Plan Review Details - Permit 18070416
Plan Review Stops For Permit 18070416
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-07-18 Cont ID  
Sent By rmcdouga Date 2018-07-18 Time 18:46 Rev Time 0.00
Received By rmcdouga Date 2018-07-18 Time 18:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-07-19 Cont ID  
Sent By jleahy Date 2018-07-19 Time 17:49 Rev Time 0.00
Received By jleahy Date 2018-07-19 Time 17:48 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-07-23 Cont ID  
Sent By rmcdouga Date 2018-07-23 Time 13:20 Rev Time 0.00
Received By rmcdouga Date 2018-07-23 Time 13:20 Sent To  
Notes
2018-07-23 13:21:05GAS POOL HEATER IS EXISTING.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-25 Cont ID  
Sent By rmcdouga Date 2018-08-25 Time 08:49 Rev Time 0.00
Received By rmcdouga Date 2018-08-21 Time 14:04 Sent To  
Notes
2018-08-22 14:04:55RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-07-23 Cont ID  
Sent By rmcdouga Date 2018-07-23 Time 15:18 Rev Time 0.00
Received By rmcdouga Date 2018-07-10 Time 11:13 Sent To  
Notes
2018-07-12 11:13:36ROUTED TO ZONING INBOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-08-25 Cont ID  
Sent By rmcdouga Date 2018-08-25 Time 08:48 Rev Time 0.00
Received By rmcdouga Date 2018-08-25 Time 08:48 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-07-23 Cont ID  
Sent By rmcdouga Date 2018-07-23 Time 15:18 Rev Time 0.00
Received By rmcdouga Date 2018-07-23 Time 15:18 Sent To  
Notes
2018-07-23 15:18:40PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY PLUMBING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE TOTAL DYNAMIC HEAD CALCULATOR THAT IS ON SHEET 2
 OF THE PLANS DOES NOT PROVIDE THE ACTUAL FRICTION LOSS
 FOR THE PIPE, FITTINGS AND VALVES. THE FRICTION LOSS
 FOR THE FILTER, HEATER AND SALT SYSTEM WERE NOT
 INCLUDED IN THE CALCULATIONS. FBC 107.2.1
  
 2) IT DOES NOT APPEAR THAT THE SPA WATER IS BEING
 FILTERED. PLEASE CLARIFY. FBC 107.2.1 & FBC-R 4501.20

Review Stop Z ZONING
Rev No 2 Status P Date 2018-08-28 Cont ID  
Sent By mcruz Date 2018-08-28 Time 15:18 Rev Time 0.00
Received By mcruz Date 2018-08-28 Time 15:18 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-07-17 Cont ID  
Sent By mcruz Date 2018-07-17 Time 15:33 Rev Time 0.00
Received By mcruz Date 2018-07-17 Time 15:32 Sent To  
Notes
***NONE***