| 2018-08-06 08:13:18 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| | LOADS. NEC 220. MATH FOR LOAD CALCULATION IS INCORRECT. |
| | 208V, 3 PHASE LOAD IS DIVIDED BY 360 NOT 415. CORRECT |
| | MATH PUTS LOAD AT 138AMP NOT 84. PROVIDE PROPER |
| | ITEMIZED LOAD CALC SHOWING ALL LOADS. |
| | |
| | 2. PROVIDE ACCURATE PANEL SCHEDULE. PANEL SCHEDULE SAYS |
| | ITS A SINGLE PHASE PANEL. FBC 107.2.1 PROVIDE PANEL |
| | SCHEDULE INDICATING ANY NEW OR ALTERED CIRCUITS, THE |
| | WIRE AND BREAKER SIZE FOR THESE CIRCUITS, AND AFCI OR |
| | GFCI PROTECTION WHERE APPLICABLE TO COMPLY WITH CODE. |
| | NEC 210.8, 210.12, 215.5, 408.4; WPB FBC 107.3.5; FBC |
| | RE E3706.2, E3902 |
| | |
| | 3. PROVIDE CLEAR AND PROFESSIONALLY DRAWN PLAN. THE |
| | SUBMITTED FLOOR PLAN IS UNACCEPTABLE. PLEASE REVIEW THE |
| | FOLLOWING SECTIONS FROM THE WEST PALM BEACH AMENDMENTS |
| | TO THE FBC: |
| | |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS |
| | SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING |
| | OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, |
| | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| | SECTION 107.3.5). |
| | |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WPB |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |