Plan Review Details - Permit 18070421
Plan Review Stops For Permit 18070421
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-11-02 Cont ID  
Sent By shill Date 2018-11-02 Time 12:08 Rev Time 0.00
Received By shill Date 2018-11-02 Time 12:08 Sent To  
Notes
2018-11-02 12:09:12DIGITALLY SIGNED PAGES RECEIVED VIA EMAIL
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-11-01 Cont ID  
Sent By shill Date 2018-11-01 Time 16:45 Rev Time 0.00
Received By shill Date 2018-11-01 Time 16:45 Sent To  
Notes
2018-11-01 16:49:01****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. TWO PAGES (A2.1, A3.1) ARE NOT SEALED AND DATED IN
 ACCORDANCE WITH FLORIDA STATUTE 481. IT APPEARS THAT
 SOMEONE SIGNED THE PAGE. BUT NEGLECTED TO SEAL AND DATE
 IT.
  
 DOES THE ARCHITECT HAVE A DIGITAL SIGNATURE? IF YES,
 PLEASE SEND THESE TWO SHEETS TO ME VIA EMAIL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-10-15 Cont ID  
Sent By shill Date 2018-10-15 Time 12:55 Rev Time 0.00
Received By shill Date 2018-10-15 Time 12:39 Sent To  
Notes
2018-10-15 12:55:13****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FROM PREVIOUS LIST:
  
 SHEET CS, FBC B 1004, CLARIFY OCCUPANT LOAD OF 6
 EMPLOYEES, USE GROUP "KITCHEN".
  
 FBC B 302.1, DECLARE AN OCCUPANCY CLASSIFICATION. FBC B
 TABLE 1004.1.2, DECLARE AN OCCUPANT LOAD.
  
 2ND REVIEW - 17 SEATS AND 12 EMPLOYEES ARE NOTED. SEE
 FBC B 1004.1.2, ARE THE SEATS FIXED? IF THEY ARE,
 REVISE PLAN TO NOTE FIXED SEATING, PROVIDE DETAILS, AND
 SHOW COMPLIANCE WITH FBC A 902. IF THEY ARE NOT FIXED,
 REVISE IN ACCORDANCE WITH FBC B TABLE 1004.1.2.
  
 IT APPEARS THAT ARCHITECT IS CALCULATING OCCUPANTS AT
 60SF PER PERSON PLUS SEATS. IT APPEARS THAT 15SF PER
 PERSON SHOULD BE UTILIZED, SEE TABLE B 1004.1.2,
 ASSEMBLY WITHOUT FIXED SEATS. IF ARCHITECT DISAGREES,
 PLEASE CONTACT ME PRIOR TO RESUBMITTING.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-14 Cont ID  
Sent By shill Date 2018-08-14 Time 06:41 Rev Time 0.00
Received By shill Date 2018-08-14 Time 06:41 Sent To  
Notes
2018-08-14 06:45:11****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SHEET CS, FBC B 1004, CLARIFY OCCUPANT LOAD OF 6
 EMPLOYEES, USE GROUP "KITCHEN".
  
 FBC B 302.1, DECLARE AN OCCUPANCY CLASSIFICATION. FBC B
 TABLE 1004.1.2, DECLARE AN OCCUPANT LOAD.
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-10-29 Cont ID  
Sent By jpearson Date 2018-10-29 Time 09:12 Rev Time 0.00
Received By jpearson Date 2018-10-29 Time 08:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-09-28 Cont ID  
Sent By jpearson Date 2018-09-28 Time 14:30 Rev Time 0.00
Received By jpearson Date 2018-09-28 Time 11:06 Sent To  
Notes
2018-09-28 14:34:16CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET
 OF ALL COPIES) IS REQUIRED TO BEAR THE NAME AND BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS
 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-07-30 Cont ID  
Sent By jpearson Date 2018-07-30 Time 14:12 Rev Time 0.00
Received By jpearson Date 2018-07-30 Time 10:21 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2018-10-29 Cont ID  
Sent By jpearson Date 2018-10-29 Time 08:31 Rev Time 0.00
Received By jpearson Date 2018-10-29 Time 08:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-10-30 Cont ID  
Sent By scaldero Date 2018-10-30 Time 11:15 Rev Time 0.00
Received By scaldero Date 2018-10-30 Time 11:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-09-26 Cont ID  
Sent By scaldero Date 2018-09-26 Time 10:04 Rev Time 0.00
Received By scaldero Date 2018-09-26 Time 09:55 Sent To  
Notes
2018-09-26 10:04:27PERMIT #18070421
 FIRE PLAN REVIEW COMMENTS:
  
 APPROVED PROVISO:
  
 1) SHEET CS: OCCUPANT LOAD CONTINUES TO BE INCORRECT.
 PROPOSED NUMBER OF SEATS IS 17, HOWEVER IT STATES THAT
 THE OCCUPANT LOAD IS 12. THE OCCUPANT LOAD SHOULD NOT
 BE LESS THAN THE NUMBER OF SEATS.
 THIS NEEDS TO BE REVIEWED AND CORRECTED. PLEASE PROVIDE
 THE TOTAL OCCUPANT LOAD (EMPLOYEES, SEATED GUESTS,
 WAITING AREA GUESTS, ETC.).
 THIS WILL BE VERIFED IN THE FIELD AND AN OCCUPANT LOAD
 SIGN ISSUED PRIOR TO FINAL INSPECTION.
  
 SUE ELLEN CALDERON
 ASST. FIRE MARSHAL
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-07-25 Cont ID  
Sent By scaldero Date 2018-07-25 Time 11:27 Rev Time 0.00
Received By scaldero Date 2018-07-25 Time 11:16 Sent To  
Notes
2018-07-25 11:27:32PERMIT # 18070421
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) SHEET CS: UPDATE THE CODE LIST TO REFERENCE THE 6TH
 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2015 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS. (2017 LISTED ON SHEET CS)
  
 2) FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected]) OR IN WRITING
 (FAX: 561-804-4774) AND APPROVED BY THE OFFICE OF THE
 FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 3) ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR.
  
 4) EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED
 WITH SIGNS OR STENCILING READING FIRE BARRIER-PROTECT
 ALL OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 5) PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN
 STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE
 MAINTAINED AT ALL TIMES.
  
 6) SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO
 THE FIRE ALARM AND SPRINKLER SYSTEM.
  
 7) WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT
 SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED
 AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE
 MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM
 SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD
 INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY
 BE NEEDED.
  
 8) SHEET CS: OCCUPANT LOAD IS INCORRECT. ONLY ACCOUNTS
 FOR EMPLOYEES (6). THE NUMBER OF SEATS PROVIDED, ALONE,
 IS 17. PLEASE REVIEW AND PROVIDE ACCURATE OCCUPANT
 LOAD, ACCOUNTING FOR SEATS, STAFF, AND QUEING AREA.
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-11-09 Cont ID  
Sent By cpuell Date 2018-11-09 Time 11:43 Rev Time 0.00
Received By cpuell Date 2018-10-17 Time 13:58 Sent To  
Notes
2018-11-08 12:27:13TO ES
2018-10-19 13:58:46B25

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-15 Cont ID  
Sent By shill Date 2018-10-15 Time 12:55 Rev Time 0.00
Received By shill Date 2018-09-18 Time 15:05 Sent To  
Notes
2018-09-19 15:05:33B29

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-14 Cont ID  
Sent By shill Date 2018-08-14 Time 06:45 Rev Time 0.00
Received By shill Date 2018-07-10 Time 10:58 Sent To  
Notes
2018-07-12 10:59:00B23

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-11-07 Cont ID  
Sent By ccole Date 2018-11-07 Time 16:24 Rev Time 0.00
Received By ccole Date 2018-11-07 Time 15:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-09-28 Cont ID  
Sent By ccole Date 2018-09-28 Time 16:42 Rev Time 0.00
Received By ccole Date 2018-09-28 Time 16:29 Sent To  
Notes
2018-09-28 16:49:022ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18070421
 9/28/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2 WAS SIGNED, BUT NOT SEALED BY THE ENGINEER
 OF RECORD- SECTION 61G15-23.002 FAC.
  
 2) M1.0, NEW COMMENT: MINIMUM HEAT AND VENTILATION IS
 REQUIRED FOR THE MANAGER'S OFFICE IN COMPLIANCE WITH
 SECTION 309.1 AND TABLE 403.3.1.1 FBC M. PLEASE REVISE
 THE PLAN TO SHOW COMPLAINCE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-07-17 Cont ID  
Sent By ccole Date 2018-07-17 Time 11:22 Rev Time 0.00
Received By ccole Date 2018-07-16 Time 17:46 Sent To  
Notes
2018-07-17 11:37:491ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18070421
 7/17/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A3.0: PLEASE SHOW THE LOCATION OF THE TURBO
 CHEF OVEN ON THE EQUIPMENT FLOOR PLAN. IT IS #384 IN
 THE SCHEDULE.
  
 2) M1.0: A TYOE II HOOD IS REQUIRED FOR THE NEW TURBO
 CHEF OVEN- SEE SECTION 507.3 FBC M BELOW:
  
 507.3 TYPE II HOODS.
 TYPE II HOODS SHALL BE INSTALLED ABOVE DISHWASHERS AND
 APPLIANCES THAT PRODUCE HEAT OR MOISTURE AND DO NOT
 PRODUCE GREASE OR SMOKE AS A RESULT OF THE COOKING
 PROCESS, EXCEPT WHERE THE HEAT AND MOISTURE LOADS FROM
 SUCH APPLIANCES ARE INCORPORATED INTO THE HVAC SYSTEM
 DESIGN OR INTO THE DESIGN OF A SEPARATE REMOVAL SYSTEM.
 TYPE II HOODS SHALL BE INSTALLED ABOVE ALL APPLIANCES
 THAT PRODUCE PRODUCTS OF COMBUSTION AND DO NOT PRODUCE
 GREASE OR SMOKE AS A RESULT OF THE COOKING PROCESS.
 SPACES CONTAINING COOKING APPLIANCES THAT DO NOT
 REQUIRE TYPE II HOODS SHALL BE PROVIDED WITH EXHAUST AT
 A RATE OF 0.70 CFM PER SQUARE FOOT (0.00033 M3/S). FOR
 THE PURPOSE OF DETERMINING THE FLOOR AREA REQUIRED TO
 BE EXHAUSTED, EACH INDIVIDUAL APPLIANCE THAT IS NOT
 REQUIRED TO BE INSTALLED UNDER A TYPE II HOOD SHALL BE
 CONSIDERED AS OCCUPYING NOT LESS THAN 100 SQUARE FEET
 (9.3 M2). SUCH ADDITIONAL SQUARE FOOTAGE SHALL BE
 PROVIDED WITH EXHAUST AT A RATE OF 0.70 CFM PER SQUARE
 FOOT [.00356 M3/(S ? M2)].
  
 3) M1.0: PROVIDE A DUCT SMOKE DETECTOR IN THE SUPPLY
 SIDE OF THE RTU IN ACCORDANCE WITH SECTION 606.2.1 FBC
 M. PLACE A SYMBOL AT THE REQUIRED LOCATION.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-11-06 Cont ID  
Sent By jesmith Date 2018-11-06 Time 15:21 Rev Time 0.00
Received By jesmith Date 2018-11-06 Time 07:42 Sent To  
Notes
2018-11-06 15:21:47PLUMBING COMMENTS: APPROVED
 PROVISO
 REGARDING THE WATER TREATMENT SYSTEM, ITEM #8 ON THE
 EQUIPMENT/FIXTURE SCHEDULE, DEFERRED SUBMITTALS SHALL
 BE PROVIDED TO THE BUILDING TO THE BUILDING OFFICIAL
 AND APPROVED PRIOR TO FIRST PLUMBING INSPECTION IN
 ACCORDANCE WITH WPB FBC 107.3.4.1.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-10-04 Cont ID  
Sent By jesmith Date 2018-10-04 Time 13:55 Rev Time 0.00
Received By jesmith Date 2018-10-04 Time 13:49 Sent To  
Notes
2018-10-04 13:52:44CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 2ND REVIEW:
 PLUMBING COMMENTS: DENIED
  
 1. RE: PLAN SHEET P4; SHEET WAS SIGNED, BUT NOT SEALED
 BY THE ENGINEER OF RECORD- SECTION 61G15-23.002 FAC.
 2. RE: PLAN SHEET P2.1; PLEASE PROVIDE MANUFACTURE
 SPECIFICATIONS FOR ITEM #8,THE WATER TREATMENT (RO)
 SYSTEM (SECOND REQUEST). WPB FBC 107.2.1
 3. RE: PLAN SHEET P2.1; PROVIDE NOTE AT RPZ INDICATING
 THE RELIEF OUTLET SHALL DISCHARGE THROUGH AN AIR GAP TO
 THE FLOOR SINK IN ACCORDANCE WITH FBC PL 608.13.2. WPB
 FBC 107.2.1
 4. RE: PLAN SHEET P2.1; SCHEMATIC AND FLOOR PLAN SHOWS
 WHAT APPEAR SYMBOLS FOR A CHECK VALVE. ARE THESE CHECK
 VALVES OR BACKFLOW PREVENTORS? IF BACKFLOW PREVENTORS
 PLEASE INDICATE TYPE AND STANDARD SUCH AS ASSE 1022. IF
 IT IS THE INTENT TO PROTECT THE WATER SUPPLY TO ITEMS
 INCLUDING BUT NOT LIMITED TO THE CARBONATED BEVERAGE
 DISPENSERS AND COFFEE MAKERS WITH AN AIR GAP, THEN
 PROVIDE SPECS FOR THE UNIT THAT SHOW IT CAN BE DONE.
 NOTES REQUIRING AN INDIRECT WASTE BE RUN TO A FLOOR
 SINK THROUGH AN AIR GAP DOES NOT ADDRESS BACKFLOW
 CONNECTIONS IN THE WATER SUPPLY. AIR GAPS THAT ADDRESS
 SUCH CONNECTIONS ARE AS NOTED IN FPC PL 608.15.1.
 PLEASE CLARIFY. WPB FBC 107.2.1
 5. RE: PLAN SHEET P2.1; EQUIPMENT SCHEDULE, ITEM #204.
 THE ENGINEER IS TO PROVIDE DETAILS AND SPECS FOR MIXING
 VALVE AND BACKFLOW PREVENTOR INCLUDING PIPING
 ARRANGEMENT AND VALVING IN ACCORDANCE WITH THE
 REQUIREMENTS OF FBC PL AND WPB FBC. WPB FBC 107.2.1
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
 THE COMMENT RESPONSE LETTER NOTED ON THE TRANSMITTAL
 DID NOT APPEAR WHEN THIS REVIEW TOOK PLACE.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-08-10 Cont ID  
Sent By gjohnson Date 2018-08-10 Time 11:38 Rev Time 0.00
Received By gjohnson Date 2018-08-10 Time 08:20 Sent To  
Notes
2018-08-10 13:04:071ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE GREASEE TRAP SIZING CALCULATION INCLUDING
 EXISTING GREAS LOAD AND NEW LOAD TO DETERMINE THAT THE
 EXISTING GREASE INTERCEPTOR'S ARE LARGE ENOUGH. PER WPB
 AMEND TO FBC 107.2.1
  
 2. SHT. P2.1 UNDER FIXTURE/EQUIPMENT SCHEDULE #10 IN
 REMARKS IT IS REFERENCING A GAS GRIDDLE AND CLAMSHELL
 PLEASE CLARIFY. PER WPB AMED TO FBC 107.2.1
  
 3.PLEASE PROVIDE MANUFACTURE SPECIFICATIONS FOR THE
 WATERHEATER, WATER TREATMENT SYSTEM AND THE WATER
 SOFTENER. . PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2018-11-02 Cont ID  
Sent By shill Date 2018-11-02 Time 12:09 Rev Time 0.00
Received By shill Date 2018-11-02 Time 12:09 Sent To  
Notes
2018-11-02 12:09:55DIGITALLY SIGNED ARCHITECTURAL PAGES RECEIVED VIA
 EMAIL, FORWARDED TO FILENET
 (2 PAGES WERE NOT SEALED & DATED)
  

Review Stop Z ZONING
Rev No 3 Status P Date 2018-11-08 Cont ID  
Sent By eschneid Date 2018-11-08 Time 17:09 Rev Time 0.25
Received By eschneid Date 2018-11-08 Time 17:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2018-10-12 Cont ID  
Sent By eschneid Date 2018-10-12 Time 13:44 Rev Time 0.25
Received By eschneid Date 2018-10-12 Time 12:01 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-07-30 Cont ID  
Sent By eschneid Date 2018-07-30 Time 16:44 Rev Time 0.25
Received By eschneid Date 2018-07-30 Time 16:44 Sent To  
Notes
***NONE***