Time 0.00
Received By jleahy Date 2018-10-10 Time 12:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-13 Cont ID  
Sent By jleahy Date 2018-08-13 Time 17:03 Rev Time 0.00
Received By jleahy Date 2018-08-13 Time 16:11 Sent To  
Notes
2018-08-13 16:59:20FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PANEL "A" IS FEEDING COMMUNITY CENTER, PLEASE SHOW
 LOCATION.
  
 2) AIC RATINGS FOR THE SERVICE IS REQUIRED SHOW
 CALCULATIONS
  
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE
 AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE SERVICE TO
 CONFIRM THE STATED AIC RATING OF THE SERVICE EQUIPMENT
 AND DOWNSTREAM
 PANELS IS ADEQUATE. NEC 110.9, 110.10
  
 3) MAIN IS 1200A NEEDS TO COMPLY WITH 240.87
  
 240.87 ARC ENERGY REDUCTION
 WHERE THE HIGHEST CONTINUOUS CURRENT TRIP SETTING FOR
 WHICH THE ACTUAL OVERCURRENT DEVICE INSTALLED IN A
 CIRCUIT BREAKER IS RATED
 OR CAN BE ADJUSTED IS 1200 A OR HIGHER, 240.87(A) AND
 (B) SHALL APPLY.
  
 (A) DOCUMENTATION. DOCUMENTATION SHALL BE AVAILABLE TO
 THOSE AUTHORIZED TO DESIGN, INSTA LL, OPERATE, OR
 INSPECT THE INSTALLATION
 AS TO THE LOCATION OF THE CIRCUIT BREAKER(S)
 .
 (B) METHOD TO REDUCE CLEARING TIME. ONE OF THE
 FOLLOWING OR APPROVED EQUIVALENT MEANS SH ALL BE
 PROVIDED:
 (1) ZONE-SELECTIVE INTERLOCKING
 (2) DIFFERENTIAL RELAYING
 (3) ENERGY-REDUCING MAINTENANCE SWITCHING WITH LOCAL
 STATUS INDICATOR
 (4) ENERGY-REDUCING ACTIVE ARC FLASH MITIGATION SYSTEM
 (5) AN APPROVED EQUIVALENT MEANS

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2018-10-24 Cont ID  
Sent By rrossano Date 2018-10-24 Time   Rev Time 0.00
Received By rrossano Date 2018-10-24 Time   Sent To I
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2018-08-20 Cont ID  
Sent By Mgonzale Date 2018-08-20 Time   Rev Time 1.00
Received By mgonzale Date 2018-08-20 Time   Sent To I
Notes
2018-08-20 10:54:01APPLICANT MUST POST A PERFORMANCE BOND FOR ENGINEERING
 SERVICES EROSION CONTROL & LAND STABILIZATION BOND
 (ORDINANCE 4060-07)
  
 BOND SHALL BE INCLUSIVE OF 110% OF ENGINEER'S OPINION
 OF COST TO RESTORE SITE TO STABILIZED SODDED GRADE,
 GOOD FOR A PERIOD OF 1 YEAR.
  
 TO: CITY OF WEST PALM BEACH, A MUNICIPAL CORPORATION OF
 THE STATE OF FLORIDA, HAVING AN ADDRESS OF 401 CLEMATIS
 STREET, WEST PALM BEACH, FLORIDA, 33402
  
 UPON SUCCESFULLY PASSING 1ST VERTICAL INSPECTION THE
 CONTRACTOR MAY REQUEST THE BOND TO BE TERMINATED.
  
 FOR MORE INFORMATION YOU MAY USE THE PERFORMANCE BOND
 FORM ON OUR WEB PAGE OR SUBMIT EQUAL INTRUMENT DIRECTLY
 TO:
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT \ ENGINEERING SERVICES
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 818-1322
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-09-27 Cont ID  
Sent By pleduc Date 2018-09-27 Time   Rev Time 0.00
Received By pleduc Date 2018-09-26 Time 15:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-07-18 Cont ID  
Sent By pleduc Date 2018-07-18 Time   Rev Time 0.00
Received By pleduc Date 2018-07-13 Time 16:03 Sent To  
Notes
2018-07-17 17:17:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET ALS 1 - THERE IS NO INDICATIONS OF REVIEW
 AND/OR COMPLIANCE WITH ANY FIRE CODE.
  
 PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE AN
 APPLICABLE NOTE TO INCLUDE THE 6TH EDITION OF THE
 FLORIDA FIRE PREVENTION CODE AND NFPA 88A, STANDARD FOR
 PARKING STRUCTURES, 2015 EDITION.
  
  
  
 2) SHEET ALS 1 - UNDER THE REQUIRED MEANS OF EGRESS
 THERE IS TWO BUSINESS INDICATORS SHOWING NUMBER OF
 EGRESSES. ONE INDICATES 2 EXITS HOWEVER THE DRAWING
 SHOWS ONE EXIT.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
  
 3) SHEET ALS 1 - THERE IS AN INDICATION OF THIS STORAGE
 OCCUPANCY AS LOW HAZARD. THIS IS A PARKING GARAGE AND
 IS CLASSIFIED AND AN ORDINARY HAZARD.
  
 PER NFPA 101, CHAPTER 42, STORAGE OCCUPANCIES
  
 42.8.1.5 CLASSIFICATION OF HAZARD OF CONTENTS. PARKING
 STRUCTURES USED ONLY FOR THE STORAGE OF VEHICLES SHALL
 BE CLASSIFIED
 AS ORDINARY HAZARD IN ACCORDANCE WITH SECTION 6.2.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES.
  
  
  
 4) THERE ARE INDICATIONS THAT THIS IS A FULLY SPRINKLED
 BUILDING. THERE ARE NO INDICATIONS OR DOCUMENTS IN
 COMPLAINCE WITH THE REQUIREMENTS FAC 61 G.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 61G15-32.003 COMMON REQUIREMENTS TO ALL FIRE PROTECTION
 ENGINEERING
 DOCUMENTS.
 (1) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS
 SHALL PROVIDE THE ENGINEERING REQUIREMENTS TO BE USED
 IN THE PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT
 DOCUMENTS AND TO INDICATE THE NATURE AND SCOPE OF THE
 WORK, AND TO DESCRIBE, DETAIL, DIMENSION, LABEL AND
 DEFINE THE FIRE PROTECTION COMPONENTS, SYSTEM(S),
 MATERIALS, ASSEMBLIES, EQUIPMENT AND ITS STRUCTURAL AND
 UTILITY SUPPORT SYSTEM(S), INSOFAR AS THEY INVOLVE THE
 SAFEGUARDING OF LIFE, HEALTH OR PROPERTY.
 (2) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS
 SHALL SPECIFY THE APPLICABLE REQUIREMENTS FOR THE
 ACCEPTANCE TESTING OF THE FIRE PROTECTION SYSTEM AND
 COMPONENTS, WHICH SHALL BE BASED UPON APPLICABLE CODES
 AND STANDARDS, WHERE AVAILABLE.
 (3) THE OCCUPANCY OF THE AREA OR DESCRIPTION OF A
 SPECIFIC HAZARD BEING PROTECTED BY THE FIRE PROTECTION
 SYSTEM(S) SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENTS.
 (4) THE APPLICABLE CODE AND STANDARD TO BE USED IN THE
 PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT
 DOCUMENTS SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENTS. WHEN CODES AND STANDARDS ARE NOT
 AVAILABLE OR APPLICABLE, AND SAID LAYOUT DOCUMENTS ARE
 TO BE BASED ON ENGINEERING JUDGMENT, ANY REASONS AND
 ASSUMPTIONS MADE TO DEVELOP THE FIRE PROTECTION CONCEPT
 SHALL BE IDENTIFIED ON THE FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENTS.
 (5) STRUCTURAL SUPPORT AND STRUCTURAL OPENINGS REQUIRED
 BY THE FIRE PROTECTION SYSTEM SHALL BE SHOWN ON THE
 FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS AND SHALL
 BE REFERENCED ON STRUCTURAL ENGINEERING DOCUMENTS.
 (6) WHEN LAYOUT DOCUMENTS CONTAIN MATERIAL DEVIATION
 FROM THE ENGINEER OF RECORD'S FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENT, SUCH LAYOUT DOCUMENTS ARE NOT
 COMPLIANT UNLESS THEY ARE ACCOMPANIED BY REVISED
 ENGINEERING DOCUMENTS MADE AND SEALED BY THE ENGINEER
 OF RECORD FOR THE FIRE PROTECTION SYSTEM.
 (7) REQUIREMENTS FOR ACTIVATION CONTROL SYSTEMS,
 SEQUENCE, OPERATING PARAMETERS, INTERLOCKS, SAFETY
 RELATED DEVICES, INDICATORS AND ALARMS, SHALL BE SHOWN
 ON THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS,
 UNLESS SHOWN ON OTHER RELATED DOCUMENTS.
 (8) ANY INFORMATION DEEMED APPROPRIATE BY THE ENGINEER
 OF RECORD TO ASSIST THE AUTHORITY HAVING JURISDICTION
 IN UNDERSTANDING THE OWNER?S INTENDED USE AND PROPOSED
 PROTECTION OF THE BUILDING OR FACILITY AND TO PROVIDE
 SUFFICIENT DIRECTION TO THE INSTALLATION CONTRACTOR OR
 OTHER INTERESTED PARTIES REGARDING THE LAYOUT OF THE
 SYSTEM(S), SHALL BE INCLUDED IN THE FIRE PROTECTION
 SYSTEM ENGINEERING DOCUMENTS.
 SPECIFIC AUTHORITY 471.008, 471.033(2), FS
 LAW IMPLEMENTED 471.005(7), 471.033(2), FS
 HISTORY?NEW 5-19-93, FORMERLY 21H-32.003, AMENDED
 4-2-2000, 6-26-01
  
 61G15-32.004 DESIGN OF WATER BASED FIRE PROTECTION
 SYSTEMS.
 (1) WATER BASED FIRE PROTECTION SYSTEMS INCLUDE, BUT
 ARE NOT LIMITED TO, AUTOMATIC SPRINKLER SYSTEMS OF WET,
 DRY, FINE WATER SPRAY (MIST), MANUAL, AND DELUGE VALVE
 CONTROLLED TYPES, PUMPING SYSTEMS, STANDPIPES, FIRE
 WATER MAINS AND DEDICATED FIRE PROTECTION WATER
 SOURCES.
 (2) TO ENSURE MINIMUM DESIGN QUALITY IN FIRE PROTECTION
 SYSTEM ENGINEERING DOCUMENTS, SAID DOCUMENTS SHALL
 INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION WHEN
 APPLICABLE:
 (A) THE POINT OF SERVICE FOR THE FIRE PROTECTION WATER
 SUPPLY AS DEFINED BY 633.021(18) F.S.
 (B) APPLICABLE NFPA STANDARD TO BE APPLIED, OR IN THE
 CASE WHERE NO SUCH STANDARD EXISTS, THE ENGINEERING
 STUDY, JUDGMENTS, AND/OR PERFORMANCE BASED ANALYSIS AND
 CONCLUSIONS.
 (C) CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA.
 (D) DESIGN APPROACH, WHICH INCLUDES SYSTEM TYPE,
 DENSITIES, DEVICE TEMPERATURE RATING, AND SPACING FOR
 EACH SEPARATE 42 HAZARD OCCUPANCY.
 (E) CHARACTERISTICS OF WATER SUPPLY TO BE USED, SUCH AS
 MAIN SIZE AND LOCATION, WHETHER IT IS DEAD-END OR
 CIRCULATING; AND IF DEAD-END, THE DISTANCE TO THE
 NEAREST CIRCULATING MAIN, AS WELL AS ITS MINIMUM
 DURATION AND RELIABILITY FOR THE MOST HYDRAULICALLY
 DEMANDING DESIGN AREA.
 (F) WHEN PRIVATE OR PUBLIC WATER SUPPLIES ARE USED, THE
 FLOW TEST DATA, INCLUDING DATE AND TIME OF TEST, WHO
 CONDUCTED TEST OR SUPPLIED INFORMATION, TEST ELEVATION,
 STATIC GAUGE PRESSURE AT NO FLOW, FLOW RATE WITH
 RESIDUAL GAUGE PRESSURE, HYDRANT BUTT COEFFICIENT, AND
 LOCATION OF TEST IN RELATION TO THE HYDRAULIC POINT OF
 SERVICE.
 (G) VALVING AND ALARM REQUIREMENTS TO MINIMIZE
 POTENTIAL FOR IMPAIRMENTS AND UNRECOGNIZED FLOW OF
 WATER.
 (H) MICROBIAL INDUCED CORROSION (MIC). THE ENGINEER OF
 RECORD SHALL MAKE REASONABLE EFFORTS TO IDENTIFY WATER
 SUPPLIES THAT COULD LEAD TO MICROBIAL INDUCED CORROSION
 (MIC). SUCH EFFORTS MAY CONSIST OF DISCUSSIONS WITH THE
 LOCAL WATER PURVEYOR AND/OR FIRE OFFICIAL, FAMILIARITY
 WITH CONDITIONS IN THE LOCAL AREA, OR LABORATORY
 TESTING OF WATER SUPPLIES. WHEN CONDITIONS ARE FOUND
 THAT MAY RESULT IN MIC CONTAMINATION OF THE FIRE
 PROTECTION PIPING, THE ENGINEER SHALL DESIGN CORRECTIVE
 MEASURES.
 (I) BACKFLOW PREVENTION AND METERING SPECIFICATIONS AND
 DETAILS TO MEET LOCAL WATER PURVEYOR REQUIREMENTS
 INCLUDING MAXIMUM ALLOWABLE PRESSURE DROP.
 (J) QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL YARD
 AND INTERIOR FIRE PROTECTION COMPONENTS.
 (3) CONTRACTOR SUBMITTALS WHICH DEVIATE FROM THE ABOVE
 MINIMUM DESIGN PARAMETERS SHALL BE CONSIDERED MATERIAL
 DEVIATIONS AND REQUIRE SUPPLEMENTAL ENGINEERING
 APPROVAL AND DOCUMENTATION.
 (4) IN THE EVENT THE ENGINEER OF RECORD PROVIDES MORE
 INFORMATION AND DIRECTION THAN IS ESTABLISHED ABOVE, HE
 OR SHE SHALL BE HELD RESPONSIBLE FOR THE TECHNICAL
 ACCURACY OF THE WORK IN ACCORDANCE WITH APPLICABLE
 CODES, STANDARDS, AND SOUND ENGINEERING PRINCIPLES.
 SPECIFIC AUTHORITY 471.008, 471.033(2), FS
 LAW IMPLEMENTED 471.005(7), 471.033(2), FS
 HISTORY?NEW 5-19-93, FORMERLY 21H-32.004, AMENDED
 4-2-2000, 6-26-01, 7-12-05
  
  
 PLEASE REVIEW AND PROVIDE THE REQUIRED DOCUMENTS WITH
 THIS MASTER PERMIT.
  
  
  
 5) SHEET E01 - THERE ARE NO INDICATIONS OF A MONITORED
 FIRE SPRINKLER SYSTEM. THE CODE REQUIRES THAT THE FIRE
 SPRINKLER SYSTEM BE MONITORED.
  
 PER NFPA 101, CHAPTER 9, FIRE PROTECTION SYSTEMS
  
  
 9.6 FIRE DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 9.6.1* GENERAL.
 9.6.1.1 THE PROVISIONS OF SECTION 9.6 SHALL APPLY ONLY
 WHERE
 SPECIFICALLY REQUIRED BY ANOTHER SECTION OF THIS CODE
 OR WHERE
 SUPERVISION OF A NEW FIRE SPRINKLER SYSTEM OR NEW FIRE
 ALARM
 SYSTEM IS REQUIRED BY THE FLORIDA BUILDING CODE.
  
 2017 FLORIDA BUILDING CODE:
  
 901.6 SUPERVISORY SERVICE.
  
 WHERE REQUIRED, FIRE PROTECTION SYSTEMS SHALL BE
 MONITORED BY AN APPROVED SUPERVISING STATION IN
 ACCORDANCE WITH NFPA 72.
  
 901.6.1 AUTOMATIC SPRINKLER SYSTEMS.
  
 AUTOMATIC SPRINKLER SYSTEMS SHALL BE MONITORED BY AN
 APPROVED SUPERVISING STATION.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT
 AND COMPLIANCE
  
  
  
 6) SHEET MO 1 - THERE ARE NO INDICATIONS OF CODE
 REFERENCE TO NFPA 88A, PARKING STRUCTURES REGARDING
 REQUIRED VENTILATION
  
 CHAPTER 6 BUILDING SERVICE AND FIRE PROTECTION
  
 6.3 VENTILATION.
 6.3.1* ALL ENCLOSED PARKING STRUCTURES SHALL BE
 VENTILATED BY
 A MECHANICAL SYSTEM CAPABLE OF PROVIDING A MINIMUM OF
 300 L/MIN PER M2 OF FLOOR AREA (1 FT3/MIN PER FT2 OF
 FLOOR
 AREA) DURING HOURS OF NORMAL OPERATION.
  
 6.3.3 MECHANICAL VENTILATING SYSTEMS SHALL BE INSTALLED
 IN ACCORDANCE
 WITH NFPA 90A. DUCTWORK SHALL BE CONSTRUCTED OF
 NONCOMBUSTIBLE MATERIAL.
  
 PLEASE REVIEW, CORRECT AND PROVIDE SPECIFIC DETAIL OR
 JUSTIFY.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-10-29 Cont ID  
Sent By rgathrig Date 2018-10-29 Time 12:28 Rev Time 0.00
Received By rgathrig Date 2018-10-29 Time 12:28 Sent To  
Notes
2018-10-29 12:29:14REVIEW COMPLETE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-29 Cont ID  
Sent By lmarchan Date 2018-10-29 Time 12:34 Rev Time 0.00
Received By lmarchan Date 2018-09-25 Time 10:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-27 Cont ID  
Sent By shill Date 2018-08-27 Time 12:23 Rev Time 0.00
Received By shill Date 2018-07-11 Time 17:11 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2018-08-24 Cont ID  
Sent By lmarchan Date 2018-08-24 Time 08:20 Rev Time 0.00
Received By lmarchan Date 2018-08-24 Time 08:20 Sent To  
Notes
2018-10-29 13:08:13MU-18-029910
2018-08-24 08:20:40IMPACT STAMP ON THE SURVEY

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-10-23 Cont ID  
Sent By ccole Date 2018-10-23 Time 14:37 Rev Time 0.00
Received By ccole Date 2018-10-23 Time 14:37 Sent To  
Notes
2018-10-23 16:49:37MECHANICAL PROVISO
  
 SUBMIT THE MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE HONEYWELL CO AND NO2
 SENSORS, AND THE NOA'S FOR THE LOUVERS AND THE
 CONDENSER STAND PRIOR TO FIRST MECHANICAL INSPECTION.
  
 ALL SUBMITTALS SHALL BEAR THE SHOP DRAWING STAMP OF
 APPROVAL BY THE ENGINEER OF RECORD.
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-08-15 Cont ID  
Sent By ccole Date 2018-08-15 Time 08:47 Rev Time 0.00
Received By ccole Date 2018-08-15 Time 08:47 Sent To  
Notes
2018-08-15 09:16:311ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18070442
 8/15/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEM- SECTION C403.2.1 FBC-17 ENERGY CONSERVATION.
 .
  
 2) ENERGY EFFICIENCY COMPLIANCE IS REQUIRED FOR THE
 CONDITIONED OFFICE PORTION OF THE NEW PARKING GARAGE
 BUILDING. PLEASE SEE SECTIONS C101.5 & C401.1 FBC EC
 AND SUBMIT A COMPLIANCE REPORT.
  
 3) M6.1: PLEASE PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR THE PARKING GARAGE IN COMPLIANCE WITH
 SECTION 404.2 FBC M.
  
 404.2 MINIMUM VENTILATION. AUTOMATIC OPERATION OF THE
 SYSTEM SHALL NOT REDUCE THE VENTILATION AIRFLOW RATE
 BELOW 0.05 CFM PER SQUARE FOOT (0.00025 M3/S ? M2) OF
 THE FLOOR AREA AND THE SYSTEM SHALL BE CAPABLE OF
 PRODUCING A VENTILATION AIRFLOW RATE OF 0.75 CFM PER
 SQUARE FOOT (0.0038 M3/S ? M2) OF FLOOR AREA.
  
 4) SITE SPECIFIC WIND LOAD ENGINEERING AND FL. PRODUCT
 APPROVALS AND/OR MIAMI-DADE NOA'S ARE REQUIRED FOR
 INSTALLATION OF THE ROOF TOP EXHAUST FANS, CONDENSER
 UNIT, AND THE GARAGE AIR INTAKE LOUVERS - SECTION
 301.15 FBC M, AND RULE 9N-3 FAC.
  
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE CO AND
 NO2 SENSORS- SECTION 304.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status P Date 2018-10-29 Cont ID  
Sent By rgathrig Date 2018-10-29 Time 10:12 Rev Time 0.00
Received By rgathrig Date 2018-10-29 Time 10:12 Sent To  
Notes
2018-10-29 10:15:12(AN EC WAS PROVIDED WITH SURVEY PROVIDE IN SUBMITTAL
 18100459 THAT DEPICTS LOCATION OF BUILDING IN BOTH THE
 6?AND 7? NAVD88 FLOOD ZONES. EC SUBMITTED WAS NOT
 CORRECT, EC WAS UNDER CONSTRUCTION AND ONLY LOCATED TOP
 OF FOOTERS IT DID NOT KNOWLEDGE PROPOSED FLOOR
 ELEVATION.EC ALSO HAD NOTATION OF FLOOD VENTS. RICHARD
 DEAN OF DEAN SURVEYING WAS CONTACTED CONCERNING THE
 FLOOD VENTS AND NOT HAVING A PROPOSED EC. HE STATED HE
 USED THE GARAGE DOOR OPENINGS AS FLOOD OPENINGS. MR.
 DEAN SAID HE WOULD PROVIDE A PROPER PROPOSED EC AND
 PROVIDE AN UNDER CONSTRUCTION EC SHOWING FLOOR
 ELEVATION. THE EC DATED 10/01/18 HE SAID IS NOT CORRECT
 AND HE WILL VOID THAT DOCUMENT. R DEAN SAID HE WOULD
 HAVE THE CORRECTED EC BY 11/02/18 COMMENT NOT CLOSED.
 HOWEVER IT WILL BE A PROVISO REG)

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2018-08-27 Cont ID  
Sent By shill Date 2018-08-27 Time 12:05 Rev Time 0.00
Received By shill Date 2018-08-27 Time 12:05 Sent To  
Notes
2018-08-27 12:05:35SEE BUILDING REVIEW
 THIS APPEARS TO BE LOCATED IN A SPECIAL FLOOD HAZARD
 AREA
 PROPOSED ELEVATION APPEARS TO COMPLY WITH 7'BFE + 2'
 FREEBOARD
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-10-24 Cont ID  
Sent By tklarge Date 2018-10-24 Time 11:58 Rev Time 0.00
Received By tklarge Date 2018-10-24 Time 11:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-07-31 Cont ID  
Sent By tklarge Date 2018-07-31 Time 12:38 Rev Time 0.00
Received By tklarge Date 2018-07-31 Time 10:52 Sent To  
Notes
2018-07-31 12:38:341) SUBMIT DOCUMENTATION AS TO HOW THE STORM DRAINAGE
 WAS SIZED. THE SYSTEM SHALL BE SIZED IN ACCORDANCE WITH
 THE 2017 FBC-PLUMBING SECS.1105.2, 1106.1, 1106.2,
 1106.3.
 2) SHT. A8.0.1 - DETAIL #1 - THE WATER CLOSET SHALL BE
 LOCATED IN ACCORDANCE WITH THE 2017 FBC- ACCESSIBILITY
 SEC.604.2.
 3) THE REAR GRAB BAR SHALL BE LOCATED IN ACCORDANCE
 WITH 2017 FBC- ACCESS. SEC.604.5.2.
 4) SHOW THE CLEAR INSIDE LENGTH AND WIDTH DIMENSIONS OF
 THE TOILET ROOM ON SHT. A8.0.1. WPB AMEND. TO FBC SEC.
 107.2.1.
 5) SHOW THE REQUIRED CLEAR FLOOR SPACE FOR THE WATER
 CLOSET AND THE LAVATORY. COMPLY WITH 2017 FBC-ACCESS.
 SECS. 604.3, 606.2.
 6) SHOW THE REQUIRED KNEE AND TOE CLEARANCES FFOR THE
 LAVATORY PER THE 2017 FBC-ACCESS. SEC. 306.
 7) SHT. A8.0.1 - THE LOCATION OF THE MIRROR SHALL
 COMPLY WITH 2017 FBC-SEC.603.3.
 8) SHOW THE LOCATION OF THE BABAY CHANGING STATION ON
 THE FLOOR PLAN.
 9) THE DOOR FOR THE TOILET ROOM APPEARS TO SWING INTO
 THE CLEAR FLOOR SPACE FOR THE LAVATORY. COMPLY WITH
 2017 FBC-ACCESS. SEC.603.2.3.
 10) SHT. P0.1 - THE ISOMETRIC OF THE ROOF DRAINAGE
 SYSTEM DOES NOT CORRELATE WITH THE PLAN VIEW ON SHT.
 P2.2. CLARIFY.
 11) A BACKFLOW PREVENTION DEVICE IS REQUIRED ON THE
 DOMESTIC WATER AND THE IRRIGATION SYSTEM FOR THIS
 STRUCTURE PER THE CITY OF WPB UTILITIES DEPT. CROSS
 CONNECTION CONTROL MANUAL.
 12) A SEPARATE PLUMBING PERMIT WILL BE REQUIRED FOR THE
 BACKFLOW DEVICES.
 13) SUBMIT A DETAIL FOR THE TERMINATION OF THE
 CONDENSATE DRAIN. THE PLAN STATES THEY DISCHARGE TO A
 GREEN AREA.WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2018-10-29 Cont ID  
Sent By shill Date 2018-10-29 Time 13:04 Rev Time 0.00
Received By shill Date 2018-10-29 Time 13:02 Sent To  
Notes
2018-10-24 12:02:06SIGNATURE ON PLUMBING SHEETS OK. T.LARGE

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-08-25 Cont ID  
Sent By shill Date 2018-08-25 Time 19:33 Rev Time 0.00
Received By shill Date 2018-08-25 Time 19:33 Sent To  
Notes
2018-08-25 19:33:28ALL DIGITAL SIGNATURES (PLANS)
  
 9/14/18 - PAPER ORIGINAL SOILS REPORT SUBMITTED UNDER
 18081379 FOUNDATION PERMIT (ISSUED)
  
 NEW SHEETS SUBMITTED NEXT REVIEW CYCLE REQUIRE REVIEW
  
2018-08-15 09:17:011ST REVIEW MECH SHEETS OK- CCOLE

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2018-09-22 Cont ID  
Sent By shill Date 2018-09-22 Time 11:44 Rev Time 0.00
Received By shill Date 2018-09-22 Time 11:44 Sent To  
Notes
2018-09-22 11:44:24AGREEMENT SUBMITTED UNDER SUBMITTAL #18090636
 THRESHOLD INSPECTION CONSULTING ENGINEERS, LLC (TICE)
 J.F. DESNOYERS, PE
 JENNINGS L. HILL, BN 3142
 DAVID ANTOINE, BN 7367
 BURTON SILVER, BN 2171
 AUTOBUILDERS, INC.
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2018-08-27 Cont ID  
Sent By shill Date 2018-08-27 Time 10:33 Rev Time 0.00
Received By shill Date 2018-08-27 Time 09:22 Sent To  
Notes
2018-08-27 09:23:44**RESIDENT INSPECTOR REQUIRED**
 TILT WALL, WELDS & BOLTS
  
 RESIDENT INSPECTOR PACKAGE REQUIRED
 1. RESIDENT INSPECTOR AGREEMENT SIGNED BY ALL PARTIES
 (SENT VIA EMAIL TO JASON KRAUS)
 2. COPIES OF LICENSES FOR ENGINEER, INSPECTORS
 3. RESUMES FOR ENGINEER, INSPECTORS
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-10-11 Cont ID  
Sent By jroach Date 2018-10-11 Time 16:37 Rev Time 0.00
Received By jroach Date 2018-10-11 Time 16:37 Sent To  
Notes
2018-10-11 16:37:48REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. LANDSCAPING SHALL BE SUBMITTED AND REVIEWED AS A
 SEPARATE PERMIT APPLICATION.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-08-20 Cont ID  
Sent By jroach Date 2018-08-20 Time 14:14 Rev Time 0.00
Received By jroach Date 2018-08-20 Time 14:14 Sent To  
Notes
2018-08-20 14:15:31ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 08.20.2018
 PERMIT NO.: 18070442
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. A SITE PLAN SHALL BE PROVIDED WHICH INCLUDES THE
 FOLLOWING:
  
  ? DATE, NORTH ARROW, AND A GRAPHIC SCALE.
  
  ? VICINITY MAP SHOWING THE PROPERTY IN RELATION TO THE
 SURROUNDING AREA.
  
  ? LOCATION OF THE PROPERTY LINE, RIGHT-OF-WAY,
 PROPOSED/EXISTING EASEMENTS, WATER COURSES AND OTHER
 ESSENTIAL FEATURES.
  
  ? STREETS, DRIVEWAYS, INTERSECTIONS, CURBS CUTS AND
 TURNING LANES ADJACENT TO OR ACROSS FROM THE SUBJECT
 PROPERTY.
  
  ? THE OUTLINES OF ALL BUILDINGS SHOWING THEIR PROPOSED
 USES, SETBACKS, DIMENSIONS, FLOOR AREA, NUMBER OF
 STORIES, HEIGHT AND POINTS OF ACCESS.
  
  ? LOCATION AND DIMENSIONS OF ALL PERIMETER TREATMENT
 (SIDEWALKS, FENCES, WALLS, OR BERMS).
  
  ? LOCATION, HEIGHT AND SIZE OF ALL FREESTANDING SIGNS
 AND OTHER ACCESSORY STRUCTURES.
  
  ? MEANS OF VEHICULAR AND PEDESTRIAN ACCESS TO AND FROM
 THE SITE.
  
  ? LAYOUT AND LOCATION OF ALL OFF-STREET PARKING,
 LOADING AND OTHER VEHICULAR USE AREAS, INCLUDING WHERE
 APPLICABLE, THE DISTANCE FROM THE PRINCIPLE USES.
  
  ? LOCATION OF ALL DISABLED SPACES, RAMPS AND SIGNS.
  
  ? LOCATION AND SCREENING OF ALL GARBAGE RECEPTACLES.
  
  ? STANDARD CITY DETAILS OF PARKING (SMALL CAR,
 HANDICAP SPACE, STANDARD SPACE), HANDICAP RAMPS,
 DRIVEWAYS, DUMPSTERS AND SIGNS.
  
  ? SUPPLY A DATA TABLE IN THE FOLLOWING FORMAT:
  
  O EXISTING/PROPOSED LAND USE AND ZONING.
  O TOTAL ACRES OF THE PROJECT.
  O TOTAL GROSS BUILDING SQUARE FOOTAGE.
  O PERCENT OF OPEN SPACE, LANDSCAPING, BUILDING
 COVERAGE & IMPERMEABLE SURFACE.
  O ACRES AND PERCENT OF WATER BODIES.
  O DENSITY AND NUMBER OF DWELLING UNITS (RESIDENTIAL).
  O PARKING COMPUTATIONS (PARKING REQUIRED, PROVIDED,
 ETC.)
  O FLOOR AREA RATIO (FAR).
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  